Certificate holders

Subtype

TTF 35

Certificate Holder
tecalor GmbH
Fürstenbergerstr. 77
37603 Holzminden
Germany
Registration number
011-1W0043
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
TTF 35
Driving energy
n/a
Heat Pump Type
Brine/Water
Refrigerant
R410A
Mass of Refrigerant

10,000 kg

Certification Date
01.11.2016
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 1

Models

TTF 35
Configure model
Model name
TTF 35
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

37.70 kW

34.49 kW

El input

7.98 kW

11.47 kW

COP

4.72

3.01

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

56 dB(A)

56 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

199 %

132 %

Prated

38.00 kW

34.00 kW

SCOP

5.17

3.50

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

38.00 kW

34.10 kW

COP Tj = +2°C

4.78

2.82

Pdh Tj = +7°C

38.50 kW

35.20 kW

COP Tj = +7°C

5.12

3.24

Pdh Tj = 12°C

39.10 kW

37.00 kW

COP Tj = 12°C

5.69

4.08

Pdh Tj = Tbiv

38.00 kW

34.10 kW

COP Tj = Tbiv

4.78

2.82

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

38.00 kW

34.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.78

2.82

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

74 W

74 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

9834 kWh

13033 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

56 dB(A)

56 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

208 %

139 %

Prated

47.00 kW

43.00 kW

SCOP

5.41

3.66

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

38.80 kW

35.80 kW

COP Tj = -7°C

5.38

3.48

Pdh Tj = +2°C

39.10 kW

36.70 kW

COP Tj = +2°C

5.67

3.91

Pdh Tj = +7°C

39.30 kW

37.40 kW

COP Tj = +7°C

5.90

4.32

Pdh Tj = 12°C

39.30 kW

37.90 kW

COP Tj = 12°C

5.94

4.66

Pdh Tj = Tbiv

38.60 kW

34.10 kW

COP Tj = Tbiv

5.26

2.82

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

38.60 kW

34.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.26

2.82

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

74 W

74 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

9.32 kW

9.15 kW

Annual energy consumption Qhe

21594 kWh

28986 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

56 dB(A)

56 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

200 %

133 %

Prated

38.00 kW

34.00 kW

SCOP

5.19

3.52

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

38.10 kW

34.50 kW

COP Tj = -7°C

4.84

2.95

Pdh Tj = +2°C

38.60 kW

35.80 kW

COP Tj = +2°C

5.20

3.50

Pdh Tj = +7°C

39.00 kW

37.50 kW

COP Tj = +7°C

5.96

4.42

Pdh Tj = 12°C

38.00 kW

34.10 kW

COP Tj = 12°C

4.75

2.82

Pdh Tj = Tbiv

38.00 kW

34.10 kW

COP Tj = Tbiv

4.78

2.82

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

38.00 kW

34.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.78

2.82

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

74 W

74 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

15136 kWh

20029 kWh