Certificate holders

Subtype

HA 7-5 OS 230V

Certificate Holder
Saunier Duval Brand Group


Germany
Registration number
011-1W0763
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
HA 7-5 OS 230V
Driving energy
n/a
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

2,390 kg

Certification Date
27.04.2021
Testing basis
DIN EN 14511-1:2019-07; EN 14511-1:2018; DIN EN 14511-2:2019-07; EN 14511-2:2018; DIN EN 14511-3:2019-07; EN 14511-3:2018; DIN EN 14511-4:2019-07; EN 14511-4:2018; DIN EN 14825:2019-07; EN 14825:2018; DIN EN 12102-1:2018-02; EN 12102-1:2017
Generate PDF Export model CSV
  • Number of models 2

Models

HA 7-5 OS 230V + HA 7-5 WSB
Configure model
Model name
HA 7-5 OS 230V + HA 7-5 WSB
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5.78 kW

4.95 kW

El input

1.26 kW

1.84 kW

COP

4.58

2.69

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

43 dB(A)

43 dB(A)

Sound power level outdoor

54 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

239 %

159 %

Prated

4.51 kW

3.94 kW

SCOP

6.04

4.05

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

4.51 kW

3.94 kW

COP Tj = +2°C

3.68

2.30

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

2.81 kW

2.45 kW

COP Tj = +7°C

5.55

3.38

Cdh Tj = +7 °C

0.98

0.99

Pdh Tj = 12°C

3.20 kW

3.15 kW

COP Tj = 12°C

7.35

5.43

Cdh Tj = +12 °C

0.98

0.98

Pdh Tj = Tbiv

4.51 kW

3.94 kW

COP Tj = Tbiv

3.68

2.30

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.51 kW

3.94 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.68

2.30

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

55 °C

55 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

997 kWh

1300 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

43 dB(A)

43 dB(A)

Sound power level outdoor

54 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

156 %

117 %

Prated

6.60 kW

5.36 kW

SCOP

3.96

3.00

Tbiv

-15 °C

-15 °C

TOL

-20 °C

-15 °C

Pdh Tj = -7°C

3.89 kW

3.55 kW

COP Tj = -7°C

3.51

2.53

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

2.31 kW

2.33 kW

COP Tj = +2°C

4.66

3.78

Cdh Tj = +2 °C

0.980

0.980

Pdh Tj = +7°C

2.77 kW

2.77 kW

COP Tj = +7°C

6.19

6.19

Cdh Tj = +7 °C

0.980

0.980

Pdh Tj = 12°C

3.20 kW

3.25 kW

COP Tj = 12°C

7.55

6.81

Cdh Tj = +12 °C

0.980

0.980

Pdh Tj = Tbiv

5.39 kW

4.37 kW

COP Tj = Tbiv

2.48

1.72

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

3.75 kW

4.37 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.09

1.72

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

1.000

WTOL

55 °C

55 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

6.60 kW

5.36 kW

Annual energy consumption Qhe

4106 kWh

4401 kWh

Pdh Tj = -15°C (if TOL<-20°C)

3.36

4.37

COP Tj = -15°C (if TOL<-20°C)

1.94

1.72

Cdh Tj = -15 °C

0.990

1.000

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

43 dB(A)

43 dB(A)

Sound power level outdoor

54 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

173 %

133 %

Prated

7.08 kW

6.36 kW

SCOP

4.40

3.39

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

6.30 kW

5.62 kW

COP Tj = -7°C

2.58

2.00

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

3.90 kW

3.31 kW

COP Tj = +2°C

4.37

3.29

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

2.72 kW

2.69 kW

COP Tj = +7°C

5.86

4.62

Cdh Tj = +7 °C

0.980

0.980

Pdh Tj = 12°C

3.28 kW

3.21 kW

COP Tj = 12°C

7.54

6.27

Cdh Tj = +12 °C

0.980

0.980

Pdh Tj = Tbiv

6.26 kW

5.62 kW

COP Tj = Tbiv

2.57

2.00

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.66 kW

4.92 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.38

1.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

55 °C

55 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.42 kW

1.44 kW

Annual energy consumption Qhe

3324 kWh

3869 kWh

HA 7-5 OS 230V + HA 7-5 STB
Configure model
Model name
HA 7-5 OS 230V + HA 7-5 STB
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5.78 kW

4.95 kW

El input

1.26 kW

1.84 kW

COP

4.58

2.69

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

44 dB(A)

Sound power level outdoor

54 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

239 %

159 %

Prated

4.51 kW

3.94 kW

SCOP

6.04

4.05

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

4.51 kW

3.94 kW

COP Tj = +2°C

3.68

2.30

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

2.81 kW

2.45 kW

COP Tj = +7°C

5.55

3.38

Cdh Tj = +7 °C

0.98

0.99

Pdh Tj = 12°C

3.20 kW

3.15 kW

COP Tj = 12°C

7.35

5.43

Cdh Tj = +12 °C

0.98

0.98

Pdh Tj = Tbiv

4.51 kW

3.94 kW

COP Tj = Tbiv

3.68

2.30

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.51 kW

3.94 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.68

2.30

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

55 °C

55 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

997 kWh

1300 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

44 dB(A)

Sound power level outdoor

54 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

156 %

117 %

Prated

6.60 kW

5.36 kW

SCOP

3.96

3.00

Tbiv

-15 °C

-15 °C

TOL

-20 °C

-15 °C

Pdh Tj = -7°C

3.89 kW

3.55 kW

COP Tj = -7°C

3.51

2.53

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

2.31 kW

2.33 kW

COP Tj = +2°C

4.66

3.78

Cdh Tj = +2 °C

0.980

0.980

Pdh Tj = +7°C

2.77 kW

2.77 kW

COP Tj = +7°C

6.19

6.19

Cdh Tj = +7 °C

0.980

0.980

Pdh Tj = 12°C

3.20 kW

3.25 kW

COP Tj = 12°C

7.55

6.81

Cdh Tj = +12 °C

0.980

0.980

Pdh Tj = Tbiv

5.39 kW

4.37 kW

COP Tj = Tbiv

2.48

1.72

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

3.75 kW

4.37 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.09

1.72

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

1.000

WTOL

55 °C

55 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

6.60 kW

5.36 kW

Annual energy consumption Qhe

4106 kWh

4401 kWh

Pdh Tj = -15°C (if TOL<-20°C)

3.36

4.37

COP Tj = -15°C (if TOL<-20°C)

1.94

1.72

Cdh Tj = -15 °C

0.990

1.000

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

44 dB(A)

Sound power level outdoor

54 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

173 %

133 %

Prated

7.08 kW

6.36 kW

SCOP

4.40

3.39

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

6.30 kW

5.62 kW

COP Tj = -7°C

2.58

2.00

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

3.90 kW

3.31 kW

COP Tj = +2°C

4.37

3.29

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

2.72 kW

2.69 kW

COP Tj = +7°C

5.86

4.62

Cdh Tj = +7 °C

0.980

0.980

Pdh Tj = 12°C

3.28 kW

3.21 kW

COP Tj = 12°C

7.54

6.27

Cdh Tj = +12 °C

0.980

0.980

Pdh Tj = Tbiv

6.26 kW

5.62 kW

COP Tj = Tbiv

2.57

2.00

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.66 kW

4.92 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.38

1.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

55 °C

55 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.42 kW

1.44 kW

Annual energy consumption Qhe

3324 kWh

3869 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

134 %

COP

3.26

Heating up time

01:28 h:min

Standby power input

70.0 W

Reference hot water temperature

51.2 °C

Mixed water at 40°C

242 l

Colder Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

102 %

COP

2.48

Heating up time

02:03 h:min

Standby power input

90.0 W

Reference hot water temperature

46.9 °C

Mixed water at 40°C

246 l

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

112 %

COP

2.73

Heating up time

01:45 h:min

Standby power input

80.0 W

Reference hot water temperature

50.7 °C

Mixed water at 40°C

246 l