2,600 kg
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
3.54 kW
3.64 kW
El input
0.69 kW
1.18 kW
COP
5.12
3.08
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
53 dB(A)
53 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
159 %
130 %
Prated
9.30 kW
9.80 kW
SCOP
4.05
3.32
Tbiv
-12 °C
-12 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
5.70 kW
5.90 kW
COP Tj = -7°C
3.33
2.74
Pdh Tj = +2°C
3.40 kW
3.60 kW
COP Tj = +2°C
5.18
4.14
Pdh Tj = +7°C
2.90 kW
2.90 kW
COP Tj = +7°C
5.73
4.70
Pdh Tj = 12°C
3.30 kW
3.30 kW
COP Tj = 12°C
6.44
5.41
Pdh Tj = Tbiv
6.90 kW
7.30 kW
COP Tj = Tbiv
2.99
2.47
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.20 kW
6.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.31
1.84
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
7 W
7 W
PSB
25 W
25 W
PCK
37 W
37 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.10 kW
3.80 kW
Annual energy consumption Qhe
5666 kWh
7239 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
53 dB(A)
53 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190 %
148 %
Prated
8.00 kW
8.30 kW
SCOP
4.82
3.27
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
7.10 kW
7.30 kW
COP Tj = -7°C
3.05
2.39
Pdh Tj = +2°C
4.70 kW
4.70 kW
COP Tj = +2°C
4.57
3.85
Pdh Tj = +7°C
3.10 kW
2.90 kW
COP Tj = +7°C
5.86
4.48
Pdh Tj = 12°C
3.60 kW
3.30 kW
COP Tj = 12°C
7.22
5.30
Pdh Tj = Tbiv
7.10 kW
7.30 kW
COP Tj = Tbiv
2.95
2.28
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.30 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.05
2.39
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.99
0.99
WTOL
65 °C
65 °C
Poff
25 W
25 W
PTO
7 W
7 W
PSB
25 W
25 W
PCK
37 W
37 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.70 kW
0.50 kW
Annual energy consumption Qhe
3409 kWh
4529 kWh