1,000 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
10.48 kW
9.17 kW
El input
2.30 kW
3.21 kW
COP
4.56
2.86
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
58 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184 %
143 %
Prated
11.62 kW
11.83 kW
SCOP
4.67
3.66
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
10.28 kW
10.47 kW
COP Tj = -7°C
2.97
2.31
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.30 kW
6.43 kW
COP Tj = +2°C
4.48
3.49
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.58 kW
4.33 kW
COP Tj = +7°C
6.50
5.09
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
5.33 kW
5.16 kW
COP Tj = 12°C
8.31
6.65
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
10.28 kW
10.47 kW
COP Tj = Tbiv
2.97
2.31
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.79 kW
9.99 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.59
2.08
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
11 W
11 W
PTO
12 W
12 W
PSB
11 W
11 W
PCK
83 W
83 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.83 kW
1.85 kW
Annual energy consumption Qhe
5144 kWh
6679 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.72 kW
9.67 kW
El input
2.13 kW
3.12 kW
COP
4.57
3.10
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
58 dB(A)
59 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
141 %
Prated
11.63 kW
11.71 kW
SCOP
4.71
3.60
Tbiv
-7 °C
-7 °C
TOL
-25 °C
-25 °C
Pdh Tj = -7°C
10.29 kW
10.36 kW
COP Tj = -7°C
2.99
2.28
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.30 kW
6.45 kW
COP Tj = +2°C
4.54
3.45
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.19 kW
4.25 kW
COP Tj = +7°C
6.37
4.93
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
4.87 kW
5.03 kW
COP Tj = 12°C
8.09
6.40
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
10.29 kW
10.36 kW
COP Tj = Tbiv
2.99
2.28
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.71 kW
9.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.68
2.05
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
12 W
12 W
PSB
10 W
10 W
PCK
48 W
48 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.92 kW
1.82 kW
Annual energy consumption Qhe
5105 kWh
6718 kWh