6,200 kg
Brine/Water Heat Pump
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
36.70 kW
34.70 kW
El input
8.30 kW
11.40 kW
COP
4.40
3.00
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
193 %
175 %
Prated
36.70 kW
34.70 kW
SCOP
5.04
4.59
Tbiv
2 °C
2 °C
TOL
-22 °C
-22 °C
Pdh Tj = +2°C
36.70 kW
34.70 kW
COP Tj = +2°C
4.40
3.00
Cdh Tj = +2 °C
Pdh Tj = +7°C
37.80 kW
37.12 kW
COP Tj = +7°C
4.84
3.99
Cdh Tj = +7 °C
Pdh Tj = 12°C
38.90 kW
40.60 kW
COP Tj = 12°C
5.32
5.55
Cdh Tj = +12 °C
Pdh Tj = Tbiv
36.70 kW
34.70 kW
COP Tj = Tbiv
4.40
3.00
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
36.70 kW
34.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
3.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
9736 kWh
10108 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
197 %
180 %
Prated
36.70 kW
34.70 kW
SCOP
5.13
4.71
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
38.17 kW
37.82 kW
COP Tj = -7°C
5.02
4.23
Cdh Tj = -7 °C
Pdh Tj = +2°C
38.90 kW
39.91 kW
COP Tj = +2°C
5.24
5.13
Cdh Tj = +2 °C
Pdh Tj = +7°C
39.27 kW
41.29 kW
COP Tj = +7°C
5.46
5.82
Cdh Tj = +7 °C
Pdh Tj = 12°C
39.64 kW
42.33 kW
COP Tj = 12°C
5.54
6.30
Cdh Tj = +12 °C
Pdh Tj = Tbiv
36.70 kW
34.70 kW
COP Tj = Tbiv
4.40
3.00
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
36.70 kW
34.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
3.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
17636 kWh
18161 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
192 %
174 %
Prated
36.70 kW
34.70 kW
SCOP
5.01
4.54
Tbiv
-10 °C
-10 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
37.07 kW
35.74 kW
COP Tj = -7°C
4.49
3.27
Cdh Tj = -7 °C
Pdh Tj = +2°C
38.17 kW
38.52 kW
COP Tj = +2°C
5.02
4.50
Cdh Tj = +2 °C
Pdh Tj = +7°C
38.90 kW
39.91 kW
COP Tj = +7°C
5.24
5.28
Cdh Tj = +7 °C
Pdh Tj = 12°C
39.64 kW
41.64 kW
COP Tj = 12°C
5.54
6.18
Cdh Tj = +12 °C
Pdh Tj = Tbiv
36.70 kW
34.70 kW
COP Tj = Tbiv
4.40
3.00
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
36.70 kW
34.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.40
3.00
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
15136 kWh
15793 kWh
Water/Water Heat Pump
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
49.00 kW
46.00 kW
El input
9.20 kW
12.60 kW
COP
5.30
3.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
230 %
203 %
Prated
48.85 kW
46.00 kW
SCOP
5.96
5.27
Tbiv
2 °C
2 °C
TOL
-22 °C
-22 °C
Pdh Tj = +2°C
48.85 kW
46.00 kW
COP Tj = +2°C
5.31
3.65
Cdh Tj = +2 °C
Pdh Tj = +7°C
49.95 kW
48.42 kW
COP Tj = +7°C
5.75
4.64
Cdh Tj = +7 °C
Pdh Tj = 12°C
51.05 kW
51.90 kW
COP Tj = 12°C
6.23
6.20
Cdh Tj = +12 °C
Pdh Tj = Tbiv
48.85 kW
46.00 kW
COP Tj = Tbiv
5.31
3.65
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
48.85 kW
46.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.31
3.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
10958 kWh
11670 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
233 %
204 %
Prated
48.85 kW
46.00 kW
SCOP
6.02
5.30
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
50.32 kW
49.12 kW
COP Tj = -7°C
5.93
4.88
Cdh Tj = -7 °C
Pdh Tj = +2°C
51.05 kW
51.21 kW
COP Tj = +2°C
6.15
5.78
Cdh Tj = +2 °C
Pdh Tj = +7°C
51.42 kW
52.59 kW
COP Tj = +7°C
6.37
6.47
Cdh Tj = +7 °C
Pdh Tj = 12°C
51.79 kW
53.63 kW
COP Tj = 12°C
6.45
6.95
Cdh Tj = +12 °C
Pdh Tj = Tbiv
48.85 kW
46.00 kW
COP Tj = Tbiv
5.31
3.65
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
48.85 kW
46.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.31
3.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
19989 kWh
21386 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
229 %
200 %
Prated
48.85 kW
46.00 kW
SCOP
5.93
5.21
Tbiv
-10 °C
-10 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
49.22 kW
47.04 kW
COP Tj = -7°C
5.40
3.92
Cdh Tj = -7 °C
Pdh Tj = +2°C
50.32 kW
49.82 kW
COP Tj = +2°C
5.93
5.15
Cdh Tj = +2 °C
Pdh Tj = +7°C
51.05 kW
51.21 kW
COP Tj = +7°C
6.15
5.93
Cdh Tj = +7 °C
Pdh Tj = 12°C
51.79 kW
52.94 kW
COP Tj = 12°C
6.45
6.83
Cdh Tj = +12 °C
Pdh Tj = Tbiv
48.85 kW
46.00 kW
COP Tj = Tbiv
5.31
3.65
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
48.85 kW
46.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.31
3.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
17006 kWh
18234 kWh