3,400 kg
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
59.22 kW
54.20 kW
El input
13.72 kW
17.90 kW
COP
4.32
3.02
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
47 dB(A)
47 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
181 %
142 %
Prated
67.00 kW
67.00 kW
SCOP
4.73
3.75
Tbiv
-18 °C
-15 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
60.30 kW
56.20 kW
COP Tj = -7°C
4.62
3.53
Pdh Tj = +2°C
30.60 kW
29.10 kW
COP Tj = +2°C
4.90
4.01
Pdh Tj = +7°C
30.80 kW
29.70 kW
COP Tj = +7°C
5.00
4.29
Pdh Tj = 12°C
30.80 kW
30.10 kW
COP Tj = 12°C
4.80
4.46
Pdh Tj = Tbiv
59.60 kW
55.30 kW
COP Tj = Tbiv
4.45
3.28
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
59.20 kW
54.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.31
3.03
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
65 °C
65 °C
Poff
2 W
2 W
PTO
100 W
100 W
PSB
7 W
7 W
PCK
80 W
80 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.80 kW
12.90 kW
Annual energy consumption Qhe
34918 kWh
43924 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
47 dB(A)
47 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
176 %
138 %
Prated
67.00 kW
67.00 kW
SCOP
4.60
3.65
Tbiv
-7 °C
-5 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
59.50 kW
54.80 kW
COP Tj = -7°C
4.42
3.17
Pdh Tj = +2°C
60.10 kW
56.60 kW
COP Tj = +2°C
4.59
3.62
Pdh Tj = +7°C
30.50 kW
29.20 kW
COP Tj = +7°C
4.87
4.06
Pdh Tj = 12°C
30.80 kW
29.80 kW
COP Tj = 12°C
4.91
4.31
Pdh Tj = Tbiv
59.50 kW
55.20 kW
COP Tj = Tbiv
4.42
3.26
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
59.20 kW
24.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.31
3.03
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
65 °C
65 °C
Poff
2 W
2 W
PTO
120 W
120 W
PSB
7 W
7 W
PCK
80 W
80 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.80 kW
12.90 kW
Annual energy consumption Qhe
30169 kWh
38048 kWh