2,350 kg
Brine/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
17.33 kW
16.02 kW
El input
3.94 kW
5.57 kW
COP
4.40
2.88
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
47 dB(A)
47 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
137 %
Prated
17.35 kW
16.12 kW
SCOP
4.81
3.63
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
17.33 kW
16.02 kW
COP Tj = +2°C
4.40
2.88
Cdh Tj = +2 °C
0.998
0.999
Pdh Tj = +7°C
17.49 kW
16.39 kW
COP Tj = +7°C
4.66
3.31
Cdh Tj = +7 °C
0.998
0.999
Pdh Tj = 12°C
17.71 kW
16.97 kW
COP Tj = 12°C
5.04
4.07
Cdh Tj = +12 °C
0.998
0.998
Pdh Tj = Tbiv
17.33 kW
16.02 kW
COP Tj = Tbiv
4.40
2.88
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
17.33 kW
16.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
2.88
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.998
0.999
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4817 kWh
5940 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
47 dB(A)
47 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
186 %
139 %
Prated
17.35 kW
16.15 kW
SCOP
4.85
3.67
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
17.52 kW
16.49 kW
COP Tj = -7°C
4.76
3.43
Cdh Tj = -7 °C
0.998
0.998
Pdh Tj = +2°C
17.59 kW
16.80 kW
COP Tj = +2°C
4.95
3.85
Cdh Tj = +2 °C
0.998
0.998
Pdh Tj = +7°C
17.71 kW
17.05 kW
COP Tj = +7°C
5.11
4.22
Cdh Tj = +7 °C
0.998
0.998
Pdh Tj = 12°C
17.73 kW
17.28 kW
COP Tj = 12°C
5.17
4.54
Cdh Tj = +12 °C
0.998
0.998
Pdh Tj = Tbiv
17.33 kW
16.02 kW
COP Tj = Tbiv
4.40
2.88
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
17.33 kW
16.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
2.88
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.998
0.999
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
8813 kWh
10843 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
47 dB(A)
47 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
141 %
Prated
17.31 kW
16.13 kW
SCOP
4.75
3.73
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
17.41 kW
16.13 kW
COP Tj = -7°C
4.47
3.13
Cdh Tj = -7 °C
0.998
0.999
Pdh Tj = +2°C
17.48 kW
16.61 kW
COP Tj = +2°C
4.70
3.68
Cdh Tj = +2 °C
0.998
0.998
Pdh Tj = +7°C
17.63 kW
16.88 kW
COP Tj = +7°C
4.00
4.07
Cdh Tj = +7 °C
0.998
0.998
Pdh Tj = 12°C
17.75 kW
17.17 kW
COP Tj = 12°C
4.94
4.50
Cdh Tj = +12 °C
0.998
0.998
Pdh Tj = Tbiv
17.33 kW
16.02 kW
COP Tj = Tbiv
4.40
2.97
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
17.33 kW
16.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
2.97
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.998
0.999
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
7531 kWh
8944 kWh
Water/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
22.67 kW
20.32 kW
El input
4.46 kW
6.05 kW
COP
5.08
3.36
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
210 %
165 %
Prated
22.60 kW
20.30 kW
SCOP
5.45
4.33
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
22.67 kW
20.32 kW
COP Tj = +2°C
5.08
3.36
Cdh Tj = +2 °C
0.996
0.998
Pdh Tj = +7°C
22.76 kW
21.08 kW
COP Tj = +7°C
5.31
3.92
Cdh Tj = +7 °C
0.996
0.997
Pdh Tj = 12°C
23.10 kW
22.15 kW
COP Tj = 12°C
5.71
4.96
Cdh Tj = +12 °C
0.996
0.997
Pdh Tj = Tbiv
22.67 kW
20.32 kW
COP Tj = Tbiv
5.08
3.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
22.67 kW
20.32 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.08
3.36
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.998
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5538 kWh
6258 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
192 %
161 %
Prated
37.80 kW
35.50 kW
SCOP
5.00
4.23
Tbiv
-7 °C
-7 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
23.10 kW
21.70 kW
COP Tj = -7°C
5.68
4.51
Cdh Tj = -7 °C
0.996
0.997
Pdh Tj = +2°C
23.21 kW
22.10 kW
COP Tj = +2°C
5.81
4.94
Cdh Tj = +2 °C
0.996
0.997
Pdh Tj = +7°C
23.30 kW
22.43 kW
COP Tj = +7°C
5.92
5.34
Cdh Tj = +7 °C
0.996
0.996
Pdh Tj = 12°C
23.33 kW
22.61 kW
COP Tj = 12°C
5.92
5.62
Cdh Tj = +12 °C
0.996
0.996
Pdh Tj = Tbiv
23.10 kW
21.70 kW
COP Tj = Tbiv
5.68
4.51
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
22.67 kW
20.32 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.08
3.36
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.998
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
15.13 kW
15.18 kW
Annual energy consumption Qhe
18645 kWh
20708 kWh
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
210 %
166 %
Prated
25.80 kW
23.50 kW
SCOP
5.45
4.36
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
22.78 kW
20.73 kW
COP Tj = -7°C
5.20
3.65
Cdh Tj = -7 °C
0.996
0.997
Pdh Tj = +2°C
22.95 kW
21.48 kW
COP Tj = +2°C
5.45
4.33
Cdh Tj = +2 °C
0.996
0.997
Pdh Tj = +7°C
23.14 kW
21.98 kW
COP Tj = +7°C
5.69
4.82
Cdh Tj = +7 °C
0.996
0.997
Pdh Tj = 12°C
23.29 kW
22.41 kW
COP Tj = 12°C
5.90
5.34
Cdh Tj = +12 °C
0.996
0.996
Pdh Tj = Tbiv
22.73 kW
20.73 kW
COP Tj = Tbiv
5.20
3.65
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
22.67 kW
20.32 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.08
3.36
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.998
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.13 kW
3.18 kW
Annual energy consumption Qhe
9789 kWh
11140 kWh
Brine/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
17.33 kW
16.02 kW
El input
3.94 kW
5.57 kW
COP
4.40
2.88
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
47 dB(A)
47 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
137 %
Prated
17.35 kW
16.12 kW
SCOP
4.81
3.63
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
17.33 kW
16.02 kW
COP Tj = +2°C
4.40
2.88
Cdh Tj = +2 °C
0.998
0.999
Pdh Tj = +7°C
17.49 kW
16.39 kW
COP Tj = +7°C
4.66
3.31
Cdh Tj = +7 °C
0.998
0.999
Pdh Tj = 12°C
17.71 kW
16.97 kW
COP Tj = 12°C
5.04
4.07
Cdh Tj = +12 °C
0.998
0.998
Pdh Tj = Tbiv
17.33 kW
16.02 kW
COP Tj = Tbiv
4.40
2.88
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
17.33 kW
16.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
2.88
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.998
0.999
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4817 kWh
5940 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
47 dB(A)
47 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
186 %
139 %
Prated
17.35 kW
16.15 kW
SCOP
4.85
3.67
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
17.52 kW
16.49 kW
COP Tj = -7°C
4.76
3.43
Cdh Tj = -7 °C
0.998
0.998
Pdh Tj = +2°C
17.59 kW
16.80 kW
COP Tj = +2°C
4.95
3.85
Cdh Tj = +2 °C
0.998
0.998
Pdh Tj = +7°C
17.71 kW
17.05 kW
COP Tj = +7°C
5.11
4.22
Cdh Tj = +7 °C
0.998
0.998
Pdh Tj = 12°C
17.73 kW
17.28 kW
COP Tj = 12°C
5.17
4.54
Cdh Tj = +12 °C
0.998
0.998
Pdh Tj = Tbiv
17.33 kW
16.02 kW
COP Tj = Tbiv
4.40
2.88
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
17.33 kW
16.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
2.88
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.998
0.999
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
8813 kWh
10843 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
47 dB(A)
47 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
141 %
Prated
17.31 kW
16.13 kW
SCOP
4.75
3.73
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
17.41 kW
16.13 kW
COP Tj = -7°C
4.47
3.13
Cdh Tj = -7 °C
0.998
0.999
Pdh Tj = +2°C
17.48 kW
16.61 kW
COP Tj = +2°C
4.70
3.68
Cdh Tj = +2 °C
0.998
0.998
Pdh Tj = +7°C
17.63 kW
16.88 kW
COP Tj = +7°C
4.00
4.07
Cdh Tj = +7 °C
0.998
0.998
Pdh Tj = 12°C
17.75 kW
17.17 kW
COP Tj = 12°C
4.94
4.50
Cdh Tj = +12 °C
0.998
0.998
Pdh Tj = Tbiv
17.33 kW
16.02 kW
COP Tj = Tbiv
4.40
2.97
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
17.33 kW
16.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
2.97
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.998
0.999
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
7531 kWh
8944 kWh
Water/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
22.67 kW
20.32 kW
El input
4.46 kW
6.05 kW
COP
5.08
3.36
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
210 %
165 %
Prated
22.60 kW
20.30 kW
SCOP
5.45
4.33
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
22.67 kW
20.32 kW
COP Tj = +2°C
5.08
3.36
Cdh Tj = +2 °C
0.996
0.998
Pdh Tj = +7°C
22.76 kW
21.08 kW
COP Tj = +7°C
5.31
3.92
Cdh Tj = +7 °C
0.996
0.997
Pdh Tj = 12°C
23.10 kW
22.15 kW
COP Tj = 12°C
5.71
4.96
Cdh Tj = +12 °C
0.996
0.997
Pdh Tj = Tbiv
22.67 kW
20.32 kW
COP Tj = Tbiv
5.08
3.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
22.67 kW
20.32 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.08
3.36
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.998
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5538 kWh
6258 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
192 %
161 %
Prated
37.80 kW
35.50 kW
SCOP
5.00
4.23
Tbiv
-7 °C
-7 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
23.10 kW
21.70 kW
COP Tj = -7°C
5.68
4.51
Cdh Tj = -7 °C
0.996
0.997
Pdh Tj = +2°C
23.21 kW
22.10 kW
COP Tj = +2°C
5.81
4.94
Cdh Tj = +2 °C
0.996
0.997
Pdh Tj = +7°C
23.30 kW
22.43 kW
COP Tj = +7°C
5.92
5.34
Cdh Tj = +7 °C
0.996
0.996
Pdh Tj = 12°C
23.33 kW
22.61 kW
COP Tj = 12°C
5.92
5.62
Cdh Tj = +12 °C
0.996
0.996
Pdh Tj = Tbiv
23.10 kW
21.70 kW
COP Tj = Tbiv
5.68
4.51
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
22.67 kW
20.32 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.08
3.36
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.998
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
15.13 kW
15.18 kW
Annual energy consumption Qhe
18645 kWh
20708 kWh
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
210 %
166 %
Prated
25.80 kW
23.50 kW
SCOP
5.45
4.36
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
22.78 kW
20.73 kW
COP Tj = -7°C
5.20
3.65
Cdh Tj = -7 °C
0.996
0.997
Pdh Tj = +2°C
22.95 kW
21.48 kW
COP Tj = +2°C
5.45
4.33
Cdh Tj = +2 °C
0.996
0.997
Pdh Tj = +7°C
23.14 kW
21.98 kW
COP Tj = +7°C
5.69
4.82
Cdh Tj = +7 °C
0.996
0.997
Pdh Tj = 12°C
23.29 kW
22.41 kW
COP Tj = 12°C
5.90
5.34
Cdh Tj = +12 °C
0.996
0.996
Pdh Tj = Tbiv
22.73 kW
20.73 kW
COP Tj = Tbiv
5.20
3.65
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
22.67 kW
20.32 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.08
3.36
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.996
0.998
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.13 kW
3.18 kW
Annual energy consumption Qhe
9789 kWh
11140 kWh