Certificate holders

Subtype

AQUATOP T28H

Certificate Holder
ELCO GmbH
Hohenzollernstrasse 31
72379 Hechingen
Germany
Registration number
011-1W0310
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
AQUATOP T28H
Driving energy
n/a
Heat Pump Type
Brine/Water and Water/Water
Refrigerant
R407c
Mass of Refrigerant

5,700 kg

Certification Date
04.05.2019
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 1

Models

AQUATOP T28H
Configure model
Model name
AQUATOP T28H
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x230V 50Hz

Brine/Water Heat Pump

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

28.70 kW

24.80 kW

El input

6.50 kW

9.20 kW

COP

4.40

2.70

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

193 %

157 %

Prated

28.70 kW

24.80 kW

SCOP

5.03

4.13

Tbiv

2 °C

2 °C

TOL

-22 °C

-22 °C

Pdh Tj = +2°C

28.70 kW

24.80 kW

COP Tj = +2°C

4.40

2.70

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

29.56 kW

26.54 kW

COP Tj = +7°C

4.84

3.59

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

30.42 kW

29.02 kW

COP Tj = 12°C

5.32

5.00

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

28.70 kW

24.80 kW

COP Tj = Tbiv

4.40

2.70

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

28.70 kW

24.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.40

2.70

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

7630 kWh

8030 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

197 %

161 %

Prated

28.70 kW

24.80 kW

SCOP

5.13

4.23

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

29.85 kW

27.03 kW

COP Tj = -7°C

5.02

3.81

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

30.42 kW

28.52 kW

COP Tj = +2°C

5.24

4.62

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

30.71 kW

29.51 kW

COP Tj = +7°C

5.46

5.24

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

31.00 kW

30.26 kW

COP Tj = 12°C

5.54

5.67

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

28.70 kW

24.80 kW

COP Tj = Tbiv

4.40

2.70

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

28.70 kW

24.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.40

2.70

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

13792 kWh

14453 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

192 %

155 %

Prated

28.70 kW

24.80 kW

SCOP

5.01

4.08

Tbiv

-10 °C

-10 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

28.99 kW

25.54 kW

COP Tj = -7°C

4.49

2.94

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

29.85 kW

27.53 kW

COP Tj = +2°C

5.02

4.05

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

30.42 kW

28.52 kW

COP Tj = +7°C

5.24

4.75

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

31.00 kW

29.76 kW

COP Tj = 12°C

5.54

5.56

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

28.70 kW

24.80 kW

COP Tj = Tbiv

4.40

2.70

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

28.70 kW

24.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.40

2.70

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

11837 kWh

12560 kWh

Water/Water Heat Pump

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

35.50 kW

34.20 kW

El input

7.00 kW

9.70 kW

COP

5.10

3.50

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

233 %

191 %

Prated

37.20 kW

34.16 kW

SCOP

6.02

4.98

Tbiv

2 °C

2 °C

TOL

-22 °C

-22 °C

Pdh Tj = +2°C

37.20 kW

34.16 kW

COP Tj = +2°C

5.38

3.52

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

38.06 kW

35.90 kW

COP Tj = +7°C

5.82

4.41

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

38.92 kW

38.38 kW

COP Tj = 12°C

6.30

5.82

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

37.20 kW

34.16 kW

COP Tj = Tbiv

5.38

3.52

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

37.20 kW

34.16 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.38

3.52

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

8253 kWh

9170 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

236 %

192 %

Prated

37.20 kW

34.16 kW

SCOP

6.09

5.01

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

38.35 kW

36.39 kW

COP Tj = -7°C

5.99

4.63

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

38.92 kW

37.88 kW

COP Tj = +2°C

6.22

5.43

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

39.21 kW

38.87 kW

COP Tj = +7°C

6.44

6.05

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

39.50 kW

39.62 kW

COP Tj = 12°C

6.52

6.48

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

37.20 kW

34.16 kW

COP Tj = Tbiv

5.38

3.52

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

37.20 kW

34.16 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.38

3.52

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

15056 kWh

16805 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

232 %

189 %

Prated

37.20 kW

34.16 kW

SCOP

6.00

4.92

Tbiv

-10 °C

-10 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

37.49 kW

34.90 kW

COP Tj = -7°C

5.47

3.76

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

38.35 kW

36.89 kW

COP Tj = +2°C

5.99

4.87

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

38.92 kW

37.88 kW

COP Tj = +7°C

6.22

5.57

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

39.50 kW

39.12 kW

COP Tj = 12°C

6.52

6.38

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

37.20 kW

34.16 kW

COP Tj = Tbiv

5.38

3.52

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

37.20 kW

34.16 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.38

3.52

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

12807 kWh

14330 kWh