Certificate holders

Subtype

VITOCAL 100 A- (AF) 14

Certificate Holder
Viessmann Climate Solutions SE
Viessmannstr. 1
35107 Allendorf/Eder
Germany
Registration number
ICIM-PDC-000087 / 01
Certification Body
ICIM S.p.A.
Subtype title
VITOCAL 100 A- (AF) 14
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

3,600 kg

Certification Date
25.06.2020
Testing basis
HP KEYMARK certification scheme rules rev. no. 7
Generate PDF Export model CSV
  • Number of models 2

Models

AWO-AC (AF) 101.A14
Configure model
Model name
AWO-AC (AF) 101.A14
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
3x400V 50Hz

Cooling

EN 14511-2

+7°C/+12°C

El input

3.53 kW

Cooling capacity

11.48

EER

3.25

EN 14825

+7°C/+12°C

Pdesignc

11.48 kW

SEER

4.62

Pdc Tj = 35°C

11.48 kW

EER Tj = 35°C

3.25

Pdc Tj = 30°C

8.47 kW

EER Tj = 30°C

4.31

Cdc Tj = 30 °C

1.0

Pdc Tj = 25°C

5.41 kW

EER Tj = 25°C

4.91

Cdc Tj = 25 °C

1.0

Pdc Tj = 20°C

5.53 kW

EER Tj = 20°C

6.52

Cdc Tj = 20 °C

1.0

Poff

19 W

PTO

0 W

PSB

19 W

PCK

30 W

Annual energy consumption Qce

1492 kWh

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.10 kW

12.80 kW

El input

2.91 kW

4.25 kW

COP

4.85

3.01

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

dB(A)

dB(A)

Sound power level outdoor

68 dB(A)

68 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

130 %

Prated

12.00 kW

12.00 kW

SCOP

4.48

3.31

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-15 °C

Pdh Tj = -7°C

10.70 kW

10.30 kW

COP Tj = -7°C

2.98

2.10

Cdh Tj = -7 °C

1.00

1.00

Pdh Tj = +2°C

6.50 kW

6.20 kW

COP Tj = +2°C

4.20

3.21

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

5.80 kW

5.70 kW

COP Tj = +7°C

5.98

4.19

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

6.70 kW

6.60 kW

COP Tj = 12°C

8.16

6.17

Cdh Tj = +12 °C

0.98

0.98

Pdh Tj = Tbiv

10.70 kW

10.30 kW

COP Tj = Tbiv

2.98

2.10

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.50 kW

10.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.69

1.96

WTOL

60 °C

60 °C

Poff

19 W

19 W

PTO

19 W

19 W

PSB

19 W

19 W

PCK

30 W

30 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5584 kWh

7260 kWh

AWO-M-AC (AF) 101.A14
Configure model
Model name
AWO-M-AC (AF) 101.A14
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
1x230V 50Hz

Cooling

EN 14511-2

+7°C/+12°C

El input

3.53 kW

Cooling capacity

11.48

EER

3.25

EN 14825

+7°C/+12°C

Pdesignc

11.48 kW

SEER

4.62

Pdc Tj = 35°C

11.48 kW

EER Tj = 35°C

3.25

Pdc Tj = 30°C

8.47 kW

EER Tj = 30°C

4.31

Cdc Tj = 30 °C

1.0

Pdc Tj = 25°C

5.41 kW

EER Tj = 25°C

4.91

Cdc Tj = 25 °C

1.0

Pdc Tj = 20°C

5.53 kW

EER Tj = 20°C

6.52

Cdc Tj = 20 °C

1.0

Poff

19 W

PTO

0 W

PSB

19 W

PCK

30 W

Annual energy consumption Qce

1492 kWh

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.10 kW

12.80 kW

El input

2.91 kW

4.25 kW

COP

4.85

3.01

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

dB(A)

dB(A)

Sound power level outdoor

68 dB(A)

68 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

130 %

Prated

12.00 kW

12.00 kW

SCOP

4.48

3.31

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-15 °C

Pdh Tj = -7°C

10.70 kW

10.30 kW

COP Tj = -7°C

2.98

2.10

Cdh Tj = -7 °C

1.00

1.00

Pdh Tj = +2°C

6.50 kW

6.20 kW

COP Tj = +2°C

4.20

3.21

Cdh Tj = +2 °C

1.00

1.00

Pdh Tj = +7°C

5.80 kW

5.70 kW

COP Tj = +7°C

5.98

4.19

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

6.70 kW

6.60 kW

COP Tj = 12°C

8.16

6.17

Cdh Tj = +12 °C

0.98

0.98

Pdh Tj = Tbiv

10.70 kW

10.30 kW

COP Tj = Tbiv

2.98

2.10

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.50 kW

10.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.69

1.96

WTOL

60 °C

60 °C

Poff

19 W

19 W

PTO

19 W

19 W

PSB

19 W

19 W

PCK

30 W

30 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5584 kWh

7260 kWh