Certificate holders

Subtype

24. YUTAKI S (N2) & S Combi (NW2) 2.5HP R32

Certificate Holder
Johnson Controls-Hitachi AirConditioning Spain
Ronda Shimizu, 1. Pol. Ind. Can Torrella
08233 Vacarisses, Barcelona
Spain
Registration number
041-K002-71
Certification Body
BRE Global Limited
Subtype title
24. YUTAKI S (N2) & S Combi (NW2) 2.5HP R32
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,200 kg

Certification Date
13.09.2024
Testing basis
Heat Pump Keymark Scheme Rules v14
Generate PDF Export model CSV Download certificate
  • Number of models 4

Models

RAS-2.5WHVRP2E - RWM-2.5R2E - Heating only
Configure model
Model name
RAS-2.5WHVRP2E - RWM-2.5R2E - Heating only
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.00 kW

6.00 kW

El input

1.20 kW

2.22 kW

COP

5.00

2.70

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

51 dB(A)

51 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

125 %

Prated

5.80 kW

5.00 kW

SCOP

4.45

3.21

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.10 kW

4.42 kW

COP Tj = -7°C

2.50

1.85

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

3.10 kW

2.69 kW

COP Tj = +2°C

4.45

3.15

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.00 kW

2.43 kW

COP Tj = +7°C

6.65

4.80

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.05 kW

2.80 kW

COP Tj = 12°C

9.00

6.80

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

5.10 kW

4.42 kW

COP Tj = Tbiv

2.50

1.85

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.30 kW

3.90 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.50

1.70

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

12 W

12 W

PTO

0 W

0 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.50 kW

1.10 kW

Annual energy consumption Qhe

2677 kWh

3218 kWh

RAS-2.5WHVRP2E - RWM-2.5R2E - with Cooling kit
Configure model
Model name
RAS-2.5WHVRP2E - RWM-2.5R2E - with Cooling kit
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.00 kW

6.00 kW

El input

1.20 kW

2.22 kW

COP

5.00

2.70

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

1.47 kW

1.19 kW

Cooling capacity

5.30

6.30

EER

3.60

5.30

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

5.30 kW

6.30 kW

SEER

5.48

8.50

Pdc Tj = 35°C

5.30 kW

6.30 kW

EER Tj = 35°C

3.60

5.30

Cdc Tj = 35 °C

0.900

0.900

Pdc Tj = 30°C

3.91 kW

4.64 kW

EER Tj = 30°C

4.50

7.00

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

2.51 kW

2.98 kW

EER Tj = 25°C

6.30

9.90

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

2.88 kW

2.65 kW

EER Tj = 20°C

8.20

12.61

Cdc Tj = 20 °C

0.900

0.900

Poff

12 W

12 W

PTO

0 W

0 W

PSB

12 W

12 W

PCK

0 W

0 W

Annual energy consumption Qce

581 kWh

445 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

51 dB(A)

51 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

127 %

Prated

5.80 kW

5.00 kW

SCOP

4.52

3.25

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.10 kW

4.42 kW

COP Tj = -7°C

2.50

1.85

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

3.10 kW

2.69 kW

COP Tj = +2°C

4.45

3.15

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.00 kW

2.43 kW

COP Tj = +7°C

6.65

4.80

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.05 kW

2.80 kW

COP Tj = 12°C

9.00

6.80

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

5.10 kW

4.42 kW

COP Tj = Tbiv

2.50

1.85

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.30 kW

3.90 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.50

1.70

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

12 W

12 W

PTO

0 W

0 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.50 kW

1.10 kW

Annual energy consumption Qhe

2633 kWh

3149 kWh

RAS-2.5WHVRP2E - RWD-2.5RW2E-220S - Heating only
Configure model
Model name
RAS-2.5WHVRP2E - RWD-2.5RW2E-220S - Heating only
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.00 kW

6.00 kW

El input

1.20 kW

2.20 kW

COP

5.00

2.70

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

51 dB(A)

51 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

175 %

125 %

Prated

5.80 kW

5.00 kW

SCOP

4.45

3.21

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.10 kW

4.42 kW

COP Tj = -7°C

2.50

1.85

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

3.10 kW

2.69 kW

COP Tj = +2°C

4.45

3.15

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.00 kW

2.43 kW

COP Tj = +7°C

6.65

4.80

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.05 kW

2.80 kW

COP Tj = 12°C

9.00

6.80

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

5.10 kW

4.42 kW

COP Tj = Tbiv

2.50

1.85

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.30 kW

3.90 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.50

1.70

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

12 W

12 W

PTO

0 W

0 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.50 kW

1.10 kW

Annual energy consumption Qhe

2677 kWh

3218 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

126 %

COP

3.10

Heating up time

1:40 h:min

Standby power input

32.0 W

Reference hot water temperature

52.6 °C

Mixed water at 40°C

283 l

RAS-2.5WHVRP2E - RWD-2.5RW2E-220S - with Cooling kit
Configure model
Model name
RAS-2.5WHVRP2E - RWD-2.5RW2E-220S - with Cooling kit
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.00 kW

6.00 kW

El input

1.20 kW

2.22 kW

COP

5.00

2.70

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

1.47 kW

1.19 kW

Cooling capacity

5.30

6.30

EER

3.60

5.30

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

5.30 kW

6.30 kW

SEER

5.48

8.50

Pdc Tj = 35°C

5.30 kW

6.30 kW

EER Tj = 35°C

3.60

5.30

Cdc Tj = 35 °C

0.900

0.900

Pdc Tj = 30°C

3.91 kW

4.64 kW

EER Tj = 30°C

4.50

7.00

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

2.51 kW

2.98 kW

EER Tj = 25°C

6.30

9.90

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

2.88 kW

2.65 kW

EER Tj = 20°C

8.20

12.61

Cdc Tj = 20 °C

0.900

0.900

Poff

12 W

12 W

PTO

0 W

0 W

PSB

12 W

12 W

PCK

0 W

0 W

Annual energy consumption Qce

581 kWh

445 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

51 dB(A)

51 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

127 %

Prated

5.80 kW

5.00 kW

SCOP

4.52

3.25

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.10 kW

4.42 kW

COP Tj = -7°C

2.50

1.85

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

3.10 kW

2.69 kW

COP Tj = +2°C

4.45

3.15

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.00 kW

2.43 kW

COP Tj = +7°C

6.65

4.80

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.05 kW

2.80 kW

COP Tj = 12°C

9.00

6.80

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

5.10 kW

4.42 kW

COP Tj = Tbiv

2.50

1.85

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.30 kW

3.90 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.50

1.70

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

12 W

12 W

PTO

0 W

0 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.50 kW

1.10 kW

Annual energy consumption Qhe

2633 kWh

3174 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

L

Efficiency ηDHW

126 %

126 %

COP

3.10

3.10

Heating up time

1:40 h:min

1:40 h:min

Standby power input

34.0 W

32.0 W

Reference hot water temperature

52.6 °C

52.6 °C

Mixed water at 40°C

283 l

283 l