1,000 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.00 kW
8.00 kW
El input
1.73 kW
2.86 kW
COP
4.60
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
51 dB(A)
51 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
125 %
Prated
6.70 kW
5.80 kW
SCOP
4.46
3.20
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.90 kW
5.10 kW
COP Tj = -7°C
2.70
1.85
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.59 kW
3.10 kW
COP Tj = +2°C
4.30
3.05
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.20 kW
2.43 kW
COP Tj = +7°C
6.60
4.73
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.50 kW
2.80 kW
COP Tj = 12°C
9.70
7.51
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
5.90 kW
5.10 kW
COP Tj = Tbiv
2.70
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.60 kW
5.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.70
1.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
12 W
12 W
PTO
0 W
0 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.10 kW
0.80 kW
Annual energy consumption Qhe
3088 kWh
3722 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.00 kW
8.00 kW
El input
1.73 kW
2.86 kW
COP
4.60
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.94 kW
1.40 kW
Cooling capacity
6.50
7.00
EER
3.35
5.00
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
6.50 kW
7.00 kW
SEER
5.27
8.35
Pdc Tj = 35°C
6.50 kW
7.00 kW
EER Tj = 35°C
3.35
5.00
Cdc Tj = 35 °C
0.900
0.900
Pdc Tj = 30°C
4.79 kW
5.16 kW
EER Tj = 30°C
4.50
6.40
Cdc Tj = 30 °C
0.900
0.900
Pdc Tj = 25°C
2.90 kW
3.32 kW
EER Tj = 25°C
6.00
10.00
Cdc Tj = 25 °C
0.900
0.900
Pdc Tj = 20°C
3.40 kW
3.60 kW
EER Tj = 20°C
7.50
13.50
Cdc Tj = 20 °C
0.900
0.900
Poff
12 W
12 W
PTO
0 W
0 W
PSB
12 W
12 W
PCK
0 W
0 W
Annual energy consumption Qce
740 kWh
503 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
51 dB(A)
51 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
127 %
Prated
6.70 kW
5.80 kW
SCOP
4.53
3.24
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.90 kW
5.10 kW
COP Tj = -7°C
2.70
1.85
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
3.59 kW
3.10 kW
COP Tj = +2°C
4.30
3.05
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
3.20 kW
2.43 kW
COP Tj = +7°C
6.60
4.73
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.50 kW
2.80 kW
COP Tj = 12°C
9.70
7.51
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
5.90 kW
5.10 kW
COP Tj = Tbiv
2.70
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.60 kW
5.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.70
1.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
12 W
12 W
PTO
0 W
0 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.10 kW
0.80 kW
Annual energy consumption Qhe
3045 kWh
3678 kWh