Certificate holders

Subtype

HA 5-6 O 230V

Certificate Holder
Saunier Duval Brand Group


Germany
Registration number
011-1W0765
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
HA 5-6 O 230V
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R290
Mass of Refrigerant

0,600 kg

Certification Date
25.03.2022
Testing basis
DIN EN 14511-1:2019-07; EN 14511-1:2018, DIN EN 14511-2:2019-07; EN 14511-2:2018, DIN EN 14511-3:2019-07; EN 14511-3:2018, DIN EN 14511-4:2019-07; EN 14511-4:2018, DIN EN 14825:2019-07; EN 14825:2018, DIN EN 12102-1:2018-02; EN 12102-1:2017
Generate PDF Export model CSV
  • Number of models 6

Models

HA 5-6 O 230V
Configure model
Model name
HA 5-6 O 230V
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

3.36 kW

4.83 kW

El input

0.69 kW

1.71 kW

COP

4.80

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

51 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

233 %

157 %

Prated

4.96 kW

5.07 kW

SCOP

5.89

3.99

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

4.96 kW

5.07 kW

COP Tj = +2°C

3.35

2.30

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

3.42 kW

3.08 kW

COP Tj = +7°C

5.45

3.43

Cdh Tj = +7 °C

0.97

0.98

Pdh Tj = 12°C

2.59 kW

2.42 kW

COP Tj = 12°C

7.25

5.17

Cdh Tj = +12 °C

0.96

0.97

Pdh Tj = Tbiv

4.96 kW

5.07 kW

COP Tj = Tbiv

3.35

2.30

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.96 kW

5.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.35

2.30

WTOL

70 °C

70 °C

Poff

8 W

8 W

PTO

17 W

17 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

1125 kWh

1697 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

51 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

158 %

116 %

Prated

5.01 kW

4.76 kW

SCOP

4.02

2.98

Tbiv

-15 °C

-15 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

3.22 kW

2.89 kW

COP Tj = -7°C

3.36

2.45

Cdh Tj = -7 °C

0.980

0.990

Pdh Tj = +2°C

1.92 kW

1.85 kW

COP Tj = +2°C

5.04

3.65

Cdh Tj = +2 °C

0.960

0.970

Pdh Tj = +7°C

2.33 kW

2.21 kW

COP Tj = +7°C

6.82

5.01

Cdh Tj = +7 °C

0.960

0.960

Pdh Tj = 12°C

2.62 kW

2.56 kW

COP Tj = 12°C

7.24

6.46

Cdh Tj = +12 °C

0.960

0.960

Pdh Tj = Tbiv

4.09 kW

3.88 kW

COP Tj = Tbiv

2.13

1.67

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.04 kW

3.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.00

1.50

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

70 °C

70 °C

Poff

8 W

8 W

PTO

17 W

17 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

5.01 kW

4.76 kW

Annual energy consumption Qhe

3076 kWh

3930 kWh

Pdh Tj = -15°C (if TOL<-20°C)

4.09

3.88

COP Tj = -15°C (if TOL<-20°C)

2.13

1.67

Cdh Tj = -15 °C

0.990

0.990

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

51 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

183 %

130 %

Prated

4.81 kW

4.88 kW

SCOP

4.66

3.33

Tbiv

-7 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.26 kW

4.32 kW

COP Tj = -7°C

2.78

2.11

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

2.70 kW

2.46 kW

COP Tj = +2°C

4.62

3.19

Cdh Tj = +2 °C

0.970

0.980

Pdh Tj = +7°C

2.29 kW

2.12 kW

COP Tj = +7°C

6.41

4.40

Cdh Tj = +7 °C

0.960

0.970

Pdh Tj = 12°C

2.61 kW

2.52 kW

COP Tj = 12°C

7.61

6.03

Cdh Tj = +12 °C

0.960

0.960

Pdh Tj = Tbiv

4.26 kW

4.63 kW

COP Tj = Tbiv

2.78

1.86

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.13 kW

4.63 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.43

1.86

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

70 °C

70 °C

Poff

8 W

8 W

PTO

17 W

17 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.68 kW

kW

Annual energy consumption Qhe

2135 kWh

3029 kWh

HA 5-6 O 230V B2
Configure model
Model name
HA 5-6 O 230V B2
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

3.36 kW

4.83 kW

El input

0.69 kW

1.71 kW

COP

4.80

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

51 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

225 %

153 %

Prated

4.96 kW

5.07 kW

SCOP

5.71

3.91

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

4.96 kW

5.07 kW

COP Tj = +2°C

3.35

2.30

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

3.42 kW

3.08 kW

COP Tj = +7°C

5.45

3.43

Cdh Tj = +7 °C

0.97

0.98

Pdh Tj = 12°C

2.59 kW

2.42 kW

COP Tj = 12°C

7.25

5.17

Cdh Tj = +12 °C

0.96

0.97

Pdh Tj = Tbiv

4.96 kW

5.07 kW

COP Tj = Tbiv

3.35

2.30

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.96 kW

5.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.35

2.30

WTOL

70 °C

70 °C

Poff

8 W

8 W

PTO

17 W

17 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

1161 kWh

1733 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

51 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

157 %

116 %

Prated

5.01 kW

4.76 kW

SCOP

3.99

2.97

Tbiv

-15 °C

-15 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

3.22 kW

2.89 kW

COP Tj = -7°C

3.36

2.45

Cdh Tj = -7 °C

0.980

0.990

Pdh Tj = +2°C

1.92 kW

1.85 kW

COP Tj = +2°C

5.04

3.65

Cdh Tj = +2 °C

0.960

0.970

Pdh Tj = +7°C

2.33 kW

2.21 kW

COP Tj = +7°C

6.82

5.01

Cdh Tj = +7 °C

0.960

0.960

Pdh Tj = 12°C

2.62 kW

2.56 kW

COP Tj = 12°C

7.24

6.46

Cdh Tj = +12 °C

0.960

0.960

Pdh Tj = Tbiv

4.09 kW

3.88 kW

COP Tj = Tbiv

2.13

1.67

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.04 kW

3.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.00

1.50

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

70 °C

70 °C

Poff

8 W

8 W

PTO

17 W

17 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

5.01 kW

4.76 kW

Annual energy consumption Qhe

3094 kWh

3948 kWh

Pdh Tj = -15°C (if TOL<-20°C)

4.09

3.88

COP Tj = -15°C (if TOL<-20°C)

2.13

1.67

Cdh Tj = -15 °C

0.990

0.990

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

51 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

129 %

Prated

4.81 kW

4.88 kW

SCOP

4.59

3.30

Tbiv

-7 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

4.26 kW

4.32 kW

COP Tj = -7°C

2.78

2.11

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

2.70 kW

2.46 kW

COP Tj = +2°C

4.62

3.19

Cdh Tj = +2 °C

0.970

0.980

Pdh Tj = +7°C

2.29 kW

2.12 kW

COP Tj = +7°C

6.41

4.40

Cdh Tj = +7 °C

0.960

0.970

Pdh Tj = 12°C

2.61 kW

2.52 kW

COP Tj = 12°C

7.61

6.03

Cdh Tj = +12 °C

0.960

0.960

Pdh Tj = Tbiv

4.26 kW

4.63 kW

COP Tj = Tbiv

2.78

1.86

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.13 kW

4.63 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.43

1.86

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

70 °C

70 °C

Poff

8 W

8 W

PTO

17 W

17 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.68 kW

kW

Annual energy consumption Qhe

2165 kWh

3059 kWh

HA 5-6 O 230V B3
Configure model
Model name
HA 5-6 O 230V B3
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4.21 kW

4.83 kW

El input

0.95 kW

1.71 kW

COP

4.39

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

52 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

215 %

157 %

Prated

4.75 kW

5.07 kW

SCOP

5.44

3.99

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

4.75 kW

5.07 kW

COP Tj = +2°C

3.22

2.30

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

3.33 kW

3.08 kW

COP Tj = +7°C

5.07

3.43

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

2.48 kW

2.42 kW

COP Tj = 12°C

6.61

5.17

Cdh Tj = +12 °C

0.96

0.97

Pdh Tj = Tbiv

4.75 kW

5.07 kW

COP Tj = Tbiv

3.22

2.30

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.75 kW

5.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.22

2.30

WTOL

55 °C

55 °C

Poff

8 W

8 W

PTO

17 W

17 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

1166 kWh

1697 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

52 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

148 %

116 %

Prated

4.68 kW

4.76 kW

SCOP

3.77

2.98

Tbiv

-15 °C

-15 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

2.69 kW

2.89 kW

COP Tj = -7°C

3.26

2.45

Cdh Tj = -7 °C

0.980

0.990

Pdh Tj = +2°C

1.90 kW

1.85 kW

COP Tj = +2°C

4.66

3.65

Cdh Tj = +2 °C

0.960

0.970

Pdh Tj = +7°C

2.22 kW

2.21 kW

COP Tj = +7°C

6.04

5.01

Cdh Tj = +7 °C

0.960

0.960

Pdh Tj = 12°C

2.49 kW

2.56 kW

COP Tj = 12°C

6.79

6.46

Cdh Tj = +12 °C

0.960

0.960

Pdh Tj = Tbiv

3.82 kW

3.88 kW

COP Tj = Tbiv

2.01

1.67

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

3.70 kW

3.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.88

1.50

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

55 °C

55 °C

Poff

8 W

8 W

PTO

17 W

17 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

4.68 kW

4.76 kW

Annual energy consumption Qhe

3064 kWh

3930 kWh

Pdh Tj = -15°C (if TOL<-20°C)

3.82

3.88

COP Tj = -15°C (if TOL<-20°C)

2.01

1.67

Cdh Tj = -15 °C

0.990

0.990

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

52 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

130 %

Prated

4.45 kW

4.88 kW

SCOP

4.50

3.33

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

3.93 kW

4.32 kW

COP Tj = -7°C

2.79

2.11

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

2.17 kW

2.46 kW

COP Tj = +2°C

4.46

3.19

Cdh Tj = +2 °C

0.970

0.980

Pdh Tj = +7°C

2.26 kW

2.12 kW

COP Tj = +7°C

5.99

4.40

Cdh Tj = +7 °C

0.960

0.960

Pdh Tj = 12°C

2.54 kW

2.52 kW

COP Tj = 12°C

7.16

6.03

Cdh Tj = +12 °C

0.960

0.960

Pdh Tj = Tbiv

4.42 kW

4.63 kW

COP Tj = Tbiv

2.21

1.86

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.42 kW

4.63 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.21

1.86

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

55 °C

55 °C

Poff

8 W

8 W

PTO

17 W

17 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

kW

kW

Annual energy consumption Qhe

2045 kWh

3029 kWh

HA 3-6 O 230V
Configure model
Model name
HA 3-6 O 230V
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

3.32 kW

4.79 kW

El input

0.69 kW

1.71 kW

COP

4.80

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

51 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

208 %

153 %

Prated

3.53 kW

3.55 kW

SCOP

5.29

3.89

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

3.53 kW

3.55 kW

COP Tj = +2°C

3.42

2.31

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

2.18 kW

2.44 kW

COP Tj = +7°C

4.97

3.37

Cdh Tj = +7 °C

0.97

0.98

Pdh Tj = 12°C

2.40 kW

2.37 kW

COP Tj = 12°C

6.45

5.11

Cdh Tj = +12 °C

0.96

0.97

Pdh Tj = Tbiv

3.53 kW

3.55 kW

COP Tj = Tbiv

3.42

2.31

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

3.53 kW

3.55 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.42

2.31

WTOL

55 °C

55 °C

Poff

8 W

8 W

PTO

17 W

17 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

892 kWh

1219 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

51 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

147 %

108 %

Prated

3.34 kW

3.15 kW

SCOP

3.75

2.78

Tbiv

-15 °C

-15 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

2.11 kW

1.92 kW

COP Tj = -7°C

3.34

2.25

Cdh Tj = -7 °C

0.980

0.980

Pdh Tj = +2°C

1.78 kW

1.71 kW

COP Tj = +2°C

4.45

3.46

Cdh Tj = +2 °C

0.960

0.970

Pdh Tj = +7°C

2.16 kW

2.09 kW

COP Tj = +7°C

6.23

4.71

Cdh Tj = +7 °C

0.960

0.970

Pdh Tj = 12°C

2.49 kW

2.44 kW

COP Tj = 12°C

7.22

6.17

Cdh Tj = +12 °C

0.960

0.960

Pdh Tj = Tbiv

2.72 kW

2.57 kW

COP Tj = Tbiv

2.16

1.61

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.69 kW

2.43 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.06

1.46

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

55 °C

55 °C

Poff

8 W

8 W

PTO

17 W

17 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

3.34 kW

3.15 kW

Annual energy consumption Qhe

2192 kWh

2787 kWh

Pdh Tj = -15°C (if TOL<-20°C)

 

 

COP Tj = -15°C (if TOL<-20°C)

 

 

Cdh Tj = -15 °C

 

 

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

51 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

124 %

Prated

4.19 kW

4.18 kW

SCOP

4.50

3.18

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

3.71 kW

3.69 kW

COP Tj = -7°C

3.04

2.08

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

2.18 kW

2.32 kW

COP Tj = +2°C

4.40

3.01

Cdh Tj = +2 °C

0.970

0.980

Pdh Tj = +7°C

2.15 kW

2.03 kW

COP Tj = +7°C

5.96

4.28

Cdh Tj = +7 °C

0.960

0.970

Pdh Tj = 12°C

2.41 kW

2.42 kW

COP Tj = 12°C

7.04

5.84

Cdh Tj = +12 °C

0.960

0.960

Pdh Tj = Tbiv

3.71 kW

3.69 kW

COP Tj = Tbiv

3.04

2.08

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

3.34 kW

3.31 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.51

1.81

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

55 °C

55 °C

Poff

8 W

8 W

PTO

17 W

17 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.84 kW

0.87 kW

Annual energy consumption Qhe

1923 kWh

2715 kWh

HA 3-6 O 230V B2
Configure model
Model name
HA 3-6 O 230V B2
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

3.32 kW

4.79 kW

El input

0.69 kW

1.71 kW

COP

4.80

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

51 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

200 %

148 %

Prated

3.53 kW

3.55 kW

SCOP

5.08

3.78

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

3.53 kW

3.55 kW

COP Tj = +2°C

3.42

2.31

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

2.18 kW

2.44 kW

COP Tj = +7°C

4.97

3.37

Cdh Tj = +7 °C

0.97

0.98

Pdh Tj = 12°C

2.40 kW

2.37 kW

COP Tj = 12°C

6.45

5.11

Cdh Tj = +12 °C

0.96

0.97

Pdh Tj = Tbiv

3.53 kW

3.55 kW

COP Tj = Tbiv

3.42

2.31

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

3.53 kW

3.55 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.42

2.31

WTOL

55 °C

55 °C

Poff

8 W

8 W

PTO

17 W

17 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

928 kWh

1255 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

51 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

146 %

108 %

Prated

3.34 kW

3.15 kW

SCOP

3.72

2.77

Tbiv

-15 °C

-15 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

2.11 kW

1.92 kW

COP Tj = -7°C

3.34

2.25

Cdh Tj = -7 °C

0.980

0.980

Pdh Tj = +2°C

1.78 kW

1.71 kW

COP Tj = +2°C

4.45

3.46

Cdh Tj = +2 °C

0.960

0.970

Pdh Tj = +7°C

2.16 kW

2.09 kW

COP Tj = +7°C

6.23

4.71

Cdh Tj = +7 °C

0.960

0.970

Pdh Tj = 12°C

2.49 kW

2.44 kW

COP Tj = 12°C

7.22

6.17

Cdh Tj = +12 °C

0.960

0.960

Pdh Tj = Tbiv

2.72 kW

2.57 kW

COP Tj = Tbiv

2.16

1.61

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.69 kW

2.43 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.06

1.46

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

55 °C

55 °C

Poff

8 W

8 W

PTO

17 W

17 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

3.34 kW

3.15 kW

Annual energy consumption Qhe

2210 kWh

2805 kWh

Pdh Tj = -15°C (if TOL<-20°C)

 

 

COP Tj = -15°C (if TOL<-20°C)

 

 

Cdh Tj = -15 °C

 

 

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

51 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

174 %

123 %

Prated

4.19 kW

4.18 kW

SCOP

4.43

3.14

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

3.71 kW

3.69 kW

COP Tj = -7°C

3.04

2.08

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

2.18 kW

2.32 kW

COP Tj = +2°C

4.40

3.01

Cdh Tj = +2 °C

0.970

0.980

Pdh Tj = +7°C

2.15 kW

2.03 kW

COP Tj = +7°C

5.96

4.28

Cdh Tj = +7 °C

0.960

0.970

Pdh Tj = 12°C

2.41 kW

2.42 kW

COP Tj = 12°C

7.04

5.84

Cdh Tj = +12 °C

0.960

0.960

Pdh Tj = Tbiv

3.71 kW

3.69 kW

COP Tj = Tbiv

3.04

2.08

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

3.34 kW

3.31 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.51

1.81

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

55 °C

55 °C

Poff

8 W

8 W

PTO

17 W

17 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.84 kW

0.87 kW

Annual energy consumption Qhe

1953 kWh

2745 kWh

HA 4-6 O 230V B3
Configure model
Model name
HA 4-6 O 230V B3
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4.07 kW

3.64 kW

El input

0.89 kW

1.28 kW

COP

4.59

2.83

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

50 dB(A)

52 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

220 %

155 %

Prated

3.40 kW

3.43 kW

SCOP

5.57

3.94

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

3.44 kW

3.43 kW

COP Tj = +2°C

3.36

2.28

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

2.33 kW

2.16 kW

COP Tj = +7°C

5.21

3.39

Cdh Tj = +7 °C

0.97

0.98

Pdh Tj = 12°C

2.57 kW

2.45 kW

COP Tj = 12°C

7.00

5.25

Cdh Tj = +12 °C

0.96

0.97

Pdh Tj = Tbiv

3.44 kW

3.43 kW

COP Tj = Tbiv

3.36

2.28

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

3.44 kW

3.43 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.36

2.28

WTOL

75 °C

75 °C

Poff

8 W

8 W

PTO

17 W

17 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

815 kWh

1164 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

50 dB(A)

52 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

152 %

113 %

Prated

4.00 kW

3.48 kW

SCOP

3.87

2.90

Tbiv

-15 °C

-15 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

2.42 kW

2.12 kW

COP Tj = -7°C

3.26

2.40

Cdh Tj = -7 °C

0.980

0.980

Pdh Tj = +2°C

1.92 kW

1.76 kW

COP Tj = +2°C

4.80

3.53

Cdh Tj = +2 °C

0.960

0.970

Pdh Tj = +7°C

2.26 kW

2.14 kW

COP Tj = +7°C

6.27

4.81

Cdh Tj = +7 °C

0.960

0.970

Pdh Tj = 12°C

2.59 kW

2.57 kW

COP Tj = 12°C

7.39

6.27

Cdh Tj = +12 °C

0.960

0.960

Pdh Tj = Tbiv

3.11 kW

2.84 kW

COP Tj = Tbiv

2.37

1.76

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

2.66 kW

2.41 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.02

1.47

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

75 °C

75 °C

Poff

8 W

8 W

PTO

17 W

17 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

4.00 kW

3.48 kW

Annual energy consumption Qhe

2543 kWh

2959 kWh

Pdh Tj = -15°C (if TOL<-20°C)

 

 

COP Tj = -15°C (if TOL<-20°C)

 

 

Cdh Tj = -15 °C

 

 

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

50 dB(A)

52 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

180 %

131 %

Prated

4.13 kW

4.22 kW

SCOP

4.56

3.34

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

3.65 kW

3.73 kW

COP Tj = -7°C

2.97

2.12

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

2.20 kW

2.28 kW

COP Tj = +2°C

4.48

3.24

Cdh Tj = +2 °C

0.970

0.980

Pdh Tj = +7°C

2.23 kW

2.11 kW

COP Tj = +7°C

6.02

4.45

Cdh Tj = +7 °C

0.960

0.970

Pdh Tj = 12°C

2.59 kW

2.54 kW

COP Tj = 12°C

7.39

5.97

Cdh Tj = +12 °C

0.960

0.960

Pdh Tj = Tbiv

3.65 kW

3.73 kW

COP Tj = Tbiv

2.97

2.12

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

3.65 kW

3.35 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.65

1.86

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

 

 

WTOL

75 °C

75 °C

Poff

8 W

8 W

PTO

17 W

17 W

PSB

17 W

17 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.48 kW

0.87 kW

Annual energy consumption Qhe

1870 kWh

2606 kWh