Certificate holders

Subtype

AQUATOP T43H

Certificate Holder
ELCO GmbH
Hohenzollernstrasse 31
72379 Hechingen
Germany
Registration number
011-1W0312
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
AQUATOP T43H
Driving energy
n/a
Heat Pump Type
Brine/Water and Water/Water
Refrigerant
R407c
Mass of Refrigerant

7,400 kg

Certification Date
04.05.2019
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 1

Models

AQUATOP T43H
Configure model
Model name
AQUATOP T43H
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x230V 50Hz

Brine/Water Heat Pump

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

44.44 kW

41.30 kW

El input

10.00 kW

13.50 kW

COP

4.40

3.10

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

193 %

181 %

Prated

44.40 kW

41.30 kW

SCOP

5.04

4.74

Tbiv

2 °C

2 °C

TOL

-22 °C

-22 °C

Pdh Tj = +2°C

44.40 kW

41.30 kW

COP Tj = +2°C

4.40

3.10

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

45.73 kW

44.19 kW

COP Tj = +7°C

4.84

4.12

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

47.06 kW

48.32 kW

COP Tj = 12°C

5.32

5.74

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

44.40 kW

41.30 kW

COP Tj = Tbiv

4.40

3.10

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

44.40 kW

41.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.40

3.10

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

11777 kWh

11648 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

197 %

187 %

Prated

44.40 kW

41.30 kW

SCOP

5.13

4.87

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

46.18 kW

45.02 kW

COP Tj = -7°C

5.02

4.37

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

47.06 kW

47.50 kW

COP Tj = +2°C

5.24

5.30

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

47.51 kW

49.15 kW

COP Tj = +7°C

5.46

6.01

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

47.95 kW

50.39 kW

COP Tj = 12°C

5.54

6.51

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

44.40 kW

41.30 kW

COP Tj = Tbiv

4.40

3.10

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

44.40 kW

41.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.40

3.10

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

21336 kWh

20905 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

192 %

180 %

Prated

44.40 kW

41.30 kW

SCOP

5.01

4.69

Tbiv

-10 °C

-10 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

44.84 kW

42.54 kW

COP Tj = -7°C

4.49

3.38

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

46.18 kW

45.84 kW

COP Tj = +2°C

5.02

4.65

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

47.06 kW

47.50 kW

COP Tj = +7°C

5.24

5.46

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

47.95 kW

49.56 kW

COP Tj = 12°C

5.54

6.39

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

44.40 kW

41.30 kW

COP Tj = Tbiv

4.40

3.10

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

44.40 kW

41.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.40

3.10

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

18311 kWh

18195 kWh

Water/Water Heat Pump

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

59.00 kW

54.50 kW

El input

11.30 kW

15.11 kW

COP

5.20

3.60

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

225 %

201 %

Prated

58.60 kW

54.50 kW

SCOP

5.83

5.23

Tbiv

2 °C

2 °C

TOL

-22 °C

-22 °C

Pdh Tj = +2°C

58.60 kW

54.50 kW

COP Tj = +2°C

5.19

3.56

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

59.93 kW

57.39 kW

COP Tj = +7°C

5.63

4.58

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

61.26 kW

61.52 kW

COP Tj = 12°C

6.11

6.20

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

58.60 kW

54.50 kW

COP Tj = Tbiv

5.19

3.56

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

58.60 kW

54.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.19

3.56

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

13422 kWh

13929 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

228 %

203 %

Prated

58.60 kW

54.50 kW

SCOP

5.90

5.26

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

60.38 kW

58.22 kW

COP Tj = -7°C

5.81

4.83

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

61.26 kW

60.70 kW

COP Tj = +2°C

6.02

5.76

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

61.71 kW

62.35 kW

COP Tj = +7°C

6.25

6.47

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

62.15 kW

63.59 kW

COP Tj = 12°C

6.33

6.97

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

58.60 kW

54.50 kW

COP Tj = Tbiv

5.19

3.56

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

58.60 kW

54.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.19

3.56

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

24485 kWh

25527 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

224 %

199 %

Prated

58.60 kW

54.50 kW

SCOP

5.81

5.17

Tbiv

-10 °C

-10 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

59.04 kW

55.74 kW

COP Tj = -7°C

5.28

3.84

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

60.38 kW

59.04 kW

COP Tj = +2°C

5.81

5.11

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

61.26 kW

60.70 kW

COP Tj = +7°C

6.02

5.92

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

62.15 kW

62.76 kW

COP Tj = 12°C

6.33

6.85

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

58.60 kW

54.50 kW

COP Tj = Tbiv

5.19

3.56

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

58.60 kW

54.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.19

3.56

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

20831 kWh

21775 kWh