Certificate holders

Subtype

DAIKIN ALTHERMA LT MONOBLOC 11kW

Certificate Holder
DAIKIN Europe N.V.
Zandvoordestraat 300
B-8400 Oostende
Belgium
Reg. No.
011-1W0259
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Name of testing laboratory
Danish Technological Institute
Subtype title
DAIKIN ALTHERMA LT MONOBLOC 11kW
Driving energy
n/a
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410a
Mass Of Refrigerant

3,400 kg

Certification Date
n/a
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 8

Models

EDLQ011CV3
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

11.20 kW

10.76 kW

El input

2.43 kW

3.97 kW

COP

4.60

2.71

Indoor water flow rate

1.93 m³/h

1.32 m³/h

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

156 %

120 %

Prated

11.00 kW

10.00 kW

SCOP

3.98

3.09

Tbiv

-5 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.90 kW

8.80 kW

COP Tj = -7°C

2.63

1.99

Pdh Tj = +2°C

6.00 kW

5.30 kW

COP Tj = +2°C

4.05

3.24

Pdh Tj = +7°C

5.70 kW

4.50 kW

COP Tj = +7°C

6.77

4.31

Pdh Tj = 12°C

6.50 kW

5.40 kW

COP Tj = 12°C

8.97

6.41

Pdh Tj = Tbiv

9.10 kW

8.80 kW

COP Tj = Tbiv

2.82

1.99

Pdh Tj = TOL

8.80 kW

9.10 kW

COP Tj = TOL

2.34

1.79

Cdh

1.00

1.00

WTOL

35 °C

55 °C

Poff

55 W

55 W

PTO

57 W

57 W

PSB

55 W

55 W

PCK

55 W

55 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

2.40 kW

0.90 kW

Annual energy consumption Qhe

5380 kWh

6260 kWh

EBLQ011CV3
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

11.20 kW

10.76 kW

El input

2.43 kW

3.97 kW

COP

4.60

2.71

Indoor water flow rate

1.93 m³/h

1.32 m³/h

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

156 %

120 %

Prated

11.00 kW

10.00 kW

SCOP

3.98

3.09

Tbiv

-5 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.90 kW

8.80 kW

COP Tj = -7°C

2.63

1.99

Pdh Tj = +2°C

6.00 kW

5.30 kW

COP Tj = +2°C

4.05

3.24

Pdh Tj = +7°C

5.70 kW

4.50 kW

COP Tj = +7°C

6.77

4.31

Pdh Tj = 12°C

6.50 kW

5.40 kW

COP Tj = 12°C

8.97

6.41

Pdh Tj = Tbiv

9.10 kW

8.80 kW

COP Tj = Tbiv

2.82

1.99

Pdh Tj = TOL

8.80 kW

9.10 kW

COP Tj = TOL

2.34

1.79

Cdh

1.00

1.00

WTOL

35 °C

55 °C

Poff

55 W

55 W

PTO

57 W

57 W

PSB

55 W

55 W

PCK

55 W

55 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

2.40 kW

0.90 kW

Annual energy consumption Qhe

5380 kWh

6260 kWh

EBLQ011C3V3
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

11.20 kW

10.76 kW

El input

2.43 kW

3.97 kW

COP

4.60

2.71

Indoor water flow rate

1.93 m³/h

1.32 m³/h

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

156 %

120 %

Prated

11.00 kW

10.00 kW

SCOP

3.98

3.09

Tbiv

-5 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.90 kW

8.80 kW

COP Tj = -7°C

2.63

1.99

Pdh Tj = +2°C

6.00 kW

5.30 kW

COP Tj = +2°C

4.05

3.24

Pdh Tj = +7°C

5.70 kW

4.50 kW

COP Tj = +7°C

6.77

4.31

Pdh Tj = 12°C

6.50 kW

5.40 kW

COP Tj = 12°C

8.97

6.41

Pdh Tj = Tbiv

9.10 kW

8.80 kW

COP Tj = Tbiv

2.82

1.99

Pdh Tj = TOL

8.80 kW

9.10 kW

COP Tj = TOL

2.34

1.79

Cdh

1.00

1.00

WTOL

35 °C

55 °C

Poff

55 W

55 W

PTO

57 W

57 W

PSB

55 W

55 W

PCK

55 W

55 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

2.40 kW

0.90 kW

Annual energy consumption Qhe

5380 kWh

6260 kWh

EBLQ011CW1
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

11.20 kW

10.76 kW

El input

2.43 kW

3.97 kW

COP

4.60

2.71

Indoor water flow rate

1.93 m³/h

1.32 m³/h

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

156 %

120 %

Prated

11.00 kW

10.00 kW

SCOP

3.98

3.09

Tbiv

-5 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.90 kW

8.80 kW

COP Tj = -7°C

2.63

1.99

Pdh Tj = +2°C

6.00 kW

5.30 kW

COP Tj = +2°C

4.05

3.24

Pdh Tj = +7°C

5.70 kW

4.50 kW

COP Tj = +7°C

6.77

4.31

Pdh Tj = 12°C

6.50 kW

5.40 kW

COP Tj = 12°C

8.97

6.41

Pdh Tj = Tbiv

9.10 kW

8.80 kW

COP Tj = Tbiv

2.82

1.99

Pdh Tj = TOL

8.80 kW

9.10 kW

COP Tj = TOL

2.34

1.79

Cdh

1.00

1.00

WTOL

35 °C

55 °C

Poff

55 W

55 W

PTO

57 W

57 W

PSB

55 W

55 W

PCK

55 W

55 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

2.40 kW

0.90 kW

Annual energy consumption Qhe

5380 kWh

6260 kWh

EBLQ011C3W1
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

11.20 kW

10.76 kW

El input

2.43 kW

3.97 kW

COP

4.60

2.71

Indoor water flow rate

1.93 m³/h

1.32 m³/h

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

156 %

120 %

Prated

11.00 kW

10.00 kW

SCOP

3.98

3.09

Tbiv

-5 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.90 kW

8.80 kW

COP Tj = -7°C

2.63

1.99

Pdh Tj = +2°C

6.00 kW

5.30 kW

COP Tj = +2°C

4.05

3.24

Pdh Tj = +7°C

5.70 kW

4.50 kW

COP Tj = +7°C

6.77

4.31

Pdh Tj = 12°C

6.50 kW

5.40 kW

COP Tj = 12°C

8.97

6.41

Pdh Tj = Tbiv

9.10 kW

8.80 kW

COP Tj = Tbiv

2.82

1.99

Pdh Tj = TOL

8.80 kW

9.10 kW

COP Tj = TOL

2.34

1.79

Cdh

1.00

1.00

WTOL

35 °C

55 °C

Poff

55 W

55 W

PTO

57 W

57 W

PSB

55 W

55 W

PCK

55 W

55 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

2.40 kW

0.90 kW

Annual energy consumption Qhe

5380 kWh

6260 kWh

EDLQ011C3V3
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

11.20 kW

10.76 kW

El input

2.43 kW

3.97 kW

COP

4.60

2.71

Indoor water flow rate

1.93 m³/h

1.32 m³/h

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

156 %

120 %

Prated

11.00 kW

10.00 kW

SCOP

3.98

3.09

Tbiv

-5 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.90 kW

8.80 kW

COP Tj = -7°C

2.63

1.99

Pdh Tj = +2°C

6.00 kW

5.30 kW

COP Tj = +2°C

4.05

3.24

Pdh Tj = +7°C

5.70 kW

4.50 kW

COP Tj = +7°C

6.77

4.31

Pdh Tj = 12°C

6.50 kW

5.40 kW

COP Tj = 12°C

8.97

6.41

Pdh Tj = Tbiv

9.10 kW

8.80 kW

COP Tj = Tbiv

2.82

1.99

Pdh Tj = TOL

8.80 kW

9.10 kW

COP Tj = TOL

2.34

1.79

Cdh

1.00

1.00

WTOL

35 °C

55 °C

Poff

55 W

55 W

PTO

57 W

57 W

PSB

55 W

55 W

PCK

55 W

55 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

2.40 kW

0.90 kW

Annual energy consumption Qhe

5380 kWh

6260 kWh

EDLQ011CW1
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

11.20 kW

10.76 kW

El input

2.43 kW

3.97 kW

COP

4.60

2.71

Indoor water flow rate

1.93 m³/h

1.32 m³/h

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

156 %

120 %

Prated

11.00 kW

10.00 kW

SCOP

3.98

3.09

Tbiv

-5 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.90 kW

8.80 kW

COP Tj = -7°C

2.63

1.99

Pdh Tj = +2°C

6.00 kW

5.30 kW

COP Tj = +2°C

4.05

3.24

Pdh Tj = +7°C

5.70 kW

4.50 kW

COP Tj = +7°C

6.77

4.31

Pdh Tj = 12°C

6.50 kW

5.40 kW

COP Tj = 12°C

8.97

6.41

Pdh Tj = Tbiv

9.10 kW

8.80 kW

COP Tj = Tbiv

2.82

1.99

Pdh Tj = TOL

8.80 kW

9.10 kW

COP Tj = TOL

2.34

1.79

Cdh

1.00

1.00

WTOL

35 °C

55 °C

Poff

55 W

55 W

PTO

57 W

57 W

PSB

55 W

55 W

PCK

55 W

55 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

2.40 kW

0.90 kW

Annual energy consumption Qhe

5380 kWh

6260 kWh

EDLQ011C3W1
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

11.20 kW

10.76 kW

El input

2.43 kW

3.97 kW

COP

4.60

2.71

Indoor water flow rate

1.93 m³/h

1.32 m³/h

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

156 %

120 %

Prated

11.00 kW

10.00 kW

SCOP

3.98

3.09

Tbiv

-5 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.90 kW

8.80 kW

COP Tj = -7°C

2.63

1.99

Pdh Tj = +2°C

6.00 kW

5.30 kW

COP Tj = +2°C

4.05

3.24

Pdh Tj = +7°C

5.70 kW

4.50 kW

COP Tj = +7°C

6.77

4.31

Pdh Tj = 12°C

6.50 kW

5.40 kW

COP Tj = 12°C

8.97

6.41

Pdh Tj = Tbiv

9.10 kW

8.80 kW

COP Tj = Tbiv

2.82

1.99

Pdh Tj = TOL

8.80 kW

9.10 kW

COP Tj = TOL

2.34

1.79

Cdh

1.00

1.00

WTOL

35 °C

55 °C

Poff

55 W

55 W

PTO

57 W

57 W

PSB

55 W

55 W

PCK

55 W

55 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

2.40 kW

0.90 kW

Annual energy consumption Qhe

5380 kWh

6260 kWh