1,270 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.33 kW
15.23 kW
El input
3.30 kW
4.52 kW
COP
4.94
3.37
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
3.70 kW
Cooling capacity
12.41
EER
3.35
EN 14825
+7°C/+12°C
Pdesignc
12.41 kW
SEER
5.02
Pdc Tj = 35°C
12.41 kW
EER Tj = 35°C
3.35
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
9.77 kW
EER Tj = 30°C
4.55
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
5.84 kW
EER Tj = 25°C
5.87
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
3.36 kW
EER Tj = 20°C
5.60
Cdc Tj = 20 °C
0.963
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
1483 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
191 %
149 %
Prated
14.60 kW
13.50 kW
SCOP
4.85
3.79
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.90 kW
11.90 kW
COP Tj = -7°C
2.93
2.30
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
8.30 kW
7.40 kW
COP Tj = +2°C
4.79
3.67
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
6.10 kW
6.00 kW
COP Tj = +7°C
6.45
4.91
Cdh Tj = +7 °C
0.977
0.982
Pdh Tj = 12°C
5.50 kW
7.10 kW
COP Tj = 12°C
8.11
7.67
Cdh Tj = +12 °C
0.969
0.976
Pdh Tj = Tbiv
12.90 kW
11.90 kW
COP Tj = Tbiv
2.93
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.00 kW
11.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.65
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
68 °C
68 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.60 kW
2.50 kW
Annual energy consumption Qhe
6233 kWh
7347 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
18.72 kW
17.38 kW
El input
4.05 kW
5.32 kW
COP
4.62
3.27
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
4.35 kW
Cooling capacity
13.75
EER
3.16
EN 14825
+7°C/+12°C
Pdesignc
13.75 kW
SEER
5.04
Pdc Tj = 35°C
13.75 kW
EER Tj = 35°C
3.16
Cdc Tj = 35 °C
1.000
Pdc Tj = 30°C
10.39 kW
EER Tj = 30°C
4.65
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
6.90 kW
EER Tj = 25°C
5.91
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
3.36 kW
EER Tj = 20°C
5.56
Cdc Tj = 20 °C
0.964
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
1635 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
146 %
Prated
15.00 kW
14.00 kW
SCOP
4.76
3.73
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.30 kW
12.40 kW
COP Tj = -7°C
2.86
2.26
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
8.30 kW
7.60 kW
COP Tj = +2°C
4.76
3.63
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
6.00 kW
6.00 kW
COP Tj = +7°C
6.28
4.93
Cdh Tj = +7 °C
0.977
0.982
Pdh Tj = 12°C
5.50 kW
6.80 kW
COP Tj = 12°C
7.84
6.72
Cdh Tj = +12 °C
0.969
0.978
Pdh Tj = Tbiv
13.30 kW
12.40 kW
COP Tj = Tbiv
2.86
2.26
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.40 kW
11.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.57
2.10
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
68 °C
68 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.60 kW
2.40 kW
Annual energy consumption Qhe
6496 kWh
7751 kWh