8,800 kg
Brine/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
50.31 kW
48.10 kW
El input
11.06 kW
15.92 kW
COP
4.55
3.02
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
50 dB(A)
50 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
203 %
158 %
Prated
84.07 kW
81.29 kW
SCOP
5.27
4.16
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
84.07 kW
81.29 kW
COP Tj = +2°C
3.95
2.91
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
54.05 kW
52.26 kW
COP Tj = +7°C
4.94
3.69
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
24.02 kW
23.23 kW
COP Tj = 12°C
5.84
4.87
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
84.07 kW
81.29 kW
COP Tj = Tbiv
3.95
2.91
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
84.07 kW
81.29 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.95
2.91
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
21295 kWh
26114 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
50 dB(A)
50 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
209 %
166 %
Prated
84.07 kW
81.29 kW
SCOP
5.44
4.35
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
50.89 kW
49.20 kW
COP Tj = -7°C
5.11
3.92
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
30.97 kW
29.95 kW
COP Tj = +2°C
5.91
4.84
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
22.81 kW
23.10 kW
COP Tj = +7°C
5.80
5.00
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
22.79 kW
23.19 kW
COP Tj = 12°C
5.58
5.06
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
84.07 kW
81.29 kW
COP Tj = Tbiv
3.95
2.91
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
84.07 kW
81.29 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.95
2.91
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
38123 kWh
46029 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
50 dB(A)
50 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
202 %
159 %
Prated
84.07 kW
81.29 kW
SCOP
5.25
4.18
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
74.37 kW
71.91 kW
COP Tj = -7°C
4.23
3.15
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
45.27 kW
43.77 kW
COP Tj = +2°C
5.26
4.15
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
29.10 kW
28.14 kW
COP Tj = +7°C
5.95
4.91
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
22.80 kW
23.00 kW
COP Tj = 12°C
5.72
4.94
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
84.07 kW
81.29 kW
COP Tj = Tbiv
3.95
2.91
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
84.07 kW
81.29 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.95
2.91
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
33054 kWh
40141 kWh
Water/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
50.31 kW
48.10 kW
El input
11.06 kW
15.92 kW
COP
4.55
3.02
Warmer Climate
EN 14825
Low temperature
Medium temperature
ηs
307 %
221 %
Prated
75.12 kW
79.55 kW
SCOP
7.88
5.72
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
75.12 kW
79.55 kW
COP Tj = +2°C
5.44
3.77
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
48.29 kW
51.14 kW
COP Tj = +7°C
7.27
4.96
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
28.61 kW
28.49 kW
COP Tj = 12°C
8.99
6.92
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
75.12 kW
79.55 kW
COP Tj = Tbiv
5.44
3.77
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
75.12 kW
79.55 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.44
3.77
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
12740 kWh
18594 kWh
Colder Climate
EN 14825
Low temperature
Medium temperature
ηs
320 %
229 %
Prated
75.12 kW
79.55 kW
SCOP
8.20
5.93
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
45.47 kW
48.15 kW
COP Tj = -7°C
7.58
5.25
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
27.68 kW
29.31 kW
COP Tj = +2°C
9.08
6.62
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
28.63 kW
28.55 kW
COP Tj = +7°C
9.11
7.13
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
28.60 kW
28.61 kW
COP Tj = 12°C
8.86
7.38
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
75.12 kW
79.55 kW
COP Tj = Tbiv
5.44
3.77
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
75.12 kW
79.55 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.44
3.77
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
22572 kWh
33084 kWh
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
303 %
219 %
Prated
75.12 kW
79.55 kW
SCOP
7.78
5.68
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
66.45 kW
70.37 kW
COP Tj = -7°C
5.86
4.11
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
40.45 kW
42.83 kW
COP Tj = +2°C
7.78
5.61
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
28.63 kW
27.54 kW
COP Tj = +7°C
9.07
6.84
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
28.63 kW
28.56 kW
COP Tj = 12°C
9.08
7.16
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
75.12 kW
79.55 kW
COP Tj = Tbiv
5.44
3.77
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
75.12 kW
79.55 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.44
5.44
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
19949 kWh
28911 kWh