Certificate holders

Subtype

AQUATOP T22H

Certificate Holder
ELCO GmbH
Hohenzollernstrasse 31
72379 Hechingen
Germany
Registration number
011-1W0309
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
AQUATOP T22H
Driving energy
n/a
Heat Pump Type
Brine/Water and Water/Water
Refrigerant
R407c
Mass of Refrigerant

4,100 kg

Certification Date
04.05.2019
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 1

Models

AQUATOP T22H
Configure model
Model name
AQUATOP T22H
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x230V 50Hz

Brine/Water Heat Pump

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

21.00 kW

20.40 kW

El input

4.60 kW

7.00 kW

COP

4.60

2.90

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

54 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

202 %

169 %

Prated

21.00 kW

20.40 kW

SCOP

5.25

4.42

Tbiv

2 °C

2 °C

TOL

-22 °C

-22 °C

Pdh Tj = +2°C

21.00 kW

20.40 kW

COP Tj = +2°C

4.60

2.90

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

21.63 kW

21.83 kW

COP Tj = +7°C

5.06

3.86

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

22.26 kW

23.87 kW

COP Tj = 12°C

5.57

5.37

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

21.00 kW

20.40 kW

COP Tj = Tbiv

4.60

2.90

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

21.00 kW

20.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.60

2.90

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5341 kWh

6160 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

54 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

206 %

174 %

Prated

21.00 kW

20.40 kW

SCOP

5.35

4.54

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

21.84 kW

22.24 kW

COP Tj = -7°C

5.24

4.09

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

22.26 kW

23.46 kW

COP Tj = +2°C

5.47

4.96

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

22.47 kW

24.28 kW

COP Tj = +7°C

5.70

5.63

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

22.68 kW

24.89 kW

COP Tj = 12°C

5.80

6.09

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

21.00 kW

20.40 kW

COP Tj = Tbiv

4.60

2.90

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

21.00 kW

20.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.60

2.90

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

9677 kWh

11077 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

54 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

201 %

167 %

Prated

21.00 kW

20.40 kW

SCOP

5.23

4.38

Tbiv

-10 °C

-10 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

21.21 kW

21.01 kW

COP Tj = -7°C

4.69

3.16

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

21.84 kW

22.64 kW

COP Tj = +2°C

5.24

4.35

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

22.26 kW

23.46 kW

COP Tj = +7°C

5.47

5.10

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

22.68 kW

24.48 kW

COP Tj = 12°C

5.80

5.97

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

21.00 kW

20.40 kW

COP Tj = Tbiv

4.60

2.90

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

21.00 kW

20.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.60

2.90

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

8297 kWh

9624 kWh

Water/Water Heat Pump

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

25.90 kW

25.60 kW

El input

4.70 kW

7.30 kW

COP

5.50

3.52

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

54 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

241 %

195 %

Prated

25.90 kW

25.56 kW

SCOP

6.22

5.08

Tbiv

2 °C

2 °C

TOL

-22 °C

-22 °C

Pdh Tj = +2°C

25.90 kW

25.56 kW

COP Tj = +2°C

5.55

3.52

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

26.53 kW

26.99 kW

COP Tj = +7°C

6.00

4.48

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

27.16 kW

29.03 kW

COP Tj = 12°C

6.51

5.99

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

25.90 kW

25.56 kW

COP Tj = Tbiv

5.55

3.52

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

25.90 kW

25.56 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.55

3.52

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5566 kWh

6720 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

54 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

244 %

197 %

Prated

25.90 kW

25.56 kW

SCOP

6.29

5.12

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

26.74 kW

27.40 kW

COP Tj = -7°C

6.19

4.71

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

27.16 kW

28.62 kW

COP Tj = +2°C

6.42

5.58

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

27.37 kW

29.44 kW

COP Tj = +7°C

6.64

6.25

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

27.58 kW

30.05 kW

COP Tj = 12°C

6.74

6.71

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

25.90 kW

25.56 kW

COP Tj = Tbiv

5.55

3.52

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

25.90 kW

25.56 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.55

3.52

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

10151 kWh

12316 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

54 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

240 %

193 %

Prated

25.90 kW

25.56 kW

SCOP

6.20

5.03

Tbiv

-10 °C

-10 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

26.11 kW

26.17 kW

COP Tj = -7°C

5.64

3.78

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

26.74 kW

27.80 kW

COP Tj = +2°C

6.19

4.97

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

27.16 kW

28.62 kW

COP Tj = +7°C

6.42

5.72

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

27.58 kW

29.64 kW

COP Tj = 12°C

6.74

6.59

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

25.90 kW

25.56 kW

COP Tj = Tbiv

5.55

3.52

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

25.90 kW

25.56 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.55

3.53

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

0 W

0 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

8634 kWh

10501 kWh