1,250 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
10.02 kW
10.33 kW
El input
1.99 kW
3.15 kW
COP
5.03
3.27
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
192 %
147 %
Prated
10.10 kW
10.19 kW
SCOP
4.87
3.75
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.94 kW
9.02 kW
COP Tj = -7°C
3.01
2.20
Cdh Tj = -7 °C
0.990
1.000
Pdh Tj = +2°C
5.55 kW
5.73 kW
COP Tj = +2°C
4.68
3.60
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.67 kW
5.47 kW
COP Tj = +7°C
6.62
5.28
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
6.62 kW
6.51 kW
COP Tj = 12°C
9.04
7.37
Cdh Tj = +12 °C
0.980
0.980
Pdh Tj = Tbiv
8.94 kW
9.02 kW
COP Tj = Tbiv
3.01
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.50 kW
8.18 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.81
1.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
39 W
39 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.60 kW
2.01 kW
Annual energy consumption Qhe
4289 kWh
5608 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
10.02 kW
10.33 kW
El input
1.99 kW
3.15 kW
COP
5.03
3.27
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
196 %
148 %
Prated
10.15 kW
10.30 kW
SCOP
4.98
3.77
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.98 kW
9.11 kW
COP Tj = -7°C
2.95
2.12
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
5.54 kW
5.66 kW
COP Tj = +2°C
4.89
3.75
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.66 kW
5.32 kW
COP Tj = +7°C
6.76
4.94
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
6.36 kW
6.49 kW
COP Tj = 12°C
9.05
7.44
Cdh Tj = +12 °C
0.980
0.980
Pdh Tj = Tbiv
8.98 kW
9.11 kW
COP Tj = Tbiv
2.95
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.37 kW
8.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.72
1.93
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
75 °C
75 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
39 W
39 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.78 kW
1.49 kW
Annual energy consumption Qhe
4210 kWh
5648 kWh