Certificate holders

Subtype

AQUATOP T35H

Certificate Holder
ELCO GmbH
Hohenzollernstrasse 31
72379 Hechingen
Germany
Registration number
011-1W0311
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
AQUATOP T35H
Driving energy
n/a
Heat Pump Type
Brine/Water and Water/Water
Refrigerant
R407c
Mass of Refrigerant

6,200 kg

Certification Date
04.05.2019
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 1

Models

AQUATOP T35H
Configure model
Model name
AQUATOP T35H
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x230V 50Hz

Brine/Water Heat Pump

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

36.70 kW

34.70 kW

El input

8.30 kW

11.40 kW

COP

4.40

3.00

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

193 %

175 %

Prated

36.70 kW

34.70 kW

SCOP

5.04

4.59

Tbiv

2 °C

2 °C

TOL

-22 °C

-22 °C

Pdh Tj = +2°C

36.70 kW

34.70 kW

COP Tj = +2°C

4.40

3.00

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

37.80 kW

37.12 kW

COP Tj = +7°C

4.84

3.99

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

38.90 kW

40.60 kW

COP Tj = 12°C

5.32

5.55

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

36.70 kW

34.70 kW

COP Tj = Tbiv

4.40

3.00

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

36.70 kW

34.70 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.40

3.00

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

9736 kWh

10108 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

197 %

180 %

Prated

36.70 kW

34.70 kW

SCOP

5.13

4.71

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

38.17 kW

37.82 kW

COP Tj = -7°C

5.02

4.23

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

38.90 kW

39.91 kW

COP Tj = +2°C

5.24

5.13

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

39.27 kW

41.29 kW

COP Tj = +7°C

5.46

5.82

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

39.64 kW

42.33 kW

COP Tj = 12°C

5.54

6.30

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

36.70 kW

34.70 kW

COP Tj = Tbiv

4.40

3.00

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

36.70 kW

34.70 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.40

3.00

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

17636 kWh

18161 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

192 %

174 %

Prated

36.70 kW

34.70 kW

SCOP

5.01

4.54

Tbiv

-10 °C

-10 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

37.07 kW

35.74 kW

COP Tj = -7°C

4.49

3.27

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

38.17 kW

38.52 kW

COP Tj = +2°C

5.02

4.50

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

38.90 kW

39.91 kW

COP Tj = +7°C

5.24

5.28

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

39.64 kW

41.64 kW

COP Tj = 12°C

5.54

6.18

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

36.70 kW

34.70 kW

COP Tj = Tbiv

4.40

3.00

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

36.70 kW

34.70 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.40

3.00

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

15136 kWh

15793 kWh

Water/Water Heat Pump

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

49.00 kW

46.00 kW

El input

9.20 kW

12.60 kW

COP

5.30

3.70

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

230 %

203 %

Prated

48.85 kW

46.00 kW

SCOP

5.96

5.27

Tbiv

2 °C

2 °C

TOL

-22 °C

-22 °C

Pdh Tj = +2°C

48.85 kW

46.00 kW

COP Tj = +2°C

5.31

3.65

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

49.95 kW

48.42 kW

COP Tj = +7°C

5.75

4.64

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

51.05 kW

51.90 kW

COP Tj = 12°C

6.23

6.20

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

48.85 kW

46.00 kW

COP Tj = Tbiv

5.31

3.65

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

48.85 kW

46.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.31

3.65

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

10958 kWh

11670 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

233 %

204 %

Prated

48.85 kW

46.00 kW

SCOP

6.02

5.30

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

50.32 kW

49.12 kW

COP Tj = -7°C

5.93

4.88

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

51.05 kW

51.21 kW

COP Tj = +2°C

6.15

5.78

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

51.42 kW

52.59 kW

COP Tj = +7°C

6.37

6.47

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

51.79 kW

53.63 kW

COP Tj = 12°C

6.45

6.95

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

48.85 kW

46.00 kW

COP Tj = Tbiv

5.31

3.65

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

48.85 kW

46.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.31

3.65

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

19989 kWh

21386 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

229 %

200 %

Prated

48.85 kW

46.00 kW

SCOP

5.93

5.21

Tbiv

-10 °C

-10 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

49.22 kW

47.04 kW

COP Tj = -7°C

5.40

3.92

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

50.32 kW

49.82 kW

COP Tj = +2°C

5.93

5.15

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

51.05 kW

51.21 kW

COP Tj = +7°C

6.15

5.93

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

51.79 kW

52.94 kW

COP Tj = 12°C

6.45

6.83

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

48.85 kW

46.00 kW

COP Tj = Tbiv

5.31

3.65

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

48.85 kW

46.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.31

3.65

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

17006 kWh

18234 kWh