2,000 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.50 kW
8.14 kW
El input
1.60 kW
2.46 kW
COP
5.31
3.31
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.24 kW
6.77 kW
ηs
215 %
159 %
Prated
7.24 kW
6.77 kW
SCOP
5.46
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.20 kW
6.80 kW
COP Tj = +2°C
4.50
2.90
Cdh Tj = +2 °C
0.950
0.970
Pdh Tj = +7°C
7.40 kW
7.00 kW
COP Tj = +7°C
5.70
3.80
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
8.60 kW
8.40 kW
COP Tj = 12°C
7.10
5.60
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
7.20 kW
6.80 kW
COP Tj = Tbiv
4.50
2.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.20 kW
6.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.50
2.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.950
0.950
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1772 kWh
2236 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
17.13 kW
16.89 kW
ηs
153 %
127 %
Prated
17.13 kW
16.89 kW
SCOP
3.90
3.26
Tbiv
-9 °C
-9 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
10.30 kW
10.20 kW
COP Tj = -7°C
3.30
2.70
Cdh Tj = -7 °C
0.970
0.980
Pdh Tj = +2°C
6.50 kW
6.30 kW
COP Tj = +2°C
5.50
4.40
Cdh Tj = +2 °C
0.930
0.940
Pdh Tj = +7°C
7.50 kW
7.40 kW
COP Tj = +7°C
6.50
5.40
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
8.60 kW
8.60 kW
COP Tj = 12°C
7.50
6.40
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.30 kW
11.10 kW
COP Tj = Tbiv
2.90
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
17.13 kW
16.89 kW
Annual energy consumption Qhe
10819 kWh
12788 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
13.29 kW
12.09 kW
ηs
190 %
153 %
Prated
13.29 kW
12.09 kW
SCOP
4.85
3.92
Tbiv
-7 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.50 kW
10.90 kW
COP Tj = -7°C
2.80
2.30
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.10 kW
6.40 kW
COP Tj = +2°C
5.00
3.90
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
7.40 kW
7.20 kW
COP Tj = +7°C
6.20
5.00
Cdh Tj = +7 °C
0.991
0.992
Pdh Tj = 12°C
8.70 kW
8.60 kW
COP Tj = 12°C
7.70
6.40
Cdh Tj = +12 °C
0.990
0.992
Pdh Tj = Tbiv
11.50 kW
11.40 kW
COP Tj = Tbiv
2.80
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.60 kW
10.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.10
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.74 kW
1.25 kW
Annual energy consumption Qhe
5673 kWh
6594 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.00 kW
8.55 kW
El input
1.71 kW
2.59 kW
COP
5.27
3.31
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.22 kW
6.73 kW
ηs
215 %
159 %
Prated
7.22 kW
6.73 kW
SCOP
5.44
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.20 kW
6.70 kW
COP Tj = +2°C
4.40
2.80
Cdh Tj = +2 °C
0.970
0.970
Pdh Tj = +7°C
7.30 kW
6.90 kW
COP Tj = +7°C
5.60
3.80
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
8.60 kW
8.40 kW
COP Tj = 12°C
7.20
5.60
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
7.20 kW
6.70 kW
COP Tj = Tbiv
4.40
2.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.20 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
2.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.950
0.950
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1773 kWh
2224 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
18.67 kW
18.53 kW
ηs
147 %
121 %
Prated
18.67 kW
18.53 kW
SCOP
3.75
3.10
Tbiv
-8 °C
-8 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
11.20 kW
11.10 kW
COP Tj = -7°C
3.20
2.60
Cdh Tj = -7 °C
0.980
0.980
Pdh Tj = +2°C
6.90 kW
6.60 kW
COP Tj = +2°C
5.40
4.40
Cdh Tj = +2 °C
0.940
0.950
Pdh Tj = +7°C
7.50 kW
7.30 kW
COP Tj = +7°C
6.50
5.50
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
8.50 kW
8.60 kW
COP Tj = 12°C
7.40
6.50
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.80 kW
11.70 kW
COP Tj = Tbiv
3.00
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
18.67 kW
18.53 kW
Annual energy consumption Qhe
12265 kWh
14724 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
13.61 kW
13.18 kW
ηs
191 %
152 %
Prated
13.61 kW
13.18 kW
SCOP
4.86
3.89
Tbiv
-7 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
11.90 kW
COP Tj = -7°C
2.80
2.20
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.20 kW
6.80 kW
COP Tj = +2°C
5.00
3.90
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
7.50 kW
7.20 kW
COP Tj = +7°C
6.30
5.10
Cdh Tj = +7 °C
0.991
0.992
Pdh Tj = 12°C
8.70 kW
8.50 kW
COP Tj = 12°C
7.70
6.40
Cdh Tj = +12 °C
0.990
0.992
Pdh Tj = Tbiv
12.00 kW
12.10 kW
COP Tj = Tbiv
2.80
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.00 kW
11.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.57 kW
1.72 kW
Annual energy consumption Qhe
5897 kWh
7019 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.50 kW
8.14 kW
El input
1.60 kW
2.46 kW
COP
5.31
3.31
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.24 kW
6.77 kW
ηs
215 %
159 %
Prated
7.24 kW
6.77 kW
SCOP
5.46
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.20 kW
6.80 kW
COP Tj = +2°C
4.50
2.90
Cdh Tj = +2 °C
0.950
0.970
Pdh Tj = +7°C
7.40 kW
7.00 kW
COP Tj = +7°C
5.70
3.80
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
8.60 kW
8.40 kW
COP Tj = 12°C
7.10
5.60
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
7.20 kW
6.80 kW
COP Tj = Tbiv
4.50
2.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.20 kW
6.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.50
2.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.950
0.950
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1772 kWh
2236 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
17.13 kW
16.89 kW
ηs
153 %
127 %
Prated
17.13 kW
16.89 kW
SCOP
3.90
3.26
Tbiv
-9 °C
-9 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
10.30 kW
10.20 kW
COP Tj = -7°C
3.30
2.70
Cdh Tj = -7 °C
0.970
0.980
Pdh Tj = +2°C
6.50 kW
6.30 kW
COP Tj = +2°C
5.50
4.40
Cdh Tj = +2 °C
0.930
0.940
Pdh Tj = +7°C
7.50 kW
7.40 kW
COP Tj = +7°C
6.50
5.40
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
8.60 kW
8.60 kW
COP Tj = 12°C
7.50
6.40
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.30 kW
11.10 kW
COP Tj = Tbiv
2.90
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
17.13 kW
16.89 kW
Annual energy consumption Qhe
10819 kWh
12788 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
13.29 kW
12.09 kW
ηs
190 %
153 %
Prated
13.29 kW
12.09 kW
SCOP
4.85
3.92
Tbiv
-7 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.50 kW
10.90 kW
COP Tj = -7°C
2.80
2.30
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.10 kW
6.40 kW
COP Tj = +2°C
5.00
3.90
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
7.40 kW
7.20 kW
COP Tj = +7°C
6.20
5.00
Cdh Tj = +7 °C
0.991
0.992
Pdh Tj = 12°C
8.70 kW
8.60 kW
COP Tj = 12°C
7.70
6.40
Cdh Tj = +12 °C
0.990
0.992
Pdh Tj = Tbiv
11.50 kW
11.40 kW
COP Tj = Tbiv
2.80
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.60 kW
10.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.10
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.74 kW
1.25 kW
Annual energy consumption Qhe
5673 kWh
6594 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.00 kW
8.55 kW
El input
1.71 kW
2.59 kW
COP
5.27
3.31
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.22 kW
6.73 kW
ηs
215 %
159 %
Prated
7.22 kW
6.73 kW
SCOP
5.44
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.20 kW
6.70 kW
COP Tj = +2°C
4.40
2.80
Cdh Tj = +2 °C
0.970
0.970
Pdh Tj = +7°C
7.30 kW
6.90 kW
COP Tj = +7°C
5.60
3.80
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
8.60 kW
8.40 kW
COP Tj = 12°C
7.20
5.60
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
7.20 kW
6.70 kW
COP Tj = Tbiv
4.40
2.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.20 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
2.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.950
0.950
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1773 kWh
2224 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
18.67 kW
18.53 kW
ηs
147 %
121 %
Prated
18.67 kW
18.53 kW
SCOP
3.75
3.10
Tbiv
-8 °C
-8 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
11.20 kW
11.10 kW
COP Tj = -7°C
3.20
2.60
Cdh Tj = -7 °C
0.980
0.980
Pdh Tj = +2°C
6.90 kW
6.60 kW
COP Tj = +2°C
5.40
4.40
Cdh Tj = +2 °C
0.940
0.950
Pdh Tj = +7°C
7.50 kW
7.30 kW
COP Tj = +7°C
6.50
5.50
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
8.50 kW
8.60 kW
COP Tj = 12°C
7.40
6.50
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.80 kW
11.70 kW
COP Tj = Tbiv
3.00
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
18.67 kW
18.53 kW
Annual energy consumption Qhe
12265 kWh
14724 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
13.61 kW
13.18 kW
ηs
191 %
152 %
Prated
13.61 kW
13.18 kW
SCOP
4.86
3.89
Tbiv
-7 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
11.90 kW
COP Tj = -7°C
2.80
2.20
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.20 kW
6.80 kW
COP Tj = +2°C
5.00
3.90
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
7.50 kW
7.20 kW
COP Tj = +7°C
6.30
5.10
Cdh Tj = +7 °C
0.991
0.992
Pdh Tj = 12°C
8.70 kW
8.50 kW
COP Tj = 12°C
7.70
6.40
Cdh Tj = +12 °C
0.990
0.992
Pdh Tj = Tbiv
12.00 kW
12.10 kW
COP Tj = Tbiv
2.80
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.00 kW
11.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.57 kW
1.72 kW
Annual energy consumption Qhe
5897 kWh
7019 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.50 kW
8.14 kW
El input
1.60 kW
2.46 kW
COP
5.31
3.31
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.24 kW
6.77 kW
ηs
215 %
159 %
Prated
7.24 kW
6.77 kW
SCOP
5.46
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.20 kW
6.80 kW
COP Tj = +2°C
4.50
2.90
Cdh Tj = +2 °C
0.950
0.970
Pdh Tj = +7°C
7.40 kW
7.00 kW
COP Tj = +7°C
5.70
3.80
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
8.60 kW
8.40 kW
COP Tj = 12°C
7.10
5.60
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
7.20 kW
6.80 kW
COP Tj = Tbiv
4.50
2.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.20 kW
6.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.50
2.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.950
0.950
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1772 kWh
2236 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
17.13 kW
16.89 kW
ηs
153 %
127 %
Prated
17.13 kW
16.89 kW
SCOP
3.90
3.26
Tbiv
-9 °C
-9 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
10.30 kW
10.20 kW
COP Tj = -7°C
3.30
2.70
Cdh Tj = -7 °C
0.970
0.980
Pdh Tj = +2°C
6.50 kW
6.30 kW
COP Tj = +2°C
5.50
4.40
Cdh Tj = +2 °C
0.930
0.940
Pdh Tj = +7°C
7.50 kW
7.40 kW
COP Tj = +7°C
6.50
5.40
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
8.60 kW
8.60 kW
COP Tj = 12°C
7.50
6.40
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.30 kW
11.10 kW
COP Tj = Tbiv
2.90
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
17.13 kW
16.89 kW
Annual energy consumption Qhe
10819 kWh
12788 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
13.29 kW
12.09 kW
ηs
190 %
153 %
Prated
13.29 kW
12.09 kW
SCOP
4.85
3.92
Tbiv
-7 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.50 kW
10.90 kW
COP Tj = -7°C
2.80
2.30
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.10 kW
6.40 kW
COP Tj = +2°C
5.00
3.90
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
7.40 kW
7.20 kW
COP Tj = +7°C
6.20
5.00
Cdh Tj = +7 °C
0.991
0.992
Pdh Tj = 12°C
8.70 kW
8.60 kW
COP Tj = 12°C
7.70
6.40
Cdh Tj = +12 °C
0.990
0.992
Pdh Tj = Tbiv
11.50 kW
11.40 kW
COP Tj = Tbiv
2.80
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.60 kW
10.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.10
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.74 kW
1.25 kW
Annual energy consumption Qhe
5673 kWh
6594 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.00 kW
8.55 kW
El input
1.71 kW
2.59 kW
COP
5.27
3.31
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.22 kW
6.73 kW
ηs
215 %
159 %
Prated
7.22 kW
6.73 kW
SCOP
5.44
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.20 kW
6.70 kW
COP Tj = +2°C
4.40
2.80
Cdh Tj = +2 °C
0.970
0.970
Pdh Tj = +7°C
7.30 kW
6.90 kW
COP Tj = +7°C
5.60
3.80
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
8.60 kW
8.40 kW
COP Tj = 12°C
7.20
5.60
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
7.20 kW
6.70 kW
COP Tj = Tbiv
4.40
2.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.20 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
2.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.950
0.950
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1773 kWh
2224 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
18.67 kW
18.53 kW
ηs
147 %
121 %
Prated
18.67 kW
18.53 kW
SCOP
3.75
3.10
Tbiv
-8 °C
-8 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
11.20 kW
11.10 kW
COP Tj = -7°C
3.20
2.60
Cdh Tj = -7 °C
0.980
0.980
Pdh Tj = +2°C
6.90 kW
6.60 kW
COP Tj = +2°C
5.40
4.40
Cdh Tj = +2 °C
0.940
0.950
Pdh Tj = +7°C
7.50 kW
7.30 kW
COP Tj = +7°C
6.50
5.50
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
8.50 kW
8.60 kW
COP Tj = 12°C
7.40
6.50
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.80 kW
11.70 kW
COP Tj = Tbiv
3.00
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
18.67 kW
18.53 kW
Annual energy consumption Qhe
12265 kWh
14724 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
13.61 kW
13.18 kW
ηs
191 %
152 %
Prated
13.61 kW
13.18 kW
SCOP
4.86
3.89
Tbiv
-7 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
11.90 kW
COP Tj = -7°C
2.80
2.20
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.20 kW
6.80 kW
COP Tj = +2°C
5.00
3.90
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
7.50 kW
7.20 kW
COP Tj = +7°C
6.30
5.10
Cdh Tj = +7 °C
0.991
0.992
Pdh Tj = 12°C
8.70 kW
8.50 kW
COP Tj = 12°C
7.70
6.40
Cdh Tj = +12 °C
0.990
0.992
Pdh Tj = Tbiv
12.00 kW
12.10 kW
COP Tj = Tbiv
2.80
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.00 kW
11.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.57 kW
1.72 kW
Annual energy consumption Qhe
5897 kWh
7019 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.50 kW
8.14 kW
El input
1.60 kW
2.46 kW
COP
5.31
3.31
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.24 kW
6.77 kW
ηs
215 %
159 %
Prated
7.24 kW
6.77 kW
SCOP
5.46
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.20 kW
6.80 kW
COP Tj = +2°C
4.50
2.90
Cdh Tj = +2 °C
0.950
0.970
Pdh Tj = +7°C
7.40 kW
7.00 kW
COP Tj = +7°C
5.70
3.80
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
8.60 kW
8.40 kW
COP Tj = 12°C
7.10
5.60
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
7.20 kW
6.80 kW
COP Tj = Tbiv
4.50
2.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.20 kW
6.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.50
2.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.950
0.950
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1772 kWh
2236 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
17.13 kW
16.89 kW
ηs
153 %
127 %
Prated
17.13 kW
16.89 kW
SCOP
3.90
3.26
Tbiv
-9 °C
-9 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
10.30 kW
10.20 kW
COP Tj = -7°C
3.30
2.70
Cdh Tj = -7 °C
0.970
0.980
Pdh Tj = +2°C
6.50 kW
6.30 kW
COP Tj = +2°C
5.50
4.40
Cdh Tj = +2 °C
0.930
0.940
Pdh Tj = +7°C
7.50 kW
7.40 kW
COP Tj = +7°C
6.50
5.40
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
8.60 kW
8.60 kW
COP Tj = 12°C
7.50
6.40
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.30 kW
11.10 kW
COP Tj = Tbiv
2.90
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
17.13 kW
16.89 kW
Annual energy consumption Qhe
10819 kWh
12788 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
13.29 kW
12.09 kW
ηs
190 %
153 %
Prated
13.29 kW
12.09 kW
SCOP
4.85
3.92
Tbiv
-7 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.50 kW
10.90 kW
COP Tj = -7°C
2.80
2.30
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.10 kW
6.40 kW
COP Tj = +2°C
5.00
3.90
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
7.40 kW
7.20 kW
COP Tj = +7°C
6.20
5.00
Cdh Tj = +7 °C
0.991
0.992
Pdh Tj = 12°C
8.70 kW
8.60 kW
COP Tj = 12°C
7.70
6.40
Cdh Tj = +12 °C
0.990
0.992
Pdh Tj = Tbiv
11.50 kW
11.40 kW
COP Tj = Tbiv
2.80
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.60 kW
10.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.10
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.74 kW
1.25 kW
Annual energy consumption Qhe
5673 kWh
6594 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.00 kW
8.55 kW
El input
1.71 kW
2.59 kW
COP
5.27
3.31
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.22 kW
6.73 kW
ηs
215 %
159 %
Prated
7.22 kW
6.73 kW
SCOP
5.44
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.20 kW
6.70 kW
COP Tj = +2°C
4.40
2.80
Cdh Tj = +2 °C
0.970
0.970
Pdh Tj = +7°C
7.30 kW
6.90 kW
COP Tj = +7°C
5.60
3.80
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
8.60 kW
8.40 kW
COP Tj = 12°C
7.20
5.60
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
7.20 kW
6.70 kW
COP Tj = Tbiv
4.40
2.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.20 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
2.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.950
0.950
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1773 kWh
2224 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
18.67 kW
18.53 kW
ηs
147 %
121 %
Prated
18.67 kW
18.53 kW
SCOP
3.75
3.10
Tbiv
-8 °C
-8 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
11.20 kW
11.10 kW
COP Tj = -7°C
3.20
2.60
Cdh Tj = -7 °C
0.980
0.980
Pdh Tj = +2°C
6.90 kW
6.60 kW
COP Tj = +2°C
5.40
4.40
Cdh Tj = +2 °C
0.940
0.950
Pdh Tj = +7°C
7.50 kW
7.30 kW
COP Tj = +7°C
6.50
5.50
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
8.50 kW
8.60 kW
COP Tj = 12°C
7.40
6.50
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.80 kW
11.70 kW
COP Tj = Tbiv
3.00
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
18.67 kW
18.53 kW
Annual energy consumption Qhe
12265 kWh
14724 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
13.61 kW
13.18 kW
ηs
191 %
152 %
Prated
13.61 kW
13.18 kW
SCOP
4.86
3.89
Tbiv
-7 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
11.90 kW
COP Tj = -7°C
2.80
2.20
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.20 kW
6.80 kW
COP Tj = +2°C
5.00
3.90
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
7.50 kW
7.20 kW
COP Tj = +7°C
6.30
5.10
Cdh Tj = +7 °C
0.991
0.992
Pdh Tj = 12°C
8.70 kW
8.50 kW
COP Tj = 12°C
7.70
6.40
Cdh Tj = +12 °C
0.990
0.992
Pdh Tj = Tbiv
12.00 kW
12.10 kW
COP Tj = Tbiv
2.80
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.00 kW
11.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.57 kW
1.72 kW
Annual energy consumption Qhe
5897 kWh
7019 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.50 kW
8.14 kW
El input
1.60 kW
2.46 kW
COP
5.31
3.31
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.24 kW
6.77 kW
ηs
215 %
159 %
Prated
7.24 kW
6.77 kW
SCOP
5.46
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.20 kW
6.80 kW
COP Tj = +2°C
4.50
2.90
Cdh Tj = +2 °C
0.950
0.970
Pdh Tj = +7°C
7.40 kW
7.00 kW
COP Tj = +7°C
5.70
3.80
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
8.60 kW
8.40 kW
COP Tj = 12°C
7.10
5.60
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
7.20 kW
6.80 kW
COP Tj = Tbiv
4.50
2.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.20 kW
6.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.50
2.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.950
0.950
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1772 kWh
2236 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
17.13 kW
16.89 kW
ηs
153 %
127 %
Prated
17.13 kW
16.89 kW
SCOP
3.90
3.26
Tbiv
-9 °C
-9 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
10.30 kW
10.20 kW
COP Tj = -7°C
3.30
2.70
Cdh Tj = -7 °C
0.970
0.980
Pdh Tj = +2°C
6.50 kW
6.30 kW
COP Tj = +2°C
5.50
4.40
Cdh Tj = +2 °C
0.930
0.940
Pdh Tj = +7°C
7.50 kW
7.40 kW
COP Tj = +7°C
6.50
5.40
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
8.60 kW
8.60 kW
COP Tj = 12°C
7.50
6.40
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.30 kW
11.10 kW
COP Tj = Tbiv
2.90
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
17.13 kW
16.89 kW
Annual energy consumption Qhe
10819 kWh
12788 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
13.29 kW
12.09 kW
ηs
190 %
153 %
Prated
13.29 kW
12.09 kW
SCOP
4.85
3.92
Tbiv
-7 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.50 kW
10.90 kW
COP Tj = -7°C
2.80
2.30
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.10 kW
6.40 kW
COP Tj = +2°C
5.00
3.90
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
7.40 kW
7.20 kW
COP Tj = +7°C
6.20
5.00
Cdh Tj = +7 °C
0.991
0.992
Pdh Tj = 12°C
8.70 kW
8.60 kW
COP Tj = 12°C
7.70
6.40
Cdh Tj = +12 °C
0.990
0.992
Pdh Tj = Tbiv
11.50 kW
11.40 kW
COP Tj = Tbiv
2.80
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.60 kW
10.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.10
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.74 kW
1.25 kW
Annual energy consumption Qhe
5673 kWh
6594 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
128 %
COP
3.2
Heating up time
01:12 h:min
Standby power input
52 W
Reference hot water temperature
53.7 °C
Mixed water at 40°C
260 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
98 %
COP
2.44
Heating up time
01:16 h:min
Standby power input
83 W
Reference hot water temperature
53.6 °C
Mixed water at 40°C
260 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
116 %
COP
2.89
Heating up time
01:14 h:min
Standby power input
55.5 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
260 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.00 kW
8.55 kW
El input
1.71 kW
2.59 kW
COP
5.27
3.31
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.22 kW
6.73 kW
ηs
215 %
159 %
Prated
7.22 kW
6.73 kW
SCOP
5.44
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.20 kW
6.70 kW
COP Tj = +2°C
4.40
2.80
Cdh Tj = +2 °C
0.970
0.970
Pdh Tj = +7°C
7.30 kW
6.90 kW
COP Tj = +7°C
5.60
3.80
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
8.60 kW
8.40 kW
COP Tj = 12°C
7.20
5.60
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
7.20 kW
6.70 kW
COP Tj = Tbiv
4.40
2.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.20 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
2.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.950
0.950
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1773 kWh
2224 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
18.67 kW
18.53 kW
ηs
147 %
121 %
Prated
18.67 kW
18.53 kW
SCOP
3.75
3.10
Tbiv
-8 °C
-8 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
11.20 kW
11.10 kW
COP Tj = -7°C
3.20
2.60
Cdh Tj = -7 °C
0.980
0.980
Pdh Tj = +2°C
6.90 kW
6.60 kW
COP Tj = +2°C
5.40
4.40
Cdh Tj = +2 °C
0.940
0.950
Pdh Tj = +7°C
7.50 kW
7.30 kW
COP Tj = +7°C
6.50
5.50
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
8.50 kW
8.60 kW
COP Tj = 12°C
7.40
6.50
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.80 kW
11.70 kW
COP Tj = Tbiv
3.00
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
18.67 kW
18.53 kW
Annual energy consumption Qhe
12265 kWh
14724 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
13.61 kW
13.18 kW
ηs
191 %
152 %
Prated
13.61 kW
13.18 kW
SCOP
4.86
3.89
Tbiv
-7 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
11.90 kW
COP Tj = -7°C
2.80
2.20
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.20 kW
6.80 kW
COP Tj = +2°C
5.00
3.90
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
7.50 kW
7.20 kW
COP Tj = +7°C
6.30
5.10
Cdh Tj = +7 °C
0.991
0.992
Pdh Tj = 12°C
8.70 kW
8.50 kW
COP Tj = 12°C
7.70
6.40
Cdh Tj = +12 °C
0.990
0.992
Pdh Tj = Tbiv
12.00 kW
12.10 kW
COP Tj = Tbiv
2.80
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.00 kW
11.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.57 kW
1.72 kW
Annual energy consumption Qhe
5897 kWh
7019 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
128 %
COP
3.2
Heating up time
01:12 h:min
Standby power input
52 W
Reference hot water temperature
53.7 °C
Mixed water at 40°C
260 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
98 %
COP
2.44
Heating up time
01:16 h:min
Standby power input
83 W
Reference hot water temperature
53.6 °C
Mixed water at 40°C
260 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
116 %
COP
2.89
Heating up time
01:14 h:min
Standby power input
55.5 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
260 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.50 kW
8.14 kW
El input
1.60 kW
2.46 kW
COP
5.31
3.31
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.24 kW
6.77 kW
ηs
215 %
159 %
Prated
7.24 kW
6.77 kW
SCOP
5.46
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.20 kW
6.80 kW
COP Tj = +2°C
4.50
2.90
Cdh Tj = +2 °C
0.950
0.970
Pdh Tj = +7°C
7.40 kW
7.00 kW
COP Tj = +7°C
5.70
3.80
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
8.60 kW
8.40 kW
COP Tj = 12°C
7.10
5.60
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
7.20 kW
6.80 kW
COP Tj = Tbiv
4.50
2.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.20 kW
6.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.50
2.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.950
0.950
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1772 kWh
2236 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
17.13 kW
16.89 kW
ηs
153 %
127 %
Prated
17.13 kW
16.89 kW
SCOP
3.90
3.26
Tbiv
-9 °C
-9 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
10.30 kW
10.20 kW
COP Tj = -7°C
3.30
2.70
Cdh Tj = -7 °C
0.970
0.980
Pdh Tj = +2°C
6.50 kW
6.30 kW
COP Tj = +2°C
5.50
4.40
Cdh Tj = +2 °C
0.930
0.940
Pdh Tj = +7°C
7.50 kW
7.40 kW
COP Tj = +7°C
6.50
5.40
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
8.60 kW
8.60 kW
COP Tj = 12°C
7.50
6.40
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.30 kW
11.10 kW
COP Tj = Tbiv
2.90
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
17.13 kW
16.89 kW
Annual energy consumption Qhe
10819 kWh
12788 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
13.29 kW
12.09 kW
ηs
190 %
153 %
Prated
13.29 kW
12.09 kW
SCOP
4.85
3.92
Tbiv
-7 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.50 kW
10.90 kW
COP Tj = -7°C
2.80
2.30
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.10 kW
6.40 kW
COP Tj = +2°C
5.00
3.90
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
7.40 kW
7.20 kW
COP Tj = +7°C
6.20
5.00
Cdh Tj = +7 °C
0.991
0.992
Pdh Tj = 12°C
8.70 kW
8.60 kW
COP Tj = 12°C
7.70
6.40
Cdh Tj = +12 °C
0.990
0.992
Pdh Tj = Tbiv
11.50 kW
11.40 kW
COP Tj = Tbiv
2.80
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.60 kW
10.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.10
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.74 kW
1.25 kW
Annual energy consumption Qhe
5673 kWh
6594 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
128 %
COP
3.2
Heating up time
01:12 h:min
Standby power input
52 W
Reference hot water temperature
53.7 °C
Mixed water at 40°C
260 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
98 %
COP
2.44
Heating up time
01:16 h:min
Standby power input
83 W
Reference hot water temperature
53.6 °C
Mixed water at 40°C
260 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
116 %
COP
2.89
Heating up time
01:14 h:min
Standby power input
55.5 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
260 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.00 kW
8.55 kW
El input
1.71 kW
2.59 kW
COP
5.27
3.31
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.22 kW
6.73 kW
ηs
215 %
159 %
Prated
7.22 kW
6.73 kW
SCOP
5.44
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.20 kW
6.70 kW
COP Tj = +2°C
4.40
2.80
Cdh Tj = +2 °C
0.970
0.970
Pdh Tj = +7°C
7.30 kW
6.90 kW
COP Tj = +7°C
5.60
3.80
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
8.60 kW
8.40 kW
COP Tj = 12°C
7.20
5.60
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
7.20 kW
6.70 kW
COP Tj = Tbiv
4.40
2.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.20 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
2.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.950
0.950
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1773 kWh
2224 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
18.67 kW
18.53 kW
ηs
147 %
121 %
Prated
18.67 kW
18.53 kW
SCOP
3.75
3.10
Tbiv
-8 °C
-8 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
11.20 kW
11.10 kW
COP Tj = -7°C
3.20
2.60
Cdh Tj = -7 °C
0.980
0.980
Pdh Tj = +2°C
6.90 kW
6.60 kW
COP Tj = +2°C
5.40
4.40
Cdh Tj = +2 °C
0.940
0.950
Pdh Tj = +7°C
7.50 kW
7.30 kW
COP Tj = +7°C
6.50
5.50
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
8.50 kW
8.60 kW
COP Tj = 12°C
7.40
6.50
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.80 kW
11.70 kW
COP Tj = Tbiv
3.00
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
18.67 kW
18.53 kW
Annual energy consumption Qhe
12265 kWh
14724 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
13.61 kW
13.18 kW
ηs
191 %
152 %
Prated
13.61 kW
13.18 kW
SCOP
4.86
3.89
Tbiv
-7 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
11.90 kW
COP Tj = -7°C
2.80
2.20
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.20 kW
6.80 kW
COP Tj = +2°C
5.00
3.90
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
7.50 kW
7.20 kW
COP Tj = +7°C
6.30
5.10
Cdh Tj = +7 °C
0.991
0.992
Pdh Tj = 12°C
8.70 kW
8.50 kW
COP Tj = 12°C
7.70
6.40
Cdh Tj = +12 °C
0.990
0.992
Pdh Tj = Tbiv
12.00 kW
12.10 kW
COP Tj = Tbiv
2.80
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.00 kW
11.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.57 kW
1.72 kW
Annual energy consumption Qhe
5897 kWh
7019 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
128 %
COP
3.2
Heating up time
01:12 h:min
Standby power input
52 W
Reference hot water temperature
53.7 °C
Mixed water at 40°C
260 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
98 %
COP
2.44
Heating up time
01:16 h:min
Standby power input
83 W
Reference hot water temperature
53.6 °C
Mixed water at 40°C
260 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
116 %
COP
2.89
Heating up time
01:14 h:min
Standby power input
55.5 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
260 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.50 kW
8.14 kW
El input
1.60 kW
2.46 kW
COP
5.31
3.31
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.24 kW
6.77 kW
ηs
215 %
159 %
Prated
7.24 kW
6.77 kW
SCOP
5.46
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.20 kW
6.80 kW
COP Tj = +2°C
4.50
2.90
Cdh Tj = +2 °C
0.950
0.970
Pdh Tj = +7°C
7.40 kW
7.00 kW
COP Tj = +7°C
5.70
3.80
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
8.60 kW
8.40 kW
COP Tj = 12°C
7.10
5.60
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
7.20 kW
6.80 kW
COP Tj = Tbiv
4.50
2.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.20 kW
6.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.50
2.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.950
0.950
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1772 kWh
2236 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
17.13 kW
16.89 kW
ηs
153 %
127 %
Prated
17.13 kW
16.89 kW
SCOP
3.90
3.26
Tbiv
-9 °C
-9 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
10.30 kW
10.20 kW
COP Tj = -7°C
3.30
2.70
Cdh Tj = -7 °C
0.970
0.980
Pdh Tj = +2°C
6.50 kW
6.30 kW
COP Tj = +2°C
5.50
4.40
Cdh Tj = +2 °C
0.930
0.940
Pdh Tj = +7°C
7.50 kW
7.40 kW
COP Tj = +7°C
6.50
5.40
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
8.60 kW
8.60 kW
COP Tj = 12°C
7.50
6.40
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.30 kW
11.10 kW
COP Tj = Tbiv
2.90
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
17.13 kW
16.89 kW
Annual energy consumption Qhe
10819 kWh
12788 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
13.29 kW
12.09 kW
ηs
190 %
153 %
Prated
13.29 kW
12.09 kW
SCOP
4.85
3.92
Tbiv
-7 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.50 kW
10.90 kW
COP Tj = -7°C
2.80
2.30
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.10 kW
6.40 kW
COP Tj = +2°C
5.00
3.90
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
7.40 kW
7.20 kW
COP Tj = +7°C
6.20
5.00
Cdh Tj = +7 °C
0.991
0.992
Pdh Tj = 12°C
8.70 kW
8.60 kW
COP Tj = 12°C
7.70
6.40
Cdh Tj = +12 °C
0.990
0.992
Pdh Tj = Tbiv
11.50 kW
11.40 kW
COP Tj = Tbiv
2.80
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.60 kW
10.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.10
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.74 kW
1.25 kW
Annual energy consumption Qhe
5673 kWh
6594 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
128 %
COP
3.2
Heating up time
01:12 h:min
Standby power input
52 W
Reference hot water temperature
53.7 °C
Mixed water at 40°C
260 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
98 %
COP
2.44
Heating up time
01:16 h:min
Standby power input
83 W
Reference hot water temperature
53.6 °C
Mixed water at 40°C
260 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
116 %
COP
2.89
Heating up time
01:14 h:min
Standby power input
55.5 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
260 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.00 kW
8.55 kW
El input
1.71 kW
2.59 kW
COP
5.27
3.31
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.22 kW
6.73 kW
ηs
215 %
159 %
Prated
7.22 kW
6.73 kW
SCOP
5.44
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.20 kW
6.70 kW
COP Tj = +2°C
4.40
2.80
Cdh Tj = +2 °C
0.970
0.970
Pdh Tj = +7°C
7.30 kW
6.90 kW
COP Tj = +7°C
5.60
3.80
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
8.60 kW
8.40 kW
COP Tj = 12°C
7.20
5.60
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
7.20 kW
6.70 kW
COP Tj = Tbiv
4.40
2.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.20 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
2.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.950
0.950
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1773 kWh
2224 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
18.67 kW
18.53 kW
ηs
147 %
121 %
Prated
18.67 kW
18.53 kW
SCOP
3.75
3.10
Tbiv
-8 °C
-8 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
11.20 kW
11.10 kW
COP Tj = -7°C
3.20
2.60
Cdh Tj = -7 °C
0.980
0.980
Pdh Tj = +2°C
6.90 kW
6.60 kW
COP Tj = +2°C
5.40
4.40
Cdh Tj = +2 °C
0.940
0.950
Pdh Tj = +7°C
7.50 kW
7.30 kW
COP Tj = +7°C
6.50
5.50
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
8.50 kW
8.60 kW
COP Tj = 12°C
7.40
6.50
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.80 kW
11.70 kW
COP Tj = Tbiv
3.00
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
18.67 kW
18.53 kW
Annual energy consumption Qhe
12265 kWh
14724 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
13.61 kW
13.18 kW
ηs
191 %
152 %
Prated
13.61 kW
13.18 kW
SCOP
4.86
3.89
Tbiv
-7 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
11.90 kW
COP Tj = -7°C
2.80
2.20
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.20 kW
6.80 kW
COP Tj = +2°C
5.00
3.90
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
7.50 kW
7.20 kW
COP Tj = +7°C
6.30
5.10
Cdh Tj = +7 °C
0.991
0.992
Pdh Tj = 12°C
8.70 kW
8.50 kW
COP Tj = 12°C
7.70
6.40
Cdh Tj = +12 °C
0.990
0.992
Pdh Tj = Tbiv
12.00 kW
12.10 kW
COP Tj = Tbiv
2.80
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.00 kW
11.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.57 kW
1.72 kW
Annual energy consumption Qhe
5897 kWh
7019 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
128 %
COP
3.2
Heating up time
01:12 h:min
Standby power input
52 W
Reference hot water temperature
53.7 °C
Mixed water at 40°C
260 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
98 %
COP
2.44
Heating up time
01:16 h:min
Standby power input
83 W
Reference hot water temperature
53.6 °C
Mixed water at 40°C
260 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
116 %
COP
2.89
Heating up time
01:14 h:min
Standby power input
55.5 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
260 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.50 kW
8.14 kW
El input
1.60 kW
2.46 kW
COP
5.31
3.31
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.24 kW
6.77 kW
ηs
215 %
159 %
Prated
7.24 kW
6.77 kW
SCOP
5.46
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.20 kW
6.80 kW
COP Tj = +2°C
4.50
2.90
Cdh Tj = +2 °C
0.950
0.970
Pdh Tj = +7°C
7.40 kW
7.00 kW
COP Tj = +7°C
5.70
3.80
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
8.60 kW
8.40 kW
COP Tj = 12°C
7.10
5.60
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
7.20 kW
6.80 kW
COP Tj = Tbiv
4.50
2.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.20 kW
6.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.50
2.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.950
0.950
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1772 kWh
2236 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
17.13 kW
16.89 kW
ηs
153 %
127 %
Prated
17.13 kW
16.89 kW
SCOP
3.90
3.26
Tbiv
-9 °C
-9 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
10.30 kW
10.20 kW
COP Tj = -7°C
3.30
2.70
Cdh Tj = -7 °C
0.970
0.980
Pdh Tj = +2°C
6.50 kW
6.30 kW
COP Tj = +2°C
5.50
4.40
Cdh Tj = +2 °C
0.930
0.940
Pdh Tj = +7°C
7.50 kW
7.40 kW
COP Tj = +7°C
6.50
5.40
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
8.60 kW
8.60 kW
COP Tj = 12°C
7.50
6.40
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.30 kW
11.10 kW
COP Tj = Tbiv
2.90
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
17.13 kW
16.89 kW
Annual energy consumption Qhe
10819 kWh
12788 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
13.29 kW
12.09 kW
ηs
190 %
153 %
Prated
13.29 kW
12.09 kW
SCOP
4.85
3.92
Tbiv
-7 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.50 kW
10.90 kW
COP Tj = -7°C
2.80
2.30
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.10 kW
6.40 kW
COP Tj = +2°C
5.00
3.90
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
7.40 kW
7.20 kW
COP Tj = +7°C
6.20
5.00
Cdh Tj = +7 °C
0.991
0.992
Pdh Tj = 12°C
8.70 kW
8.60 kW
COP Tj = 12°C
7.70
6.40
Cdh Tj = +12 °C
0.990
0.992
Pdh Tj = Tbiv
11.50 kW
11.40 kW
COP Tj = Tbiv
2.80
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.60 kW
10.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.10
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.74 kW
1.25 kW
Annual energy consumption Qhe
5673 kWh
6594 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
128 %
COP
3.2
Heating up time
01:12 h:min
Standby power input
52 W
Reference hot water temperature
53.7 °C
Mixed water at 40°C
260 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
98 %
COP
2.44
Heating up time
01:16 h:min
Standby power input
83 W
Reference hot water temperature
53.6 °C
Mixed water at 40°C
260 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
116 %
COP
2.89
Heating up time
01:14 h:min
Standby power input
55.5 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
260 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.00 kW
8.55 kW
El input
1.71 kW
2.59 kW
COP
5.27
3.31
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.22 kW
6.73 kW
ηs
215 %
159 %
Prated
7.22 kW
6.73 kW
SCOP
5.44
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.20 kW
6.70 kW
COP Tj = +2°C
4.40
2.80
Cdh Tj = +2 °C
0.970
0.970
Pdh Tj = +7°C
7.30 kW
6.90 kW
COP Tj = +7°C
5.60
3.80
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
8.60 kW
8.40 kW
COP Tj = 12°C
7.20
5.60
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
7.20 kW
6.70 kW
COP Tj = Tbiv
4.40
2.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.20 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
2.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.950
0.950
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1773 kWh
2224 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
18.67 kW
18.53 kW
ηs
147 %
121 %
Prated
18.67 kW
18.53 kW
SCOP
3.75
3.10
Tbiv
-8 °C
-8 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
11.20 kW
11.10 kW
COP Tj = -7°C
3.20
2.60
Cdh Tj = -7 °C
0.980
0.980
Pdh Tj = +2°C
6.90 kW
6.60 kW
COP Tj = +2°C
5.40
4.40
Cdh Tj = +2 °C
0.940
0.950
Pdh Tj = +7°C
7.50 kW
7.30 kW
COP Tj = +7°C
6.50
5.50
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
8.50 kW
8.60 kW
COP Tj = 12°C
7.40
6.50
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.80 kW
11.70 kW
COP Tj = Tbiv
3.00
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
18.67 kW
18.53 kW
Annual energy consumption Qhe
12265 kWh
14724 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
13.61 kW
13.18 kW
ηs
191 %
152 %
Prated
13.61 kW
13.18 kW
SCOP
4.86
3.89
Tbiv
-7 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
11.90 kW
COP Tj = -7°C
2.80
2.20
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.20 kW
6.80 kW
COP Tj = +2°C
5.00
3.90
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
7.50 kW
7.20 kW
COP Tj = +7°C
6.30
5.10
Cdh Tj = +7 °C
0.991
0.992
Pdh Tj = 12°C
8.70 kW
8.50 kW
COP Tj = 12°C
7.70
6.40
Cdh Tj = +12 °C
0.990
0.992
Pdh Tj = Tbiv
12.00 kW
12.10 kW
COP Tj = Tbiv
2.80
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.00 kW
11.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.57 kW
1.72 kW
Annual energy consumption Qhe
5897 kWh
7019 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
128 %
COP
3.2
Heating up time
01:12 h:min
Standby power input
52 W
Reference hot water temperature
53.7 °C
Mixed water at 40°C
260 l
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
98 %
COP
2.44
Heating up time
01:16 h:min
Standby power input
83 W
Reference hot water temperature
53.6 °C
Mixed water at 40°C
260 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
116 %
COP
2.89
Heating up time
01:14 h:min
Standby power input
55.5 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
260 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.50 kW
8.14 kW
El input
1.60 kW
2.46 kW
COP
5.31
3.31
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.24 kW
6.77 kW
ηs
215 %
159 %
Prated
7.24 kW
6.77 kW
SCOP
5.46
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.20 kW
6.80 kW
COP Tj = +2°C
4.50
2.90
Cdh Tj = +2 °C
0.950
0.970
Pdh Tj = +7°C
7.40 kW
7.00 kW
COP Tj = +7°C
5.70
3.80
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
8.60 kW
8.40 kW
COP Tj = 12°C
7.10
5.60
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
7.20 kW
6.80 kW
COP Tj = Tbiv
4.50
2.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.20 kW
6.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.50
2.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.950
0.950
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1772 kWh
2236 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
17.13 kW
16.89 kW
ηs
153 %
127 %
Prated
17.13 kW
16.89 kW
SCOP
3.90
3.26
Tbiv
-9 °C
-9 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
10.30 kW
10.20 kW
COP Tj = -7°C
3.30
2.70
Cdh Tj = -7 °C
0.970
0.980
Pdh Tj = +2°C
6.50 kW
6.30 kW
COP Tj = +2°C
5.50
4.40
Cdh Tj = +2 °C
0.930
0.940
Pdh Tj = +7°C
7.50 kW
7.40 kW
COP Tj = +7°C
6.50
5.40
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
8.60 kW
8.60 kW
COP Tj = 12°C
7.50
6.40
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.30 kW
11.10 kW
COP Tj = Tbiv
2.90
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
17.13 kW
16.89 kW
Annual energy consumption Qhe
10819 kWh
12788 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
13.29 kW
12.09 kW
ηs
190 %
153 %
Prated
13.29 kW
12.09 kW
SCOP
4.85
3.92
Tbiv
-7 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.50 kW
10.90 kW
COP Tj = -7°C
2.80
2.30
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.10 kW
6.40 kW
COP Tj = +2°C
5.00
3.90
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
7.40 kW
7.20 kW
COP Tj = +7°C
6.20
5.00
Cdh Tj = +7 °C
0.991
0.992
Pdh Tj = 12°C
8.70 kW
8.60 kW
COP Tj = 12°C
7.70
6.40
Cdh Tj = +12 °C
0.990
0.992
Pdh Tj = Tbiv
11.50 kW
11.40 kW
COP Tj = Tbiv
2.80
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.60 kW
10.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.10
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
2.74 kW
1.25 kW
Annual energy consumption Qhe
5673 kWh
6594 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.00 kW
8.55 kW
El input
1.71 kW
2.59 kW
COP
5.27
3.31
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.22 kW
6.73 kW
ηs
215 %
159 %
Prated
7.22 kW
6.73 kW
SCOP
5.44
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.20 kW
6.70 kW
COP Tj = +2°C
4.40
2.80
Cdh Tj = +2 °C
0.970
0.970
Pdh Tj = +7°C
7.30 kW
6.90 kW
COP Tj = +7°C
5.60
3.80
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
8.60 kW
8.40 kW
COP Tj = 12°C
7.20
5.60
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
7.20 kW
6.70 kW
COP Tj = Tbiv
4.40
2.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.20 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
2.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.950
0.950
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1773 kWh
2224 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
18.67 kW
18.53 kW
ηs
147 %
121 %
Prated
18.67 kW
18.53 kW
SCOP
3.75
3.10
Tbiv
-8 °C
-8 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
11.20 kW
11.10 kW
COP Tj = -7°C
3.20
2.60
Cdh Tj = -7 °C
0.980
0.980
Pdh Tj = +2°C
6.90 kW
6.60 kW
COP Tj = +2°C
5.40
4.40
Cdh Tj = +2 °C
0.940
0.950
Pdh Tj = +7°C
7.50 kW
7.30 kW
COP Tj = +7°C
6.50
5.50
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
8.50 kW
8.60 kW
COP Tj = 12°C
7.40
6.50
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.80 kW
11.70 kW
COP Tj = Tbiv
3.00
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
18.67 kW
18.53 kW
Annual energy consumption Qhe
12265 kWh
14724 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
13.61 kW
13.18 kW
ηs
191 %
152 %
Prated
13.61 kW
13.18 kW
SCOP
4.86
3.89
Tbiv
-7 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
11.90 kW
COP Tj = -7°C
2.80
2.20
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.20 kW
6.80 kW
COP Tj = +2°C
5.00
3.90
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
7.50 kW
7.20 kW
COP Tj = +7°C
6.30
5.10
Cdh Tj = +7 °C
0.991
0.992
Pdh Tj = 12°C
8.70 kW
8.50 kW
COP Tj = 12°C
7.70
6.40
Cdh Tj = +12 °C
0.990
0.992
Pdh Tj = Tbiv
12.00 kW
12.10 kW
COP Tj = Tbiv
2.80
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.00 kW
11.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
2.57 kW
1.72 kW
Annual energy consumption Qhe
5897 kWh
7019 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.50 kW
8.14 kW
El input
1.60 kW
2.46 kW
COP
5.31
3.31
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.24 kW
6.77 kW
ηs
215 %
159 %
Prated
7.24 kW
6.77 kW
SCOP
5.46
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.20 kW
6.80 kW
COP Tj = +2°C
4.50
2.90
Cdh Tj = +2 °C
0.950
0.970
Pdh Tj = +7°C
7.40 kW
7.00 kW
COP Tj = +7°C
5.70
3.80
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
8.60 kW
8.40 kW
COP Tj = 12°C
7.10
5.60
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
7.20 kW
6.80 kW
COP Tj = Tbiv
4.50
2.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.20 kW
6.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.50
2.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.950
0.950
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1772 kWh
2236 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
17.13 kW
16.89 kW
ηs
153 %
127 %
Prated
17.13 kW
16.89 kW
SCOP
3.90
3.26
Tbiv
-9 °C
-9 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
10.30 kW
10.20 kW
COP Tj = -7°C
3.30
2.70
Cdh Tj = -7 °C
0.970
0.980
Pdh Tj = +2°C
6.50 kW
6.30 kW
COP Tj = +2°C
5.50
4.40
Cdh Tj = +2 °C
0.930
0.940
Pdh Tj = +7°C
7.50 kW
7.40 kW
COP Tj = +7°C
6.50
5.40
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
8.60 kW
8.60 kW
COP Tj = 12°C
7.50
6.40
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.30 kW
11.10 kW
COP Tj = Tbiv
2.90
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
17.13 kW
16.89 kW
Annual energy consumption Qhe
10819 kWh
12788 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
13.29 kW
12.09 kW
ηs
190 %
153 %
Prated
13.29 kW
12.09 kW
SCOP
4.85
3.92
Tbiv
-7 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.50 kW
10.90 kW
COP Tj = -7°C
2.80
2.30
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.10 kW
6.40 kW
COP Tj = +2°C
5.00
3.90
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
7.40 kW
7.20 kW
COP Tj = +7°C
6.20
5.00
Cdh Tj = +7 °C
0.991
0.992
Pdh Tj = 12°C
8.70 kW
8.60 kW
COP Tj = 12°C
7.70
6.40
Cdh Tj = +12 °C
0.990
0.992
Pdh Tj = Tbiv
11.50 kW
11.40 kW
COP Tj = Tbiv
2.80
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.60 kW
10.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.10
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
2.74 kW
1.25 kW
Annual energy consumption Qhe
5673 kWh
6594 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.00 kW
8.55 kW
El input
1.71 kW
2.59 kW
COP
5.27
3.31
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
7.22 kW
6.73 kW
ηs
215 %
159 %
Prated
7.22 kW
6.73 kW
SCOP
5.44
4.05
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.20 kW
6.70 kW
COP Tj = +2°C
4.40
2.80
Cdh Tj = +2 °C
0.970
0.970
Pdh Tj = +7°C
7.30 kW
6.90 kW
COP Tj = +7°C
5.60
3.80
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
8.60 kW
8.40 kW
COP Tj = 12°C
7.20
5.60
Cdh Tj = +12 °C
0.930
0.950
Pdh Tj = Tbiv
7.20 kW
6.70 kW
COP Tj = Tbiv
4.40
2.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.20 kW
6.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
2.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.950
0.950
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1773 kWh
2224 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
18.67 kW
18.53 kW
ηs
147 %
121 %
Prated
18.67 kW
18.53 kW
SCOP
3.75
3.10
Tbiv
-8 °C
-8 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
11.20 kW
11.10 kW
COP Tj = -7°C
3.20
2.60
Cdh Tj = -7 °C
0.980
0.980
Pdh Tj = +2°C
6.90 kW
6.60 kW
COP Tj = +2°C
5.40
4.40
Cdh Tj = +2 °C
0.940
0.950
Pdh Tj = +7°C
7.50 kW
7.30 kW
COP Tj = +7°C
6.50
5.50
Cdh Tj = +7 °C
0.930
0.940
Pdh Tj = 12°C
8.50 kW
8.60 kW
COP Tj = 12°C
7.40
6.50
Cdh Tj = +12 °C
0.930
0.940
Pdh Tj = Tbiv
11.80 kW
11.70 kW
COP Tj = Tbiv
3.00
2.40
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.60 kW
7.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
18.67 kW
18.53 kW
Annual energy consumption Qhe
12265 kWh
14724 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
13.61 kW
13.18 kW
ηs
191 %
152 %
Prated
13.61 kW
13.18 kW
SCOP
4.86
3.89
Tbiv
-7 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
11.90 kW
COP Tj = -7°C
2.80
2.20
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.20 kW
6.80 kW
COP Tj = +2°C
5.00
3.90
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
7.50 kW
7.20 kW
COP Tj = +7°C
6.30
5.10
Cdh Tj = +7 °C
0.991
0.992
Pdh Tj = 12°C
8.70 kW
8.50 kW
COP Tj = 12°C
7.70
6.40
Cdh Tj = +12 °C
0.990
0.992
Pdh Tj = Tbiv
12.00 kW
12.10 kW
COP Tj = Tbiv
2.80
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.00 kW
11.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
2.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
70 °C
70 °C
Poff
11 W
11 W
PTO
16 W
16 W
PSB
16 W
16 W
PCK
33 W
33 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
2.57 kW
1.72 kW
Annual energy consumption Qhe
5897 kWh
7019 kWh