0,600 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
3.36 kW
4.83 kW
El input
0.69 kW
1.71 kW
COP
4.80
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
51 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233 %
157 %
Prated
4.96 kW
5.07 kW
SCOP
5.89
3.99
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
4.96 kW
5.07 kW
COP Tj = +2°C
3.35
2.30
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.42 kW
3.08 kW
COP Tj = +7°C
5.45
3.43
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
2.59 kW
2.42 kW
COP Tj = 12°C
7.25
5.17
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
4.96 kW
5.07 kW
COP Tj = Tbiv
3.35
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.96 kW
5.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.35
2.30
WTOL
70 °C
70 °C
Poff
8 W
8 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1125 kWh
1697 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
51 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
158 %
116 %
Prated
5.01 kW
4.76 kW
SCOP
4.02
2.98
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
3.22 kW
2.89 kW
COP Tj = -7°C
3.36
2.45
Cdh Tj = -7 °C
0.980
0.990
Pdh Tj = +2°C
1.92 kW
1.85 kW
COP Tj = +2°C
5.04
3.65
Cdh Tj = +2 °C
0.960
0.970
Pdh Tj = +7°C
2.33 kW
2.21 kW
COP Tj = +7°C
6.82
5.01
Cdh Tj = +7 °C
0.960
0.960
Pdh Tj = 12°C
2.62 kW
2.56 kW
COP Tj = 12°C
7.24
6.46
Cdh Tj = +12 °C
0.960
0.960
Pdh Tj = Tbiv
4.09 kW
3.88 kW
COP Tj = Tbiv
2.13
1.67
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.04 kW
3.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.00
1.50
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
70 °C
70 °C
Poff
8 W
8 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.01 kW
4.76 kW
Annual energy consumption Qhe
3076 kWh
3930 kWh
Pdh Tj = -15°C (if TOL<-20°C)
4.09
3.88
COP Tj = -15°C (if TOL<-20°C)
2.13
1.67
Cdh Tj = -15 °C
0.990
0.990
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
51 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
130 %
Prated
4.81 kW
4.88 kW
SCOP
4.66
3.33
Tbiv
-7 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.26 kW
4.32 kW
COP Tj = -7°C
2.78
2.11
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
2.70 kW
2.46 kW
COP Tj = +2°C
4.62
3.19
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
2.29 kW
2.12 kW
COP Tj = +7°C
6.41
4.40
Cdh Tj = +7 °C
0.960
0.970
Pdh Tj = 12°C
2.61 kW
2.52 kW
COP Tj = 12°C
7.61
6.03
Cdh Tj = +12 °C
0.960
0.960
Pdh Tj = Tbiv
4.26 kW
4.63 kW
COP Tj = Tbiv
2.78
1.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.13 kW
4.63 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.43
1.86
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
70 °C
70 °C
Poff
8 W
8 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.68 kW
kW
Annual energy consumption Qhe
2135 kWh
3029 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
3.36 kW
4.83 kW
El input
0.69 kW
1.71 kW
COP
4.80
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
51 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
225 %
153 %
Prated
4.96 kW
5.07 kW
SCOP
5.71
3.91
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
4.96 kW
5.07 kW
COP Tj = +2°C
3.35
2.30
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.42 kW
3.08 kW
COP Tj = +7°C
5.45
3.43
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
2.59 kW
2.42 kW
COP Tj = 12°C
7.25
5.17
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
4.96 kW
5.07 kW
COP Tj = Tbiv
3.35
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.96 kW
5.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.35
2.30
WTOL
70 °C
70 °C
Poff
8 W
8 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1161 kWh
1733 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
51 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
157 %
116 %
Prated
5.01 kW
4.76 kW
SCOP
3.99
2.97
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
3.22 kW
2.89 kW
COP Tj = -7°C
3.36
2.45
Cdh Tj = -7 °C
0.980
0.990
Pdh Tj = +2°C
1.92 kW
1.85 kW
COP Tj = +2°C
5.04
3.65
Cdh Tj = +2 °C
0.960
0.970
Pdh Tj = +7°C
2.33 kW
2.21 kW
COP Tj = +7°C
6.82
5.01
Cdh Tj = +7 °C
0.960
0.960
Pdh Tj = 12°C
2.62 kW
2.56 kW
COP Tj = 12°C
7.24
6.46
Cdh Tj = +12 °C
0.960
0.960
Pdh Tj = Tbiv
4.09 kW
3.88 kW
COP Tj = Tbiv
2.13
1.67
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.04 kW
3.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.00
1.50
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
70 °C
70 °C
Poff
8 W
8 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.01 kW
4.76 kW
Annual energy consumption Qhe
3094 kWh
3948 kWh
Pdh Tj = -15°C (if TOL<-20°C)
4.09
3.88
COP Tj = -15°C (if TOL<-20°C)
2.13
1.67
Cdh Tj = -15 °C
0.990
0.990
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
51 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
181 %
129 %
Prated
4.81 kW
4.88 kW
SCOP
4.59
3.30
Tbiv
-7 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.26 kW
4.32 kW
COP Tj = -7°C
2.78
2.11
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
2.70 kW
2.46 kW
COP Tj = +2°C
4.62
3.19
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
2.29 kW
2.12 kW
COP Tj = +7°C
6.41
4.40
Cdh Tj = +7 °C
0.960
0.970
Pdh Tj = 12°C
2.61 kW
2.52 kW
COP Tj = 12°C
7.61
6.03
Cdh Tj = +12 °C
0.960
0.960
Pdh Tj = Tbiv
4.26 kW
4.63 kW
COP Tj = Tbiv
2.78
1.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.13 kW
4.63 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.43
1.86
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
70 °C
70 °C
Poff
8 W
8 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.68 kW
kW
Annual energy consumption Qhe
2165 kWh
3059 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.21 kW
4.83 kW
El input
0.95 kW
1.71 kW
COP
4.39
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
52 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
215 %
157 %
Prated
4.75 kW
5.07 kW
SCOP
5.44
3.99
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
4.75 kW
5.07 kW
COP Tj = +2°C
3.22
2.30
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
3.33 kW
3.08 kW
COP Tj = +7°C
5.07
3.43
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
2.48 kW
2.42 kW
COP Tj = 12°C
6.61
5.17
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
4.75 kW
5.07 kW
COP Tj = Tbiv
3.22
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.75 kW
5.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.22
2.30
WTOL
55 °C
55 °C
Poff
8 W
8 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1166 kWh
1697 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
52 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
148 %
116 %
Prated
4.68 kW
4.76 kW
SCOP
3.77
2.98
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
2.69 kW
2.89 kW
COP Tj = -7°C
3.26
2.45
Cdh Tj = -7 °C
0.980
0.990
Pdh Tj = +2°C
1.90 kW
1.85 kW
COP Tj = +2°C
4.66
3.65
Cdh Tj = +2 °C
0.960
0.970
Pdh Tj = +7°C
2.22 kW
2.21 kW
COP Tj = +7°C
6.04
5.01
Cdh Tj = +7 °C
0.960
0.960
Pdh Tj = 12°C
2.49 kW
2.56 kW
COP Tj = 12°C
6.79
6.46
Cdh Tj = +12 °C
0.960
0.960
Pdh Tj = Tbiv
3.82 kW
3.88 kW
COP Tj = Tbiv
2.01
1.67
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.70 kW
3.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.88
1.50
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
55 °C
55 °C
Poff
8 W
8 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.68 kW
4.76 kW
Annual energy consumption Qhe
3064 kWh
3930 kWh
Pdh Tj = -15°C (if TOL<-20°C)
3.82
3.88
COP Tj = -15°C (if TOL<-20°C)
2.01
1.67
Cdh Tj = -15 °C
0.990
0.990
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
52 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
130 %
Prated
4.45 kW
4.88 kW
SCOP
4.50
3.33
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.93 kW
4.32 kW
COP Tj = -7°C
2.79
2.11
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
2.17 kW
2.46 kW
COP Tj = +2°C
4.46
3.19
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
2.26 kW
2.12 kW
COP Tj = +7°C
5.99
4.40
Cdh Tj = +7 °C
0.960
0.960
Pdh Tj = 12°C
2.54 kW
2.52 kW
COP Tj = 12°C
7.16
6.03
Cdh Tj = +12 °C
0.960
0.960
Pdh Tj = Tbiv
4.42 kW
4.63 kW
COP Tj = Tbiv
2.21
1.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.42 kW
4.63 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.21
1.86
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
55 °C
55 °C
Poff
8 W
8 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
kW
kW
Annual energy consumption Qhe
2045 kWh
3029 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
3.32 kW
4.79 kW
El input
0.69 kW
1.71 kW
COP
4.80
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
51 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
208 %
153 %
Prated
3.53 kW
3.55 kW
SCOP
5.29
3.89
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
3.53 kW
3.55 kW
COP Tj = +2°C
3.42
2.31
Cdh Tj = +2 °C
0.98
0.99
Pdh Tj = +7°C
2.18 kW
2.44 kW
COP Tj = +7°C
4.97
3.37
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
2.40 kW
2.37 kW
COP Tj = 12°C
6.45
5.11
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
3.53 kW
3.55 kW
COP Tj = Tbiv
3.42
2.31
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.53 kW
3.55 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.42
2.31
WTOL
55 °C
55 °C
Poff
8 W
8 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
892 kWh
1219 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
51 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
147 %
108 %
Prated
3.34 kW
3.15 kW
SCOP
3.75
2.78
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
2.11 kW
1.92 kW
COP Tj = -7°C
3.34
2.25
Cdh Tj = -7 °C
0.980
0.980
Pdh Tj = +2°C
1.78 kW
1.71 kW
COP Tj = +2°C
4.45
3.46
Cdh Tj = +2 °C
0.960
0.970
Pdh Tj = +7°C
2.16 kW
2.09 kW
COP Tj = +7°C
6.23
4.71
Cdh Tj = +7 °C
0.960
0.970
Pdh Tj = 12°C
2.49 kW
2.44 kW
COP Tj = 12°C
7.22
6.17
Cdh Tj = +12 °C
0.960
0.960
Pdh Tj = Tbiv
2.72 kW
2.57 kW
COP Tj = Tbiv
2.16
1.61
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.69 kW
2.43 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.06
1.46
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
55 °C
55 °C
Poff
8 W
8 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.34 kW
3.15 kW
Annual energy consumption Qhe
2192 kWh
2787 kWh
Pdh Tj = -15°C (if TOL<-20°C)
COP Tj = -15°C (if TOL<-20°C)
Cdh Tj = -15 °C
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
51 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
124 %
Prated
4.19 kW
4.18 kW
SCOP
4.50
3.18
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.71 kW
3.69 kW
COP Tj = -7°C
3.04
2.08
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
2.18 kW
2.32 kW
COP Tj = +2°C
4.40
3.01
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
2.15 kW
2.03 kW
COP Tj = +7°C
5.96
4.28
Cdh Tj = +7 °C
0.960
0.970
Pdh Tj = 12°C
2.41 kW
2.42 kW
COP Tj = 12°C
7.04
5.84
Cdh Tj = +12 °C
0.960
0.960
Pdh Tj = Tbiv
3.71 kW
3.69 kW
COP Tj = Tbiv
3.04
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.34 kW
3.31 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.51
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
55 °C
55 °C
Poff
8 W
8 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.84 kW
0.87 kW
Annual energy consumption Qhe
1923 kWh
2715 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
3.32 kW
4.79 kW
El input
0.69 kW
1.71 kW
COP
4.80
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
51 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
148 %
Prated
3.53 kW
3.55 kW
SCOP
5.08
3.78
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
3.53 kW
3.55 kW
COP Tj = +2°C
3.42
2.31
Cdh Tj = +2 °C
0.98
0.99
Pdh Tj = +7°C
2.18 kW
2.44 kW
COP Tj = +7°C
4.97
3.37
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
2.40 kW
2.37 kW
COP Tj = 12°C
6.45
5.11
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
3.53 kW
3.55 kW
COP Tj = Tbiv
3.42
2.31
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.53 kW
3.55 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.42
2.31
WTOL
55 °C
55 °C
Poff
8 W
8 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
928 kWh
1255 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
51 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
146 %
108 %
Prated
3.34 kW
3.15 kW
SCOP
3.72
2.77
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
2.11 kW
1.92 kW
COP Tj = -7°C
3.34
2.25
Cdh Tj = -7 °C
0.980
0.980
Pdh Tj = +2°C
1.78 kW
1.71 kW
COP Tj = +2°C
4.45
3.46
Cdh Tj = +2 °C
0.960
0.970
Pdh Tj = +7°C
2.16 kW
2.09 kW
COP Tj = +7°C
6.23
4.71
Cdh Tj = +7 °C
0.960
0.970
Pdh Tj = 12°C
2.49 kW
2.44 kW
COP Tj = 12°C
7.22
6.17
Cdh Tj = +12 °C
0.960
0.960
Pdh Tj = Tbiv
2.72 kW
2.57 kW
COP Tj = Tbiv
2.16
1.61
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.69 kW
2.43 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.06
1.46
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
55 °C
55 °C
Poff
8 W
8 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.34 kW
3.15 kW
Annual energy consumption Qhe
2210 kWh
2805 kWh
Pdh Tj = -15°C (if TOL<-20°C)
COP Tj = -15°C (if TOL<-20°C)
Cdh Tj = -15 °C
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
51 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
174 %
123 %
Prated
4.19 kW
4.18 kW
SCOP
4.43
3.14
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.71 kW
3.69 kW
COP Tj = -7°C
3.04
2.08
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
2.18 kW
2.32 kW
COP Tj = +2°C
4.40
3.01
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
2.15 kW
2.03 kW
COP Tj = +7°C
5.96
4.28
Cdh Tj = +7 °C
0.960
0.970
Pdh Tj = 12°C
2.41 kW
2.42 kW
COP Tj = 12°C
7.04
5.84
Cdh Tj = +12 °C
0.960
0.960
Pdh Tj = Tbiv
3.71 kW
3.69 kW
COP Tj = Tbiv
3.04
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.34 kW
3.31 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.51
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
55 °C
55 °C
Poff
8 W
8 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.84 kW
0.87 kW
Annual energy consumption Qhe
1953 kWh
2745 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.07 kW
3.64 kW
El input
0.89 kW
1.28 kW
COP
4.59
2.83
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
50 dB(A)
52 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
220 %
155 %
Prated
3.40 kW
3.43 kW
SCOP
5.57
3.94
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
3.44 kW
3.43 kW
COP Tj = +2°C
3.36
2.28
Cdh Tj = +2 °C
0.98
0.99
Pdh Tj = +7°C
2.33 kW
2.16 kW
COP Tj = +7°C
5.21
3.39
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
2.57 kW
2.45 kW
COP Tj = 12°C
7.00
5.25
Cdh Tj = +12 °C
0.96
0.97
Pdh Tj = Tbiv
3.44 kW
3.43 kW
COP Tj = Tbiv
3.36
2.28
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.44 kW
3.43 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.36
2.28
WTOL
75 °C
75 °C
Poff
8 W
8 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
815 kWh
1164 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
50 dB(A)
52 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
152 %
113 %
Prated
4.00 kW
3.48 kW
SCOP
3.87
2.90
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
2.42 kW
2.12 kW
COP Tj = -7°C
3.26
2.40
Cdh Tj = -7 °C
0.980
0.980
Pdh Tj = +2°C
1.92 kW
1.76 kW
COP Tj = +2°C
4.80
3.53
Cdh Tj = +2 °C
0.960
0.970
Pdh Tj = +7°C
2.26 kW
2.14 kW
COP Tj = +7°C
6.27
4.81
Cdh Tj = +7 °C
0.960
0.970
Pdh Tj = 12°C
2.59 kW
2.57 kW
COP Tj = 12°C
7.39
6.27
Cdh Tj = +12 °C
0.960
0.960
Pdh Tj = Tbiv
3.11 kW
2.84 kW
COP Tj = Tbiv
2.37
1.76
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.66 kW
2.41 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.02
1.47
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
75 °C
75 °C
Poff
8 W
8 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.00 kW
3.48 kW
Annual energy consumption Qhe
2543 kWh
2959 kWh
Pdh Tj = -15°C (if TOL<-20°C)
COP Tj = -15°C (if TOL<-20°C)
Cdh Tj = -15 °C
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
50 dB(A)
52 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
131 %
Prated
4.13 kW
4.22 kW
SCOP
4.56
3.34
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.65 kW
3.73 kW
COP Tj = -7°C
2.97
2.12
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
2.20 kW
2.28 kW
COP Tj = +2°C
4.48
3.24
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
2.23 kW
2.11 kW
COP Tj = +7°C
6.02
4.45
Cdh Tj = +7 °C
0.960
0.970
Pdh Tj = 12°C
2.59 kW
2.54 kW
COP Tj = 12°C
7.39
5.97
Cdh Tj = +12 °C
0.960
0.960
Pdh Tj = Tbiv
3.65 kW
3.73 kW
COP Tj = Tbiv
2.97
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.65 kW
3.35 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.65
1.86
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
75 °C
75 °C
Poff
8 W
8 W
PTO
17 W
17 W
PSB
17 W
17 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.48 kW
0.87 kW
Annual energy consumption Qhe
1870 kWh
2606 kWh