Certificate holders

Subtype

RAS-4WH(V)RP2E

Certificate Holder
Johnson Controls-Hitachi AirConditioning Spain
Ronda Shimizu, 1. Pol. Ind. Can Torrella
08233 Vacarisses, Barcelona
Spain
Registration number
041-K002-73
Certification Body
BRE
Subtype title
RAS-4WH(V)RP2E
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,800 kg

Certification Date
05.09.2025
Testing basis
Heat Pump Keymark Scheme Rules Rev 15
Testing laboratory
Centro de Ensayos, Innovación y Servicios (CEIS), ES
Generate PDF Export model CSV Download certificate
  • Number of models 8

Models

01. RAS-4WHVRP2E + RWM-4R3E - Heating Only
Configure model
Model name
01. RAS-4WHVRP2E + RWM-4R3E - Heating Only
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.00 kW

10.00 kW

El input

2.17 kW

4.35 kW

COP

4.60

2.30

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

53 dB(A)

53 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

129 %

Prated

12.10 kW

12.10 kW

SCOP

4.49

3.29

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.70 kW

10.70 kW

COP Tj = -7°C

2.96

2.15

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.51 kW

6.51 kW

COP Tj = +2°C

4.20

3.06

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.19 kW

4.19 kW

COP Tj = +7°C

6.13

4.56

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.99 kW

3.65 kW

COP Tj = 12°C

8.62

6.26

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

10.70 kW

10.70 kW

COP Tj = Tbiv

2.96

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.10 kW

10.59 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.89

2.02

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

14 W

14 W

PTO

15 W

15 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

1.50 kW

Annual energy consumption Qhe

5561 kWh

7600 kWh

02. RAS-4WHVRP2E + RWM-4R3E - With Cooling Kit
Configure model
Model name
02. RAS-4WHVRP2E + RWM-4R3E - With Cooling Kit
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.00 kW

10.00 kW

El input

2.17 kW

4.35 kW

COP

4.60

2.30

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

9.00 kW

10.00 kW

Cooling capacity

2.95

2.40

EER

3.05

4.16

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

9.00 kW

10.00 kW

SEER

4.76

7.61

Pdc Tj = 35°C

9.00 kW

10.00 kW

EER Tj = 35°C

3.05

4.16

Cdc Tj = 35 °C

0.900

0.900

Pdc Tj = 30°C

6.63 kW

7.40 kW

EER Tj = 30°C

4.22

6.91

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

4.26 kW

6.00 kW

EER Tj = 25°C

5.70

8.49

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

3.60 kW

4.90 kW

EER Tj = 20°C

5.74

12.38

Cdc Tj = 20 °C

0.900

0.900

Poff

14 W

14 W

PTO

15 W

15 W

PSB

14 W

14 W

PCK

0 W

0 W

Annual energy consumption Qce

1134 kWh

789 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

53 dB(A)

53 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

129 %

Prated

12.10 kW

12.10 kW

SCOP

4.54

3.31

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.70 kW

10.70 kW

COP Tj = -7°C

2.96

2.15

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.51 kW

6.51 kW

COP Tj = +2°C

4.20

3.06

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.19 kW

4.19 kW

COP Tj = +7°C

6.13

4.56

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.99 kW

3.65 kW

COP Tj = 12°C

8.62

6.26

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

10.70 kW

10.70 kW

COP Tj = Tbiv

2.96

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.10 kW

10.59 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.89

2.02

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

14 W

14 W

PTO

15 W

15 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

1.50 kW

Annual energy consumption Qhe

5508 kWh

7548 kWh

05. RAS-4WHRP2E + RWM-4R3E - Heating Only
Configure model
Model name
05. RAS-4WHRP2E + RWM-4R3E - Heating Only
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.00 kW

10.00 kW

El input

2.17 kW

4.35 kW

COP

4.60

2.30

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

53 dB(A)

53 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

129 %

Prated

12.10 kW

12.10 kW

SCOP

4.49

3.29

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.70 kW

10.70 kW

COP Tj = -7°C

2.96

2.15

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.51 kW

6.51 kW

COP Tj = +2°C

4.20

3.06

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.19 kW

4.19 kW

COP Tj = +7°C

6.13

4.56

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.99 kW

3.65 kW

COP Tj = 12°C

8.62

6.26

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

10.70 kW

10.70 kW

COP Tj = Tbiv

2.96

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.10 kW

10.59 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.89

2.02

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

14 W

14 W

PTO

15 W

15 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

1.50 kW

Annual energy consumption Qhe

5561 kWh

7600 kWh

06. RAS-4WHRP2E + RWM-4R3E - With Cooling Kit
Configure model
Model name
06. RAS-4WHRP2E + RWM-4R3E - With Cooling Kit
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.00 kW

10.00 kW

El input

2.17 kW

4.35 kW

COP

4.60

2.30

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

9.00 kW

10.00 kW

Cooling capacity

2.95

2.40

EER

3.05

4.16

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

9.00 kW

10.00 kW

SEER

4.76

7.61

Pdc Tj = 35°C

9.00 kW

10.00 kW

EER Tj = 35°C

3.05

4.16

Cdc Tj = 35 °C

0.900

0.900

Pdc Tj = 30°C

6.63 kW

7.40 kW

EER Tj = 30°C

4.22

6.91

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

4.26 kW

6.00 kW

EER Tj = 25°C

5.70

8.49

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

3.60 kW

4.90 kW

EER Tj = 20°C

5.74

12.38

Cdc Tj = 20 °C

0.900

0.900

Poff

14 W

14 W

PTO

15 W

15 W

PSB

14 W

14 W

PCK

0 W

0 W

Annual energy consumption Qce

1134 kWh

789 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

53 dB(A)

53 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

129 %

Prated

12.10 kW

12.10 kW

SCOP

4.54

3.31

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.70 kW

10.70 kW

COP Tj = -7°C

2.96

2.15

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.51 kW

6.51 kW

COP Tj = +2°C

4.20

3.06

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.19 kW

4.19 kW

COP Tj = +7°C

6.13

4.56

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.99 kW

3.65 kW

COP Tj = 12°C

8.62

6.26

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

10.70 kW

10.70 kW

COP Tj = Tbiv

2.96

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.10 kW

10.59 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.89

2.02

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

14 W

14 W

PTO

15 W

15 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

1.50 kW

Annual energy consumption Qhe

5508 kWh

7548 kWh

03. RAS-4WHVRP2E + RWD-4RW3E-220S(-K) - Heating Only
Configure model
Model name
03. RAS-4WHVRP2E + RWD-4RW3E-220S(-K) - Heating Only
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.00 kW

10.00 kW

El input

2.17 kW

4.35 kW

COP

4.60

2.30

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

53 dB(A)

53 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

129 %

Prated

12.10 kW

12.10 kW

SCOP

4.49

3.29

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.70 kW

10.70 kW

COP Tj = -7°C

2.96

2.15

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.51 kW

6.51 kW

COP Tj = +2°C

4.20

3.06

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.19 kW

4.19 kW

COP Tj = +7°C

6.13

4.56

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.99 kW

3.65 kW

COP Tj = 12°C

8.62

6.26

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

10.70 kW

10.70 kW

COP Tj = Tbiv

2.96

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.10 kW

10.59 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.89

2.02

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

14 W

14 W

PTO

15 W

15 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

1.50 kW

Annual energy consumption Qhe

5561 kWh

7600 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

112 %

COP

2.73

Heating up time

1:13 h:min

Standby power input

43.0 W

Reference hot water temperature

52.0 °C

Mixed water at 40°C

273 l

04. RAS-4WHVRP2E + RWD-4RW3E-220S(-K) - With Cooling Kit
Configure model
Model name
04. RAS-4WHVRP2E + RWD-4RW3E-220S(-K) - With Cooling Kit
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.00 kW

10.00 kW

El input

2.17 kW

4.35 kW

COP

4.60

2.30

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

9.00 kW

10.00 kW

Cooling capacity

2.95

2.40

EER

3.05

4.16

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

9.00 kW

10.00 kW

SEER

4.76

7.61

Pdc Tj = 35°C

9.00 kW

10.00 kW

EER Tj = 35°C

3.05

4.16

Cdc Tj = 35 °C

0.900

0.900

Pdc Tj = 30°C

6.63 kW

7.40 kW

EER Tj = 30°C

4.22

6.91

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

4.26 kW

6.00 kW

EER Tj = 25°C

5.70

8.49

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

3.60 kW

4.90 kW

EER Tj = 20°C

5.74

12.38

Cdc Tj = 20 °C

0.900

0.900

Poff

14 W

14 W

PTO

15 W

15 W

PSB

14 W

14 W

PCK

0 W

0 W

Annual energy consumption Qce

1134 kWh

789 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

53 dB(A)

53 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

129 %

Prated

12.10 kW

12.10 kW

SCOP

4.54

3.31

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.70 kW

10.70 kW

COP Tj = -7°C

2.96

2.15

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.51 kW

6.51 kW

COP Tj = +2°C

4.20

3.06

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.19 kW

4.19 kW

COP Tj = +7°C

6.13

4.56

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.99 kW

3.65 kW

COP Tj = 12°C

8.62

6.26

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

10.70 kW

10.70 kW

COP Tj = Tbiv

2.96

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.10 kW

10.59 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.89

2.02

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

14 W

14 W

PTO

15 W

15 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

1.50 kW

Annual energy consumption Qhe

5508 kWh

7548 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

112 %

COP

2.73

Heating up time

1:13 h:min

Standby power input

43.0 W

Reference hot water temperature

52.0 °C

Mixed water at 40°C

273 l

07. RAS-4WHRP2E + RWD-4RW3E-220S(-K) - Heating Only
Configure model
Model name
07. RAS-4WHRP2E + RWD-4RW3E-220S(-K) - Heating Only
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.00 kW

10.00 kW

El input

2.17 kW

4.35 kW

COP

4.60

2.30

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

53 dB(A)

53 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

129 %

Prated

12.10 kW

12.10 kW

SCOP

4.49

3.29

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.70 kW

10.70 kW

COP Tj = -7°C

2.96

2.15

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.51 kW

6.51 kW

COP Tj = +2°C

4.20

3.06

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.19 kW

4.19 kW

COP Tj = +7°C

6.13

4.56

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.99 kW

3.65 kW

COP Tj = 12°C

8.62

6.26

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

10.70 kW

10.70 kW

COP Tj = Tbiv

2.96

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.10 kW

10.59 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.89

2.02

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

14 W

14 W

PTO

15 W

15 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

1.50 kW

Annual energy consumption Qhe

5561 kWh

7600 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

112 %

COP

2.73

Heating up time

1:13 h:min

Standby power input

43.0 W

Reference hot water temperature

52.0 °C

Mixed water at 40°C

273 l

08. RAS-4WHRP2E + RWD-4RW3E-220S(-K) - With Cooling Kit
Configure model
Model name
08. RAS-4WHRP2E + RWD-4RW3E-220S(-K) - With Cooling Kit
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.00 kW

10.00 kW

El input

2.17 kW

4.35 kW

COP

4.60

2.30

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

9.00 kW

10.00 kW

Cooling capacity

2.95

2.40

EER

3.05

4.16

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

9.00 kW

10.00 kW

SEER

4.76

7.61

Pdc Tj = 35°C

9.00 kW

10.00 kW

EER Tj = 35°C

3.05

4.16

Cdc Tj = 35 °C

0.900

0.900

Pdc Tj = 30°C

6.63 kW

7.40 kW

EER Tj = 30°C

4.22

6.91

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

4.26 kW

6.00 kW

EER Tj = 25°C

5.70

8.49

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

3.60 kW

4.90 kW

EER Tj = 20°C

5.74

12.38

Cdc Tj = 20 °C

0.900

0.900

Poff

14 W

14 W

PTO

15 W

15 W

PSB

14 W

14 W

PCK

0 W

0 W

Annual energy consumption Qce

1134 kWh

789 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

53 dB(A)

53 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

129 %

Prated

12.10 kW

12.10 kW

SCOP

4.54

3.31

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.70 kW

10.70 kW

COP Tj = -7°C

2.96

2.15

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.51 kW

6.51 kW

COP Tj = +2°C

4.20

3.06

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.19 kW

4.19 kW

COP Tj = +7°C

6.13

4.56

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.99 kW

3.65 kW

COP Tj = 12°C

8.62

6.26

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

10.70 kW

10.70 kW

COP Tj = Tbiv

2.96

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.10 kW

10.59 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.89

2.02

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

14 W

14 W

PTO

15 W

15 W

PSB

14 W

14 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

1.50 kW

Annual energy consumption Qhe

5508 kWh

7548 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

112 %

COP

2.73

Heating up time

1:13 h:min

Standby power input

43.0 W

Reference hot water temperature

52.0 °C

Mixed water at 40°C

273 l