2,000 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.72 kW
20.31 kW
El input
3.68 kW
7.18 kW
COP
4.54
2.83
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
69 dB(A)
70 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
157 %
126 %
Prated
12.61 kW
12.67 kW
SCOP
4.00
3.21
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.15 kW
11.21 kW
COP Tj = -7°C
3.01
2.27
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
6.82 kW
6.91 kW
COP Tj = +2°C
3.67
2.81
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.90 kW
7.09 kW
COP Tj = +7°C
4.99
4.63
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
6.35 kW
7.16 kW
COP Tj = 12°C
6.50
5.76
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
11.15 kW
11.21 kW
COP Tj = Tbiv
3.01
2.27
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.66 kW
12.32 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.83
1.85
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
49 °C
49 °C
Poff
19 W
19 W
PTO
19 W
19 W
PSB
19 W
19 W
PCK
59 W
59 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.35 kW
Annual energy consumption Qhe
6512 kWh
8144 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.91 kW
20.61 kW
El input
3.92 kW
7.91 kW
COP
4.32
2.61
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
67 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
158 %
125 %
Prated
12.89 kW
12.93 kW
SCOP
4.01
3.20
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.41 kW
11.43 kW
COP Tj = -7°C
2.96
2.26
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
6.94 kW
7.05 kW
COP Tj = +2°C
3.73
2.92
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
7.54 kW
7.13 kW
COP Tj = +7°C
5.03
4.16
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
8.26 kW
8.38 kW
COP Tj = 12°C
6.38
5.77
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
11.41 kW
11.43 kW
COP Tj = Tbiv
2.96
2.26
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.85 kW
12.96 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.94
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
55 °C
55 °C
Poff
25 W
25 W
PTO
25 W
25 W
PSB
25 W
25 W
PCK
40 W
40 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.04 kW
0.00 kW
Annual energy consumption Qhe
6634 kWh
8341 kWh