Certificate holders

Subtype

25. Yutaki S Combi Lite 2.0HP

Certificate Holder
Johnson Controls-Hitachi AirConditioning Spain
Ronda Shimizu, 1. Pol. Ind. Can Torrella
08233 Vacarisses, Barcelona
Spain
Registration number
041-K002-25
Certification Body
BRE Global Limited
Subtype title
25. Yutaki S Combi Lite 2.0HP
Driving energy
n/a
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

1,200 kg

Certification Date
n/a
Testing basis
n/a
Generate PDF Export model CSV Download certificate
  • Number of models 2

Models

RAS-2WHVN RWD-2.0NWLE-200S - Heating Only
Configure model
Model name
RAS-2WHVN RWD-2.0NWLE-200S - Heating Only
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

4.00 kW

3.75 kW

El input

0.85 kW

1.38 kW

COP

4.70

2.70

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

51 dB(A)

51 dB(A)

Sound power level outdoor

63 dB(A)

63 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

167 %

117 %

Prated

4.00 kW

4.00 kW

SCOP

4.25

3.00

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

3.55 kW

3.50 kW

COP Tj = -7°C

2.35

1.90

Pdh Tj = +2°C

2.15 kW

2.10 kW

COP Tj = +2°C

4.21

2.95

Pdh Tj = +7°C

1.70 kW

1.40 kW

COP Tj = +7°C

6.10

4.10

Pdh Tj = 12°C

2.15 kW

2.00 kW

COP Tj = 12°C

9.00

4.81

Pdh Tj = Tbiv

3.55 kW

3.50 kW

COP Tj = Tbiv

2.35

1.90

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

3.50 kW

3.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.10

1.60

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

55 °C

55 °C

Poff

3 W

3 W

PTO

0 W

0 W

PSB

3 W

3 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.50 kW

0.90 kW

Annual energy consumption Qhe

1953 kWh

2727 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

125 %

COP

3.30

Heating up time

2:13 h:min

Standby power input

30.0 W

Reference hot water temperature

53.5 °C

Mixed water at 40°C

250 l

RAS-2WHVN RWD-2.0NWLE-200S - with cooling kit
Configure model
Model name
RAS-2WHVN RWD-2.0NWLE-200S - with cooling kit
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

4.00 kW

3.75 kW

El input

0.85 kW

1.38 kW

COP

4.70

2.70

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

51 dB(A)

51 dB(A)

Sound power level outdoor

63 dB(A)

63 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

168 %

117 %

Prated

4.00 kW

4.00 kW

SCOP

4.27

3.01

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

3.55 kW

3.50 kW

COP Tj = -7°C

2.35

1.90

Pdh Tj = +2°C

2.15 kW

2.10 kW

COP Tj = +2°C

4.21

2.95

Pdh Tj = +7°C

1.70 kW

1.40 kW

COP Tj = +7°C

6.10

4.10

Pdh Tj = 12°C

2.15 kW

2.00 kW

COP Tj = 12°C

9.00

4.81

Pdh Tj = Tbiv

3.55 kW

3.50 kW

COP Tj = Tbiv

2.35

1.90

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

3.50 kW

3.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.10

1.60

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

55 °C

55 °C

Poff

3 W

3 W

PTO

0 W

0 W

PSB

3 W

3 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.50 kW

0.90 kW

Annual energy consumption Qhe

1942 kWh

2716 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

125 %

COP

3.30

Heating up time

2:13 h:min

Standby power input

30.0 W

Reference hot water temperature

53.5 °C

Mixed water at 40°C

250 l