1,500 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.30 kW
4.46 kW
El input
1.10 kW
1.65 kW
COP
4.84
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233.8 %
143 %
Prated
3.10 kW
3.50 kW
SCOP
5.92
3.65
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.13 kW
3.47 kW
COP Tj = +2°C
3.70
2.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.03 kW
3.70 kW
COP Tj = +7°C
5.26
3.07
Cdh Tj = +7 °C
0.984
0.990
Pdh Tj = 12°C
4.12 kW
3.65 kW
COP Tj = 12°C
7.91
4.95
Cdh Tj = +12 °C
0.977
0.983
Pdh Tj = Tbiv
3.13 kW
3.47 kW
COP Tj = Tbiv
3.77
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.13 kW
3.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.77
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.03 kW
Annual energy consumption Qhe
707 kWh
1271 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153.8 %
108.2 %
Prated
7.50 kW
7.30 kW
SCOP
3.92
2.78
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.68 kW
4.56 kW
COP Tj = -7°C
3.43
2.43
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.85 kW
2.75 kW
COP Tj = +2°C
5.10
3.34
Cdh Tj = +2 °C
0.978
0.985
Pdh Tj = +7°C
4.24 kW
3.76 kW
COP Tj = +7°C
6.43
4.50
Cdh Tj = +7 °C
0.982
0.985
Pdh Tj = 12°C
4.27 kW
3.92 kW
COP Tj = 12°C
8.85
6.17
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.15 kW
4.99 kW
COP Tj = Tbiv
3.05
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
4.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.50 kW
7.30 kW
Annual energy consumption Qhe
4740 kWh
6460 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184.6 %
125 %
Prated
6.20 kW
6.00 kW
SCOP
4.69
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.49 kW
5.35 kW
COP Tj = -7°C
3.06
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.44 kW
4.01 kW
COP Tj = +2°C
4.53
3.07
Cdh Tj = +2 °C
0.984
0.991
Pdh Tj = +7°C
4.11 kW
5.70 kW
COP Tj = +7°C
6.07
4.19
Cdh Tj = +7 °C
0.982
0.986
Pdh Tj = 12°C
4.28 kW
3.85 kW
COP Tj = 12°C
8.85
5.82
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.50 kW
5.35 kW
COP Tj = Tbiv
3.06
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
1.30 kW
Annual energy consumption Qhe
2738 kWh
3904 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.30 kW
4.46 kW
El input
1.10 kW
1.65 kW
COP
4.84
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233.8 %
143 %
Prated
3.10 kW
3.50 kW
SCOP
5.92
3.65
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.13 kW
3.47 kW
COP Tj = +2°C
3.70
2.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.03 kW
3.70 kW
COP Tj = +7°C
5.26
3.07
Cdh Tj = +7 °C
0.984
0.990
Pdh Tj = 12°C
4.12 kW
3.65 kW
COP Tj = 12°C
7.91
4.95
Cdh Tj = +12 °C
0.977
0.983
Pdh Tj = Tbiv
3.13 kW
3.47 kW
COP Tj = Tbiv
3.77
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.13 kW
3.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.77
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.03 kW
Annual energy consumption Qhe
707 kWh
1271 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153.8 %
108.2 %
Prated
7.50 kW
7.30 kW
SCOP
3.92
2.78
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.68 kW
4.56 kW
COP Tj = -7°C
3.43
2.43
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.85 kW
2.75 kW
COP Tj = +2°C
5.10
3.34
Cdh Tj = +2 °C
0.978
0.985
Pdh Tj = +7°C
4.24 kW
3.76 kW
COP Tj = +7°C
6.43
4.50
Cdh Tj = +7 °C
0.982
0.985
Pdh Tj = 12°C
4.27 kW
3.92 kW
COP Tj = 12°C
8.85
6.17
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.15 kW
4.99 kW
COP Tj = Tbiv
3.05
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
4.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.50 kW
7.30 kW
Annual energy consumption Qhe
4740 kWh
6460 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184.6 %
125 %
Prated
6.20 kW
6.00 kW
SCOP
4.69
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.49 kW
5.35 kW
COP Tj = -7°C
3.06
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.44 kW
4.01 kW
COP Tj = +2°C
4.53
3.07
Cdh Tj = +2 °C
0.984
0.991
Pdh Tj = +7°C
4.11 kW
5.70 kW
COP Tj = +7°C
6.07
4.19
Cdh Tj = +7 °C
0.982
0.986
Pdh Tj = 12°C
4.28 kW
3.85 kW
COP Tj = 12°C
8.85
5.82
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.50 kW
5.35 kW
COP Tj = Tbiv
3.06
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
1.30 kW
Annual energy consumption Qhe
2738 kWh
3904 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.30 kW
4.46 kW
El input
1.10 kW
1.65 kW
COP
4.84
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233.8 %
143 %
Prated
3.10 kW
3.50 kW
SCOP
5.92
3.65
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.13 kW
3.47 kW
COP Tj = +2°C
3.70
2.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.03 kW
3.70 kW
COP Tj = +7°C
5.26
3.07
Cdh Tj = +7 °C
0.984
0.990
Pdh Tj = 12°C
4.12 kW
3.65 kW
COP Tj = 12°C
7.91
4.95
Cdh Tj = +12 °C
0.977
0.983
Pdh Tj = Tbiv
3.13 kW
3.47 kW
COP Tj = Tbiv
3.77
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.13 kW
3.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.77
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.03 kW
Annual energy consumption Qhe
707 kWh
1271 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153.8 %
108.2 %
Prated
7.50 kW
7.30 kW
SCOP
3.92
2.78
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.68 kW
4.56 kW
COP Tj = -7°C
3.43
2.43
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.85 kW
2.75 kW
COP Tj = +2°C
5.10
3.34
Cdh Tj = +2 °C
0.978
0.985
Pdh Tj = +7°C
4.24 kW
3.76 kW
COP Tj = +7°C
6.43
4.50
Cdh Tj = +7 °C
0.982
0.985
Pdh Tj = 12°C
4.27 kW
3.92 kW
COP Tj = 12°C
8.85
6.17
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.15 kW
4.99 kW
COP Tj = Tbiv
3.05
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
4.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.50 kW
7.30 kW
Annual energy consumption Qhe
4740 kWh
6460 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184.6 %
125 %
Prated
6.20 kW
6.00 kW
SCOP
4.69
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.49 kW
5.35 kW
COP Tj = -7°C
3.06
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.44 kW
4.01 kW
COP Tj = +2°C
4.53
3.07
Cdh Tj = +2 °C
0.984
0.991
Pdh Tj = +7°C
4.11 kW
5.70 kW
COP Tj = +7°C
6.07
4.19
Cdh Tj = +7 °C
0.982
0.986
Pdh Tj = 12°C
4.28 kW
3.85 kW
COP Tj = 12°C
8.85
5.82
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.50 kW
5.35 kW
COP Tj = Tbiv
3.06
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
1.30 kW
Annual energy consumption Qhe
2738 kWh
3904 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.30 kW
4.46 kW
El input
1.10 kW
1.65 kW
COP
4.84
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233.8 %
143 %
Prated
3.10 kW
3.50 kW
SCOP
5.92
3.65
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.13 kW
3.47 kW
COP Tj = +2°C
3.70
2.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.03 kW
3.70 kW
COP Tj = +7°C
5.26
3.07
Cdh Tj = +7 °C
0.984
0.990
Pdh Tj = 12°C
4.12 kW
3.65 kW
COP Tj = 12°C
7.91
4.95
Cdh Tj = +12 °C
0.977
0.983
Pdh Tj = Tbiv
3.13 kW
3.47 kW
COP Tj = Tbiv
3.77
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.13 kW
3.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.77
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.03 kW
Annual energy consumption Qhe
707 kWh
1271 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153.8 %
108.2 %
Prated
7.50 kW
7.30 kW
SCOP
3.92
2.78
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.68 kW
4.56 kW
COP Tj = -7°C
3.43
2.43
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.85 kW
2.75 kW
COP Tj = +2°C
5.10
3.34
Cdh Tj = +2 °C
0.978
0.985
Pdh Tj = +7°C
4.24 kW
3.76 kW
COP Tj = +7°C
6.43
4.50
Cdh Tj = +7 °C
0.982
0.985
Pdh Tj = 12°C
4.27 kW
3.92 kW
COP Tj = 12°C
8.85
6.17
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.15 kW
4.99 kW
COP Tj = Tbiv
3.05
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
4.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.50 kW
7.30 kW
Annual energy consumption Qhe
4740 kWh
6460 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184.6 %
125 %
Prated
6.20 kW
6.00 kW
SCOP
4.69
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.49 kW
5.35 kW
COP Tj = -7°C
3.06
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.44 kW
4.01 kW
COP Tj = +2°C
4.53
3.07
Cdh Tj = +2 °C
0.984
0.991
Pdh Tj = +7°C
4.11 kW
5.70 kW
COP Tj = +7°C
6.07
4.19
Cdh Tj = +7 °C
0.982
0.986
Pdh Tj = 12°C
4.28 kW
3.85 kW
COP Tj = 12°C
8.85
5.82
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.50 kW
5.35 kW
COP Tj = Tbiv
3.06
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
1.30 kW
Annual energy consumption Qhe
2738 kWh
3904 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.30 kW
4.46 kW
El input
1.10 kW
1.65 kW
COP
4.84
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233.8 %
143 %
Prated
3.10 kW
3.50 kW
SCOP
5.92
3.65
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.13 kW
3.47 kW
COP Tj = +2°C
3.70
2.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.03 kW
3.70 kW
COP Tj = +7°C
5.26
3.07
Cdh Tj = +7 °C
0.984
0.990
Pdh Tj = 12°C
4.12 kW
3.65 kW
COP Tj = 12°C
7.91
4.95
Cdh Tj = +12 °C
0.977
0.983
Pdh Tj = Tbiv
3.13 kW
3.47 kW
COP Tj = Tbiv
3.77
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.13 kW
3.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.77
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.03 kW
Annual energy consumption Qhe
707 kWh
1271 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153.8 %
108.2 %
Prated
7.50 kW
7.30 kW
SCOP
3.92
2.78
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.68 kW
4.56 kW
COP Tj = -7°C
3.43
2.43
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.85 kW
2.75 kW
COP Tj = +2°C
5.10
3.34
Cdh Tj = +2 °C
0.978
0.985
Pdh Tj = +7°C
4.24 kW
3.76 kW
COP Tj = +7°C
6.43
4.50
Cdh Tj = +7 °C
0.982
0.985
Pdh Tj = 12°C
4.27 kW
3.92 kW
COP Tj = 12°C
8.85
6.17
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.15 kW
4.99 kW
COP Tj = Tbiv
3.05
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
4.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.50 kW
7.30 kW
Annual energy consumption Qhe
4740 kWh
6460 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184.6 %
125 %
Prated
6.20 kW
6.00 kW
SCOP
4.69
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.49 kW
5.35 kW
COP Tj = -7°C
3.06
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.44 kW
4.01 kW
COP Tj = +2°C
4.53
3.07
Cdh Tj = +2 °C
0.984
0.991
Pdh Tj = +7°C
4.11 kW
5.70 kW
COP Tj = +7°C
6.07
4.19
Cdh Tj = +7 °C
0.982
0.986
Pdh Tj = 12°C
4.28 kW
3.85 kW
COP Tj = 12°C
8.85
5.82
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.50 kW
5.35 kW
COP Tj = Tbiv
3.06
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
1.30 kW
Annual energy consumption Qhe
2738 kWh
3904 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.30 kW
4.46 kW
El input
1.10 kW
1.65 kW
COP
4.84
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233.8 %
143 %
Prated
3.10 kW
3.50 kW
SCOP
5.92
3.65
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.13 kW
3.47 kW
COP Tj = +2°C
3.70
2.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.03 kW
3.70 kW
COP Tj = +7°C
5.26
3.07
Cdh Tj = +7 °C
0.984
0.990
Pdh Tj = 12°C
4.12 kW
3.65 kW
COP Tj = 12°C
7.91
4.95
Cdh Tj = +12 °C
0.977
0.983
Pdh Tj = Tbiv
3.13 kW
3.47 kW
COP Tj = Tbiv
3.77
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.13 kW
3.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.77
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.03 kW
Annual energy consumption Qhe
707 kWh
1271 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153.8 %
108.2 %
Prated
7.50 kW
7.30 kW
SCOP
3.92
2.78
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.68 kW
4.56 kW
COP Tj = -7°C
3.43
2.43
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.85 kW
2.75 kW
COP Tj = +2°C
5.10
3.34
Cdh Tj = +2 °C
0.978
0.985
Pdh Tj = +7°C
4.24 kW
3.76 kW
COP Tj = +7°C
6.43
4.50
Cdh Tj = +7 °C
0.982
0.985
Pdh Tj = 12°C
4.27 kW
3.92 kW
COP Tj = 12°C
8.85
6.17
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.15 kW
4.99 kW
COP Tj = Tbiv
3.05
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
4.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.50 kW
7.30 kW
Annual energy consumption Qhe
4740 kWh
6460 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184.6 %
125 %
Prated
6.20 kW
6.00 kW
SCOP
4.69
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.49 kW
5.35 kW
COP Tj = -7°C
3.06
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.44 kW
4.01 kW
COP Tj = +2°C
4.53
3.07
Cdh Tj = +2 °C
0.984
0.991
Pdh Tj = +7°C
4.11 kW
5.70 kW
COP Tj = +7°C
6.07
4.19
Cdh Tj = +7 °C
0.982
0.986
Pdh Tj = 12°C
4.28 kW
3.85 kW
COP Tj = 12°C
8.85
5.82
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.50 kW
5.35 kW
COP Tj = Tbiv
3.06
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
1.30 kW
Annual energy consumption Qhe
2738 kWh
3904 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.30 kW
4.46 kW
El input
1.10 kW
1.65 kW
COP
4.84
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233.8 %
143 %
Prated
3.10 kW
3.50 kW
SCOP
5.92
3.65
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.13 kW
3.47 kW
COP Tj = +2°C
3.70
2.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.03 kW
3.70 kW
COP Tj = +7°C
5.26
3.07
Cdh Tj = +7 °C
0.984
0.990
Pdh Tj = 12°C
4.12 kW
3.65 kW
COP Tj = 12°C
7.91
4.95
Cdh Tj = +12 °C
0.977
0.983
Pdh Tj = Tbiv
3.13 kW
3.47 kW
COP Tj = Tbiv
3.77
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.13 kW
3.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.77
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.03 kW
Annual energy consumption Qhe
707 kWh
1271 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153.8 %
108.2 %
Prated
7.50 kW
7.30 kW
SCOP
3.92
2.78
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.68 kW
4.56 kW
COP Tj = -7°C
3.43
2.43
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.85 kW
2.75 kW
COP Tj = +2°C
5.10
3.34
Cdh Tj = +2 °C
0.978
0.985
Pdh Tj = +7°C
4.24 kW
3.76 kW
COP Tj = +7°C
6.43
4.50
Cdh Tj = +7 °C
0.982
0.985
Pdh Tj = 12°C
4.27 kW
3.92 kW
COP Tj = 12°C
8.85
6.17
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.15 kW
4.99 kW
COP Tj = Tbiv
3.05
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
4.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.50 kW
7.30 kW
Annual energy consumption Qhe
4740 kWh
6460 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184.6 %
125 %
Prated
6.20 kW
6.00 kW
SCOP
4.69
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.49 kW
5.35 kW
COP Tj = -7°C
3.06
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.44 kW
4.01 kW
COP Tj = +2°C
4.53
3.07
Cdh Tj = +2 °C
0.984
0.991
Pdh Tj = +7°C
4.11 kW
5.70 kW
COP Tj = +7°C
6.07
4.19
Cdh Tj = +7 °C
0.982
0.986
Pdh Tj = 12°C
4.28 kW
3.85 kW
COP Tj = 12°C
8.85
5.82
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.50 kW
5.35 kW
COP Tj = Tbiv
3.06
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
1.30 kW
Annual energy consumption Qhe
2738 kWh
3904 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.30 kW
4.46 kW
El input
1.10 kW
1.65 kW
COP
4.84
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233.8 %
143 %
Prated
3.10 kW
3.50 kW
SCOP
5.92
3.65
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.13 kW
3.47 kW
COP Tj = +2°C
3.70
2.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.03 kW
3.70 kW
COP Tj = +7°C
5.26
3.07
Cdh Tj = +7 °C
0.984
0.990
Pdh Tj = 12°C
4.12 kW
3.65 kW
COP Tj = 12°C
7.91
4.95
Cdh Tj = +12 °C
0.977
0.983
Pdh Tj = Tbiv
3.13 kW
3.47 kW
COP Tj = Tbiv
3.77
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.13 kW
3.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.77
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.03 kW
Annual energy consumption Qhe
707 kWh
1271 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153.8 %
108.2 %
Prated
7.50 kW
7.30 kW
SCOP
3.92
2.78
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.68 kW
4.56 kW
COP Tj = -7°C
3.43
2.43
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.85 kW
2.75 kW
COP Tj = +2°C
5.10
3.34
Cdh Tj = +2 °C
0.978
0.985
Pdh Tj = +7°C
4.24 kW
3.76 kW
COP Tj = +7°C
6.43
4.50
Cdh Tj = +7 °C
0.982
0.985
Pdh Tj = 12°C
4.27 kW
3.92 kW
COP Tj = 12°C
8.85
6.17
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.15 kW
4.99 kW
COP Tj = Tbiv
3.05
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
4.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.50 kW
7.30 kW
Annual energy consumption Qhe
4740 kWh
6460 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184.6 %
125 %
Prated
6.20 kW
6.00 kW
SCOP
4.69
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.49 kW
5.35 kW
COP Tj = -7°C
3.06
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.44 kW
4.01 kW
COP Tj = +2°C
4.53
3.07
Cdh Tj = +2 °C
0.984
0.991
Pdh Tj = +7°C
4.11 kW
5.70 kW
COP Tj = +7°C
6.07
4.19
Cdh Tj = +7 °C
0.982
0.986
Pdh Tj = 12°C
4.28 kW
3.85 kW
COP Tj = 12°C
8.85
5.82
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.50 kW
5.35 kW
COP Tj = Tbiv
3.06
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
1.30 kW
Annual energy consumption Qhe
2738 kWh
3904 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.30 kW
4.46 kW
El input
1.10 kW
1.65 kW
COP
4.84
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233.8 %
143 %
Prated
3.10 kW
3.50 kW
SCOP
5.92
3.65
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.13 kW
3.47 kW
COP Tj = +2°C
3.70
2.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.03 kW
3.70 kW
COP Tj = +7°C
5.26
3.07
Cdh Tj = +7 °C
0.984
0.990
Pdh Tj = 12°C
4.12 kW
3.65 kW
COP Tj = 12°C
7.91
4.95
Cdh Tj = +12 °C
0.977
0.983
Pdh Tj = Tbiv
3.13 kW
3.47 kW
COP Tj = Tbiv
3.77
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.13 kW
3.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.77
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.03 kW
Annual energy consumption Qhe
707 kWh
1271 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153.8 %
108.2 %
Prated
7.50 kW
7.30 kW
SCOP
3.92
2.78
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.68 kW
4.56 kW
COP Tj = -7°C
3.43
2.43
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.85 kW
2.75 kW
COP Tj = +2°C
5.10
3.34
Cdh Tj = +2 °C
0.978
0.985
Pdh Tj = +7°C
4.24 kW
3.76 kW
COP Tj = +7°C
6.43
4.50
Cdh Tj = +7 °C
0.982
0.985
Pdh Tj = 12°C
4.27 kW
3.92 kW
COP Tj = 12°C
8.85
6.17
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.15 kW
4.99 kW
COP Tj = Tbiv
3.05
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
4.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.50 kW
7.30 kW
Annual energy consumption Qhe
4740 kWh
6460 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184.6 %
125 %
Prated
6.20 kW
6.00 kW
SCOP
4.69
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.49 kW
5.35 kW
COP Tj = -7°C
3.06
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.44 kW
4.01 kW
COP Tj = +2°C
4.53
3.07
Cdh Tj = +2 °C
0.984
0.991
Pdh Tj = +7°C
4.11 kW
5.70 kW
COP Tj = +7°C
6.07
4.19
Cdh Tj = +7 °C
0.982
0.986
Pdh Tj = 12°C
4.28 kW
3.85 kW
COP Tj = 12°C
8.85
5.82
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.50 kW
5.35 kW
COP Tj = Tbiv
3.06
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
1.30 kW
Annual energy consumption Qhe
2738 kWh
3904 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.30 kW
4.46 kW
El input
1.10 kW
1.65 kW
COP
4.84
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233.8 %
143 %
Prated
3.10 kW
3.50 kW
SCOP
5.92
3.65
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.13 kW
3.47 kW
COP Tj = +2°C
3.70
2.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.03 kW
3.70 kW
COP Tj = +7°C
5.26
3.07
Cdh Tj = +7 °C
0.984
0.990
Pdh Tj = 12°C
4.12 kW
3.65 kW
COP Tj = 12°C
7.91
4.95
Cdh Tj = +12 °C
0.977
0.983
Pdh Tj = Tbiv
3.13 kW
3.47 kW
COP Tj = Tbiv
3.77
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.13 kW
3.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.77
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.03 kW
Annual energy consumption Qhe
707 kWh
1271 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153.8 %
108.2 %
Prated
7.50 kW
7.30 kW
SCOP
3.92
2.78
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.68 kW
4.56 kW
COP Tj = -7°C
3.43
2.43
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.85 kW
2.75 kW
COP Tj = +2°C
5.10
3.34
Cdh Tj = +2 °C
0.978
0.985
Pdh Tj = +7°C
4.24 kW
3.76 kW
COP Tj = +7°C
6.43
4.50
Cdh Tj = +7 °C
0.982
0.985
Pdh Tj = 12°C
4.27 kW
3.92 kW
COP Tj = 12°C
8.85
6.17
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.15 kW
4.99 kW
COP Tj = Tbiv
3.05
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
4.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.50 kW
7.30 kW
Annual energy consumption Qhe
4740 kWh
6460 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184.6 %
125 %
Prated
6.20 kW
6.00 kW
SCOP
4.69
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.49 kW
5.35 kW
COP Tj = -7°C
3.06
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.44 kW
4.01 kW
COP Tj = +2°C
4.53
3.07
Cdh Tj = +2 °C
0.984
0.991
Pdh Tj = +7°C
4.11 kW
5.70 kW
COP Tj = +7°C
6.07
4.19
Cdh Tj = +7 °C
0.982
0.986
Pdh Tj = 12°C
4.28 kW
3.85 kW
COP Tj = 12°C
8.85
5.82
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.50 kW
5.35 kW
COP Tj = Tbiv
3.06
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
1.30 kW
Annual energy consumption Qhe
2738 kWh
3904 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.30 kW
4.46 kW
El input
1.10 kW
1.65 kW
COP
4.84
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233.8 %
143 %
Prated
3.10 kW
3.50 kW
SCOP
5.92
3.65
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.13 kW
3.47 kW
COP Tj = +2°C
3.70
2.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.03 kW
3.70 kW
COP Tj = +7°C
5.26
3.07
Cdh Tj = +7 °C
0.984
0.990
Pdh Tj = 12°C
4.12 kW
3.65 kW
COP Tj = 12°C
7.91
4.95
Cdh Tj = +12 °C
0.977
0.983
Pdh Tj = Tbiv
3.13 kW
3.47 kW
COP Tj = Tbiv
3.77
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.13 kW
3.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.77
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.03 kW
Annual energy consumption Qhe
707 kWh
1271 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153.8 %
108.2 %
Prated
7.50 kW
7.30 kW
SCOP
3.92
2.78
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.68 kW
4.56 kW
COP Tj = -7°C
3.43
2.43
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.85 kW
2.75 kW
COP Tj = +2°C
5.10
3.34
Cdh Tj = +2 °C
0.978
0.985
Pdh Tj = +7°C
4.24 kW
3.76 kW
COP Tj = +7°C
6.43
4.50
Cdh Tj = +7 °C
0.982
0.985
Pdh Tj = 12°C
4.27 kW
3.92 kW
COP Tj = 12°C
8.85
6.17
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.15 kW
4.99 kW
COP Tj = Tbiv
3.05
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
4.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.50 kW
7.30 kW
Annual energy consumption Qhe
4740 kWh
6460 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184.6 %
125 %
Prated
6.20 kW
6.00 kW
SCOP
4.69
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.49 kW
5.35 kW
COP Tj = -7°C
3.06
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.44 kW
4.01 kW
COP Tj = +2°C
4.53
3.07
Cdh Tj = +2 °C
0.984
0.991
Pdh Tj = +7°C
4.11 kW
5.70 kW
COP Tj = +7°C
6.07
4.19
Cdh Tj = +7 °C
0.982
0.986
Pdh Tj = 12°C
4.28 kW
3.85 kW
COP Tj = 12°C
8.85
5.82
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.50 kW
5.35 kW
COP Tj = Tbiv
3.06
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
1.30 kW
Annual energy consumption Qhe
2738 kWh
3904 kWh
Domestic Hot Water (DHW)
Warmer Climate
Colder Climate
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.71
Heating up time
03:10 h:min
Standby power input
55 W
Reference hot water temperature
56.2 °C
Mixed water at 40°C
283 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.30 kW
4.46 kW
El input
1.10 kW
1.65 kW
COP
4.84
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233.8 %
143 %
Prated
3.10 kW
3.50 kW
SCOP
5.92
3.65
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.13 kW
3.47 kW
COP Tj = +2°C
3.70
2.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.03 kW
3.70 kW
COP Tj = +7°C
5.26
3.07
Cdh Tj = +7 °C
0.984
0.990
Pdh Tj = 12°C
4.12 kW
3.65 kW
COP Tj = 12°C
7.91
4.95
Cdh Tj = +12 °C
0.977
0.983
Pdh Tj = Tbiv
3.13 kW
3.47 kW
COP Tj = Tbiv
3.77
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.13 kW
3.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.77
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.03 kW
Annual energy consumption Qhe
707 kWh
1271 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153.8 %
108.2 %
Prated
7.50 kW
7.30 kW
SCOP
3.92
2.78
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.68 kW
4.56 kW
COP Tj = -7°C
3.43
2.43
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.85 kW
2.75 kW
COP Tj = +2°C
5.10
3.34
Cdh Tj = +2 °C
0.978
0.985
Pdh Tj = +7°C
4.24 kW
3.76 kW
COP Tj = +7°C
6.43
4.50
Cdh Tj = +7 °C
0.982
0.985
Pdh Tj = 12°C
4.27 kW
3.92 kW
COP Tj = 12°C
8.85
6.17
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.15 kW
4.99 kW
COP Tj = Tbiv
3.05
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
4.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.50 kW
7.30 kW
Annual energy consumption Qhe
4740 kWh
6460 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184.6 %
125 %
Prated
6.20 kW
6.00 kW
SCOP
4.69
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.49 kW
5.35 kW
COP Tj = -7°C
3.06
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.44 kW
4.01 kW
COP Tj = +2°C
4.53
3.07
Cdh Tj = +2 °C
0.984
0.991
Pdh Tj = +7°C
4.11 kW
5.70 kW
COP Tj = +7°C
6.07
4.19
Cdh Tj = +7 °C
0.982
0.986
Pdh Tj = 12°C
4.28 kW
3.85 kW
COP Tj = 12°C
8.85
5.82
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.50 kW
5.35 kW
COP Tj = Tbiv
3.06
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
1.30 kW
Annual energy consumption Qhe
2738 kWh
3904 kWh
Domestic Hot Water (DHW)
Warmer Climate
Colder Climate
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.71
Heating up time
03:10 h:min
Standby power input
55 W
Reference hot water temperature
56.2 °C
Mixed water at 40°C
283 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.30 kW
4.46 kW
El input
1.10 kW
1.65 kW
COP
4.84
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233.8 %
143 %
Prated
3.10 kW
3.50 kW
SCOP
5.92
3.65
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.13 kW
3.47 kW
COP Tj = +2°C
3.70
2.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.03 kW
3.70 kW
COP Tj = +7°C
5.26
3.07
Cdh Tj = +7 °C
0.984
0.990
Pdh Tj = 12°C
4.12 kW
3.65 kW
COP Tj = 12°C
7.91
4.95
Cdh Tj = +12 °C
0.977
0.983
Pdh Tj = Tbiv
3.13 kW
3.47 kW
COP Tj = Tbiv
3.77
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.13 kW
3.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.77
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.03 kW
Annual energy consumption Qhe
707 kWh
1271 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153.8 %
108.2 %
Prated
7.50 kW
7.30 kW
SCOP
3.92
2.78
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.68 kW
4.56 kW
COP Tj = -7°C
3.43
2.43
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.85 kW
2.75 kW
COP Tj = +2°C
5.10
3.34
Cdh Tj = +2 °C
0.978
0.985
Pdh Tj = +7°C
4.24 kW
3.76 kW
COP Tj = +7°C
6.43
4.50
Cdh Tj = +7 °C
0.982
0.985
Pdh Tj = 12°C
4.27 kW
3.92 kW
COP Tj = 12°C
8.85
6.17
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.15 kW
4.99 kW
COP Tj = Tbiv
3.05
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
4.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.50 kW
7.30 kW
Annual energy consumption Qhe
4740 kWh
6460 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184.6 %
125 %
Prated
6.20 kW
6.00 kW
SCOP
4.69
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.49 kW
5.35 kW
COP Tj = -7°C
3.06
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.44 kW
4.01 kW
COP Tj = +2°C
4.53
3.07
Cdh Tj = +2 °C
0.984
0.991
Pdh Tj = +7°C
4.11 kW
5.70 kW
COP Tj = +7°C
6.07
4.19
Cdh Tj = +7 °C
0.982
0.986
Pdh Tj = 12°C
4.28 kW
3.85 kW
COP Tj = 12°C
8.85
5.82
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.50 kW
5.35 kW
COP Tj = Tbiv
3.06
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
1.30 kW
Annual energy consumption Qhe
2738 kWh
3904 kWh
Domestic Hot Water (DHW)
Warmer Climate
Colder Climate
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.71
Heating up time
03:10 h:min
Standby power input
55 W
Reference hot water temperature
56.2 °C
Mixed water at 40°C
283 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.30 kW
4.46 kW
El input
1.10 kW
1.65 kW
COP
4.84
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233.8 %
143 %
Prated
3.10 kW
3.50 kW
SCOP
5.92
3.65
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.13 kW
3.47 kW
COP Tj = +2°C
3.70
2.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.03 kW
3.70 kW
COP Tj = +7°C
5.26
3.07
Cdh Tj = +7 °C
0.984
0.990
Pdh Tj = 12°C
4.12 kW
3.65 kW
COP Tj = 12°C
7.91
4.95
Cdh Tj = +12 °C
0.977
0.983
Pdh Tj = Tbiv
3.13 kW
3.47 kW
COP Tj = Tbiv
3.77
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.13 kW
3.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.77
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.03 kW
Annual energy consumption Qhe
707 kWh
1271 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153.8 %
108.2 %
Prated
7.50 kW
7.30 kW
SCOP
3.92
2.78
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.68 kW
4.56 kW
COP Tj = -7°C
3.43
2.43
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.85 kW
2.75 kW
COP Tj = +2°C
5.10
3.34
Cdh Tj = +2 °C
0.978
0.985
Pdh Tj = +7°C
4.24 kW
3.76 kW
COP Tj = +7°C
6.43
4.50
Cdh Tj = +7 °C
0.982
0.985
Pdh Tj = 12°C
4.27 kW
3.92 kW
COP Tj = 12°C
8.85
6.17
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.15 kW
4.99 kW
COP Tj = Tbiv
3.05
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
4.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.50 kW
7.30 kW
Annual energy consumption Qhe
4740 kWh
6460 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184.6 %
125 %
Prated
6.20 kW
6.00 kW
SCOP
4.69
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.49 kW
5.35 kW
COP Tj = -7°C
3.06
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.44 kW
4.01 kW
COP Tj = +2°C
4.53
3.07
Cdh Tj = +2 °C
0.984
0.991
Pdh Tj = +7°C
4.11 kW
5.70 kW
COP Tj = +7°C
6.07
4.19
Cdh Tj = +7 °C
0.982
0.986
Pdh Tj = 12°C
4.28 kW
3.85 kW
COP Tj = 12°C
8.85
5.82
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.50 kW
5.35 kW
COP Tj = Tbiv
3.06
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
1.30 kW
Annual energy consumption Qhe
2738 kWh
3904 kWh
Domestic Hot Water (DHW)
Warmer Climate
Colder Climate
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.71
Heating up time
03:10 h:min
Standby power input
55 W
Reference hot water temperature
56.2 °C
Mixed water at 40°C
283 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.30 kW
4.46 kW
El input
1.10 kW
1.65 kW
COP
4.84
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233.8 %
143 %
Prated
3.10 kW
3.50 kW
SCOP
5.92
3.65
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.13 kW
3.47 kW
COP Tj = +2°C
3.70
2.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.03 kW
3.70 kW
COP Tj = +7°C
5.26
3.07
Cdh Tj = +7 °C
0.984
0.990
Pdh Tj = 12°C
4.12 kW
3.65 kW
COP Tj = 12°C
7.91
4.95
Cdh Tj = +12 °C
0.977
0.983
Pdh Tj = Tbiv
3.13 kW
3.47 kW
COP Tj = Tbiv
3.77
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.13 kW
3.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.77
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.03 kW
Annual energy consumption Qhe
707 kWh
1271 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153.8 %
108.2 %
Prated
7.50 kW
7.30 kW
SCOP
3.92
2.78
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.68 kW
4.56 kW
COP Tj = -7°C
3.43
2.43
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.85 kW
2.75 kW
COP Tj = +2°C
5.10
3.34
Cdh Tj = +2 °C
0.978
0.985
Pdh Tj = +7°C
4.24 kW
3.76 kW
COP Tj = +7°C
6.43
4.50
Cdh Tj = +7 °C
0.982
0.985
Pdh Tj = 12°C
4.27 kW
3.92 kW
COP Tj = 12°C
8.85
6.17
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.15 kW
4.99 kW
COP Tj = Tbiv
3.05
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
4.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.50 kW
7.30 kW
Annual energy consumption Qhe
4740 kWh
6460 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184.6 %
125 %
Prated
6.20 kW
6.00 kW
SCOP
4.69
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.49 kW
5.35 kW
COP Tj = -7°C
3.06
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.44 kW
4.01 kW
COP Tj = +2°C
4.53
3.07
Cdh Tj = +2 °C
0.984
0.991
Pdh Tj = +7°C
4.11 kW
5.70 kW
COP Tj = +7°C
6.07
4.19
Cdh Tj = +7 °C
0.982
0.986
Pdh Tj = 12°C
4.28 kW
3.85 kW
COP Tj = 12°C
8.85
5.82
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.50 kW
5.35 kW
COP Tj = Tbiv
3.06
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
1.30 kW
Annual energy consumption Qhe
2738 kWh
3904 kWh
Domestic Hot Water (DHW)
Warmer Climate
Colder Climate
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.71
Heating up time
03:10 h:min
Standby power input
55 W
Reference hot water temperature
56.2 °C
Mixed water at 40°C
283 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.30 kW
4.46 kW
El input
1.10 kW
1.65 kW
COP
4.84
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233.8 %
143 %
Prated
3.10 kW
3.50 kW
SCOP
5.92
3.65
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.13 kW
3.47 kW
COP Tj = +2°C
3.70
2.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.03 kW
3.70 kW
COP Tj = +7°C
5.26
3.07
Cdh Tj = +7 °C
0.984
0.990
Pdh Tj = 12°C
4.12 kW
3.65 kW
COP Tj = 12°C
7.91
4.95
Cdh Tj = +12 °C
0.977
0.983
Pdh Tj = Tbiv
3.13 kW
3.47 kW
COP Tj = Tbiv
3.77
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.13 kW
3.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.77
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.03 kW
Annual energy consumption Qhe
707 kWh
1271 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153.8 %
108.2 %
Prated
7.50 kW
7.30 kW
SCOP
3.92
2.78
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.68 kW
4.56 kW
COP Tj = -7°C
3.43
2.43
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.85 kW
2.75 kW
COP Tj = +2°C
5.10
3.34
Cdh Tj = +2 °C
0.978
0.985
Pdh Tj = +7°C
4.24 kW
3.76 kW
COP Tj = +7°C
6.43
4.50
Cdh Tj = +7 °C
0.982
0.985
Pdh Tj = 12°C
4.27 kW
3.92 kW
COP Tj = 12°C
8.85
6.17
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.15 kW
4.99 kW
COP Tj = Tbiv
3.05
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
4.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.50 kW
7.30 kW
Annual energy consumption Qhe
4740 kWh
6460 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184.6 %
125 %
Prated
6.20 kW
6.00 kW
SCOP
4.69
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.49 kW
5.35 kW
COP Tj = -7°C
3.06
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.44 kW
4.01 kW
COP Tj = +2°C
4.53
3.07
Cdh Tj = +2 °C
0.984
0.991
Pdh Tj = +7°C
4.11 kW
5.70 kW
COP Tj = +7°C
6.07
4.19
Cdh Tj = +7 °C
0.982
0.986
Pdh Tj = 12°C
4.28 kW
3.85 kW
COP Tj = 12°C
8.85
5.82
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.50 kW
5.35 kW
COP Tj = Tbiv
3.06
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
1.30 kW
Annual energy consumption Qhe
2738 kWh
3904 kWh
Domestic Hot Water (DHW)
Warmer Climate
Colder Climate
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.71
Heating up time
03:10 h:min
Standby power input
55 W
Reference hot water temperature
56.2 °C
Mixed water at 40°C
283 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.30 kW
4.46 kW
El input
1.10 kW
1.65 kW
COP
4.84
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233.8 %
143 %
Prated
3.10 kW
3.50 kW
SCOP
5.92
3.65
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.13 kW
3.47 kW
COP Tj = +2°C
3.70
2.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.03 kW
3.70 kW
COP Tj = +7°C
5.26
3.07
Cdh Tj = +7 °C
0.984
0.990
Pdh Tj = 12°C
4.12 kW
3.65 kW
COP Tj = 12°C
7.91
4.95
Cdh Tj = +12 °C
0.977
0.983
Pdh Tj = Tbiv
3.13 kW
3.47 kW
COP Tj = Tbiv
3.77
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.13 kW
3.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.77
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.03 kW
Annual energy consumption Qhe
707 kWh
1271 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153.8 %
108.2 %
Prated
7.50 kW
7.30 kW
SCOP
3.92
2.78
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.68 kW
4.56 kW
COP Tj = -7°C
3.43
2.43
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.85 kW
2.75 kW
COP Tj = +2°C
5.10
3.34
Cdh Tj = +2 °C
0.978
0.985
Pdh Tj = +7°C
4.24 kW
3.76 kW
COP Tj = +7°C
6.43
4.50
Cdh Tj = +7 °C
0.982
0.985
Pdh Tj = 12°C
4.27 kW
3.92 kW
COP Tj = 12°C
8.85
6.17
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.15 kW
4.99 kW
COP Tj = Tbiv
3.05
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
4.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.50 kW
7.30 kW
Annual energy consumption Qhe
4740 kWh
6460 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184.6 %
125 %
Prated
6.20 kW
6.00 kW
SCOP
4.69
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.49 kW
5.35 kW
COP Tj = -7°C
3.06
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.44 kW
4.01 kW
COP Tj = +2°C
4.53
3.07
Cdh Tj = +2 °C
0.984
0.991
Pdh Tj = +7°C
4.11 kW
5.70 kW
COP Tj = +7°C
6.07
4.19
Cdh Tj = +7 °C
0.982
0.986
Pdh Tj = 12°C
4.28 kW
3.85 kW
COP Tj = 12°C
8.85
5.82
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.50 kW
5.35 kW
COP Tj = Tbiv
3.06
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
1.30 kW
Annual energy consumption Qhe
2738 kWh
3904 kWh
Domestic Hot Water (DHW)
Warmer Climate
Colder Climate
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.71
Heating up time
03:10 h:min
Standby power input
55 W
Reference hot water temperature
56.2 °C
Mixed water at 40°C
283 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.30 kW
4.46 kW
El input
1.10 kW
1.65 kW
COP
4.84
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233.8 %
143 %
Prated
3.10 kW
3.50 kW
SCOP
5.92
3.65
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.13 kW
3.47 kW
COP Tj = +2°C
3.70
2.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.03 kW
3.70 kW
COP Tj = +7°C
5.26
3.07
Cdh Tj = +7 °C
0.984
0.990
Pdh Tj = 12°C
4.12 kW
3.65 kW
COP Tj = 12°C
7.91
4.95
Cdh Tj = +12 °C
0.977
0.983
Pdh Tj = Tbiv
3.13 kW
3.47 kW
COP Tj = Tbiv
3.77
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.13 kW
3.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.77
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.03 kW
Annual energy consumption Qhe
707 kWh
1271 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153.8 %
108.2 %
Prated
7.50 kW
7.30 kW
SCOP
3.92
2.78
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.68 kW
4.56 kW
COP Tj = -7°C
3.43
2.43
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.85 kW
2.75 kW
COP Tj = +2°C
5.10
3.34
Cdh Tj = +2 °C
0.978
0.985
Pdh Tj = +7°C
4.24 kW
3.76 kW
COP Tj = +7°C
6.43
4.50
Cdh Tj = +7 °C
0.982
0.985
Pdh Tj = 12°C
4.27 kW
3.92 kW
COP Tj = 12°C
8.85
6.17
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.15 kW
4.99 kW
COP Tj = Tbiv
3.05
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
4.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.50 kW
7.30 kW
Annual energy consumption Qhe
4740 kWh
6460 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184.6 %
125 %
Prated
6.20 kW
6.00 kW
SCOP
4.69
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.49 kW
5.35 kW
COP Tj = -7°C
3.06
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.44 kW
4.01 kW
COP Tj = +2°C
4.53
3.07
Cdh Tj = +2 °C
0.984
0.991
Pdh Tj = +7°C
4.11 kW
5.70 kW
COP Tj = +7°C
6.07
4.19
Cdh Tj = +7 °C
0.982
0.986
Pdh Tj = 12°C
4.28 kW
3.85 kW
COP Tj = 12°C
8.85
5.82
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.50 kW
5.35 kW
COP Tj = Tbiv
3.06
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.20 kW
1.30 kW
Annual energy consumption Qhe
2738 kWh
3904 kWh
Domestic Hot Water (DHW)
Warmer Climate
Colder Climate
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
113 %
COP
2.71
Heating up time
03:10 h:min
Standby power input
55 W
Reference hot water temperature
56.2 °C
Mixed water at 40°C
283 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.30 kW
4.46 kW
El input
1.10 kW
1.65 kW
COP
4.84
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
234 %
143 %
Prated
3.10 kW
3.50 kW
SCOP
5.92
3.65
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.13 kW
3.47 kW
COP Tj = +2°C
3.70
2.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.03 kW
3.70 kW
COP Tj = +7°C
5.26
3.07
Cdh Tj = +7 °C
0.984
0.990
Pdh Tj = 12°C
4.12 kW
3.65 kW
COP Tj = 12°C
7.91
4.95
Cdh Tj = +12 °C
0.977
0.983
Pdh Tj = Tbiv
3.13 kW
3.47 kW
COP Tj = Tbiv
3.77
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.13 kW
3.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.77
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Gas
Gas
Supplementary Heater: PSUP
0.00 kW
0.03 kW
Annual energy consumption Qhe
707 kWh
1271 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
154 %
108 %
Prated
7.50 kW
7.30 kW
SCOP
3.92
2.78
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.68 kW
4.56 kW
COP Tj = -7°C
3.43
2.43
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.85 kW
2.75 kW
COP Tj = +2°C
5.10
3.34
Cdh Tj = +2 °C
0.978
0.985
Pdh Tj = +7°C
4.24 kW
3.76 kW
COP Tj = +7°C
6.43
4.50
Cdh Tj = +7 °C
0.982
0.985
Pdh Tj = 12°C
4.27 kW
3.92 kW
COP Tj = 12°C
8.85
6.17
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.15 kW
4.99 kW
COP Tj = Tbiv
3.05
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
4.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Gas
Gas
Supplementary Heater: PSUP
7.50 kW
7.30 kW
Annual energy consumption Qhe
4740 kWh
6460 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
125 %
Prated
6.20 kW
6.00 kW
SCOP
4.69
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.49 kW
5.35 kW
COP Tj = -7°C
3.06
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.44 kW
4.01 kW
COP Tj = +2°C
4.53
3.07
Cdh Tj = +2 °C
0.984
0.991
Pdh Tj = +7°C
4.11 kW
5.70 kW
COP Tj = +7°C
6.07
4.19
Cdh Tj = +7 °C
0.982
0.986
Pdh Tj = 12°C
4.28 kW
3.85 kW
COP Tj = 12°C
8.85
5.82
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.50 kW
5.35 kW
COP Tj = Tbiv
3.06
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Gas
Gas
Supplementary Heater: PSUP
1.20 kW
1.30 kW
Annual energy consumption Qhe
2738 kWh
3904 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.30 kW
4.46 kW
El input
1.10 kW
1.65 kW
COP
4.84
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
234 %
143 %
Prated
3.10 kW
3.50 kW
SCOP
5.92
3.65
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
3.13 kW
3.47 kW
COP Tj = +2°C
3.70
2.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
4.03 kW
3.70 kW
COP Tj = +7°C
5.26
3.07
Cdh Tj = +7 °C
0.984
0.990
Pdh Tj = 12°C
4.12 kW
3.65 kW
COP Tj = 12°C
7.91
4.95
Cdh Tj = +12 °C
0.977
0.983
Pdh Tj = Tbiv
3.13 kW
3.47 kW
COP Tj = Tbiv
3.77
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.13 kW
3.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.77
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Gas
Gas
Supplementary Heater: PSUP
0.00 kW
0.03 kW
Annual energy consumption Qhe
707 kWh
1271 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
154 %
108 %
Prated
7.50 kW
7.30 kW
SCOP
3.92
2.78
Tbiv
-10 °C
-10 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
4.68 kW
4.56 kW
COP Tj = -7°C
3.43
2.43
Cdh Tj = -7 °C
0.991
0.993
Pdh Tj = +2°C
2.85 kW
2.75 kW
COP Tj = +2°C
5.10
3.34
Cdh Tj = +2 °C
0.978
0.985
Pdh Tj = +7°C
4.24 kW
3.76 kW
COP Tj = +7°C
6.43
4.50
Cdh Tj = +7 °C
0.982
0.985
Pdh Tj = 12°C
4.27 kW
3.92 kW
COP Tj = 12°C
8.85
6.17
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.15 kW
4.99 kW
COP Tj = Tbiv
3.05
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
4.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.08
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Gas
Gas
Supplementary Heater: PSUP
7.50 kW
7.30 kW
Annual energy consumption Qhe
4740 kWh
6460 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
125 %
Prated
6.20 kW
6.00 kW
SCOP
4.69
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
5.49 kW
5.35 kW
COP Tj = -7°C
3.06
2.09
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
3.44 kW
4.01 kW
COP Tj = +2°C
4.53
3.07
Cdh Tj = +2 °C
0.984
0.991
Pdh Tj = +7°C
4.11 kW
5.70 kW
COP Tj = +7°C
6.07
4.19
Cdh Tj = +7 °C
0.982
0.986
Pdh Tj = 12°C
4.28 kW
3.85 kW
COP Tj = 12°C
8.85
5.82
Cdh Tj = +12 °C
0.975
0.981
Pdh Tj = Tbiv
5.50 kW
5.35 kW
COP Tj = Tbiv
3.06
2.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.01 kW
4.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.79
1.79
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
12 W
12 W
PTO
7 W
7 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Gas
Gas
Supplementary Heater: PSUP
1.20 kW
1.30 kW
Annual energy consumption Qhe
2738 kWh
3904 kWh