1,700 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
21.00 kW
19.60 kW
El input
4.31 kW
6.13 kW
COP
4.87
3.20
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
5.26 kW
Cooling capacity
17.40
EER
3.31
EN 14825
+7°C/+12°C
Pdesignc
17.40 kW
SEER
5.27
Pdc Tj = 35°C
17.40 kW
EER Tj = 35°C
3.31
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
12.80 kW
EER Tj = 30°C
4.44
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
9.22 kW
EER Tj = 25°C
5.84
Cdc Tj = 25 °C
0.986
Pdc Tj = 20°C
9.61 kW
EER Tj = 20°C
7.12
Cdc Tj = 20 °C
0.984
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
1981 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
187 %
145 %
Prated
20.00 kW
19.00 kW
SCOP
4.75
3.70
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
17.40 kW
16.60 kW
COP Tj = -7°C
2.92
2.12
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
10.60 kW
10.20 kW
COP Tj = +2°C
4.41
3.60
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
9.50 kW
9.20 kW
COP Tj = +7°C
6.90
5.15
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
11.10 kW
10.80 kW
COP Tj = 12°C
8.48
6.47
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
17.40 kW
16.60 kW
COP Tj = Tbiv
2.92
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.80 kW
15.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.51
1.82
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
69 °C
69 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.20 kW
3.90 kW
Annual energy consumption Qhe
8561 kWh
10466 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
22.80 kW
21.60 kW
El input
4.78 kW
6.79 kW
COP
4.77
3.18
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
5.89 kW
Cooling capacity
18.90
EER
3.21
EN 14825
+7°C/+12°C
Pdesignc
18.90 kW
SEER
5.27
Pdc Tj = 35°C
18.90 kW
EER Tj = 35°C
3.21
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
13.90 kW
EER Tj = 30°C
4.37
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
9.32 kW
EER Tj = 25°C
5.90
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
9.66 kW
EER Tj = 20°C
7.16
Cdc Tj = 20 °C
0.984
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
2151 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
186 %
147 %
Prated
21.00 kW
21.00 kW
SCOP
4.72
3.74
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
18.60 kW
18.20 kW
COP Tj = -7°C
2.81
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
11.30 kW
11.10 kW
COP Tj = +2°C
4.47
3.67
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
9.50 kW
9.20 kW
COP Tj = +7°C
6.81
5.18
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
11.10 kW
10.80 kW
COP Tj = 12°C
8.45
6.62
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
18.60 kW
18.20 kW
COP Tj = Tbiv
2.81
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
17.00 kW
16.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
69 °C
69 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.00 kW
4.70 kW
Annual energy consumption Qhe
9199 kWh
11363 kWh