4,000 kg
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
30.72 kW
29.40 kW
El input
6.92 kW
10.20 kW
COP
4.44
2.90
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
47 dB(A)
47 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
186 %
144 %
Prated
35.00 kW
35.00 kW
SCOP
4.85
3.80
Tbiv
-18 °C
-16 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
31.00 kW
30.10 kW
COP Tj = -7°C
4.75
3.55
Pdh Tj = +2°C
15.60 kW
15.30 kW
COP Tj = +2°C
5.06
4.04
Pdh Tj = +7°C
15.60 kW
15.40 kW
COP Tj = +7°C
5.14
4.39
Pdh Tj = 12°C
15.60 kW
15.50 kW
COP Tj = 12°C
4.86
4.55
Pdh Tj = Tbiv
30.80 kW
29.60 kW
COP Tj = Tbiv
4.55
3.24
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
30.80 kW
19.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.38
2.99
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.98
0.99
WTOL
65 °C
65 °C
Poff
2 W
2 W
PTO
60 W
60 W
PSB
7 W
7 W
PCK
70 W
70 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.20 kW
5.70 kW
Annual energy consumption Qhe
17817 kWh
22770 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
47 dB(A)
47 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
137 %
Prated
35.00 kW
35.00 kW
SCOP
4.65
3.63
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
30.80 kW
29.50 kW
COP Tj = -7°C
4.51
3.15
Pdh Tj = +2°C
30.90 kW
30.20 kW
COP Tj = +2°C
4.69
3.64
Pdh Tj = +7°C
15.60 kW
15.30 kW
COP Tj = +7°C
5.02
4.09
Pdh Tj = 12°C
15.60 kW
15.40 kW
COP Tj = 12°C
5.01
4.40
Pdh Tj = Tbiv
30.80 kW
29.60 kW
COP Tj = Tbiv
4.51
3.23
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
30.80 kW
29.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.38
2.99
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.98
0.99
WTOL
65 °C
65 °C
Poff
2 W
2 W
PTO
80 W
80 W
PSB
7 W
7 W
PCK
70 W
70 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.20 kW
5.70 kW
Annual energy consumption Qhe
15539 kWh
19880 kWh