0,580 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.80 kW
5.25 kW
El input
1.18 kW
1.78 kW
COP
4.90
2.95
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
1.46 kW
Cooling capacity
4.60
EER
3.15
EN 14825
+7°C/+12°C
Pdesignc
4.60 kW
SEER
5.34
Pdc Tj = 35°C
4.60 kW
EER Tj = 35°C
3.15
Cdc Tj = 35 °C
Pdc Tj = 30°C
3.39 kW
EER Tj = 30°C
4.60
Cdc Tj = 30 °C
Pdc Tj = 25°C
2.18 kW
EER Tj = 25°C
6.43
Cdc Tj = 25 °C
Pdc Tj = 20°C
2.05 kW
EER Tj = 20°C
8.17
Cdc Tj = 20 °C
0.940
Poff
10 W
PTO
15 W
PSB
10 W
PCK
0 W
Annual energy consumption Qce
2760 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
48 dB(A)
50 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190 %
131 %
Prated
4.88 kW
4.87 kW
SCOP
4.82
3.34
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.32 kW
4.31 kW
COP Tj = -7°C
2.77
2.00
Cdh Tj = -7 °C
Pdh Tj = +2°C
2.63 kW
2.62 kW
COP Tj = +2°C
4.59
3.14
Cdh Tj = +2 °C
Pdh Tj = +7°C
1.96 kW
1.69 kW
COP Tj = +7°C
7.05
4.74
Cdh Tj = +7 °C
0.946
0.961
Pdh Tj = 12°C
2.28 kW
2.25 kW
COP Tj = 12°C
9.08
6.69
Cdh Tj = +12 °C
0.940
0.955
Pdh Tj = Tbiv
4.32 kW
4.31 kW
COP Tj = Tbiv
2.77
2.00
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.38 kW
4.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.74
1.78
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
15 W
15 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.50 kW
0.87 kW
Annual energy consumption Qhe
2092 kWh
3010 kWh