0,760 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.60 kW
7.55 kW
El input
1.58 kW
2.40 kW
COP
4.80
3.15
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
2.13 kW
Cooling capacity
6.50
EER
3.05
EN 14825
+7°C/+12°C
Pdesignc
6.50 kW
SEER
5.28
Pdc Tj = 35°C
6.50 kW
EER Tj = 35°C
3.05
Cdc Tj = 35 °C
Pdc Tj = 30°C
4.79 kW
EER Tj = 30°C
4.49
Cdc Tj = 30 °C
Pdc Tj = 25°C
3.08 kW
EER Tj = 25°C
6.36
Cdc Tj = 25 °C
Pdc Tj = 20°C
2.95 kW
EER Tj = 20°C
7.33
Cdc Tj = 20 °C
0.963
Poff
10 W
PTO
15 W
PSB
10 W
PCK
0 W
Annual energy consumption Qce
3900 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
49 dB(A)
51 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
131 %
Prated
6.43 kW
6.45 kW
SCOP
4.69
3.34
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.69 kW
5.71 kW
COP Tj = -7°C
2.68
1.90
Cdh Tj = -7 °C
Pdh Tj = +2°C
3.46 kW
3.48 kW
COP Tj = +2°C
4.60
3.12
Cdh Tj = +2 °C
Pdh Tj = +7°C
2.80 kW
2.68 kW
COP Tj = +7°C
6.63
4.97
Cdh Tj = +7 °C
0.964
0.972
Pdh Tj = 12°C
3.23 kW
3.16 kW
COP Tj = 12°C
8.51
7.09
Cdh Tj = +12 °C
0.960
0.966
Pdh Tj = Tbiv
5.69 kW
5.71 kW
COP Tj = Tbiv
2.68
1.90
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.27 kW
5.29 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.36
1.71
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
75 °C
75 °C
Poff
10 W
10 W
PTO
15 W
15 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
1.16 kW
1.16 kW
Annual energy consumption Qhe
2829 kWh
3989 kWh