3,800 kg
Brine/Water Heat Pump
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.83 kW
14.78 kW
El input
3.44 kW
5.34 kW
COP
4.89
2.77
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
159 %
Prated
16.92 kW
15.27 kW
SCOP
5.19
4.19
Tbiv
2 °C
2 °C
TOL
-22 °C
-22 °C
Pdh Tj = +2°C
16.92 kW
15.27 kW
COP Tj = +2°C
4.67
2.80
Cdh Tj = +2 °C
Pdh Tj = +7°C
17.59 kW
16.64 kW
COP Tj = +7°C
5.23
3.64
Cdh Tj = +7 °C
Pdh Tj = 12°C
17.76 kW
18.47 kW
COP Tj = 12°C
5.37
5.15
Cdh Tj = +12 °C
Pdh Tj = Tbiv
16.92 kW
15.27 kW
COP Tj = Tbiv
4.67
2.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
16.92 kW
15.27 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.67
2.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
20 W
20 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4354 kWh
4872 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
203 %
160 %
Prated
16.92 kW
15.27 kW
SCOP
5.28
4.19
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
17.76 kW
16.79 kW
COP Tj = -7°C
5.37
3.86
Cdh Tj = -7 °C
Pdh Tj = +2°C
17.76 kW
18.01 kW
COP Tj = +2°C
5.37
4.73
Cdh Tj = +2 °C
Pdh Tj = +7°C
17.76 kW
18.78 kW
COP Tj = +7°C
5.37
5.43
Cdh Tj = +7 °C
Pdh Tj = 12°C
17.76 kW
19.08 kW
COP Tj = 12°C
5.37
5.74
Cdh Tj = +12 °C
Pdh Tj = Tbiv
16.92 kW
15.27 kW
COP Tj = Tbiv
4.67
2.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
16.92 kW
15.27 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.67
2.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
20 W
20 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
7901 kWh
8986 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45 dB(A)
45 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
201 %
158 %
Prated
16.92 kW
15.27 kW
SCOP
5.22
4.15
Tbiv
-10 °C
-10 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
17.08 kW
15.72 kW
COP Tj = -7°C
5.37
3.05
Cdh Tj = -7 °C
Pdh Tj = +2°C
17.76 kW
17.10 kW
COP Tj = +2°C
5.37
4.11
Cdh Tj = +2 °C
Pdh Tj = +7°C
17.76 kW
18.17 kW
COP Tj = +7°C
5.37
4.87
Cdh Tj = +7 °C
Pdh Tj = 12°C
17.76 kW
19.10 kW
COP Tj = 12°C
5.37
5.74
Cdh Tj = +12 °C
Pdh Tj = Tbiv
16.92 kW
15.27 kW
COP Tj = Tbiv
4.67
2.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
16.92 kW
15.27 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.67
2.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
20 W
20 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6700 kWh
7605 kWh
Water/Water Heat Pump
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
21.27 kW
19.35 kW
El input
3.53 kW
5.31 kW
COP
6.03
3.64
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
34 dB(A)
34 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
260 %
210 %
Prated
21.27 kW
19.35 kW
SCOP
6.70
5.44
Tbiv
2 °C
2 °C
TOL
-22 °C
-22 °C
Pdh Tj = +2°C
21.27 kW
19.35 kW
COP Tj = +2°C
6.03
3.64
Cdh Tj = +2 °C
Pdh Tj = +7°C
22.11 kW
21.09 kW
COP Tj = +7°C
6.75
4.73
Cdh Tj = +7 °C
Pdh Tj = 12°C
22.33 kW
23.41 kW
COP Tj = 12°C
6.93
6.70
Cdh Tj = +12 °C
Pdh Tj = Tbiv
21.27 kW
19.35 kW
COP Tj = Tbiv
6.03
3.64
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
21.27 kW
19.35 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
6.03
3.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
20 W
20 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4242 kWh
4754 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
34 dB(A)
34 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
264 %
215 %
Prated
21.27 kW
19.35 kW
SCOP
6.81
5.58
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
22.33 kW
21.28 kW
COP Tj = -7°C
6.93
5.02
Cdh Tj = -7 °C
Pdh Tj = +2°C
22.33 kW
22.82 kW
COP Tj = +2°C
6.93
6.15
Cdh Tj = +2 °C
Pdh Tj = +7°C
22.33 kW
23.80 kW
COP Tj = +7°C
6.93
7.06
Cdh Tj = +7 °C
Pdh Tj = 12°C
22.33 kW
24.18 kW
COP Tj = 12°C
6.93
7.46
Cdh Tj = +12 °C
Pdh Tj = Tbiv
21.27 kW
19.35 kW
COP Tj = Tbiv
6.03
3.64
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
21.27 kW
19.35 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
6.03
3.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
20 W
20 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
7701 kWh
8552 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
34 dB(A)
34 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
261 %
207 %
Prated
21.47 kW
19.35 kW
SCOP
6.73
5.39
Tbiv
-10 °C
-10 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
21.47 kW
19.92 kW
COP Tj = -7°C
6.21
3.97
Cdh Tj = -7 °C
Pdh Tj = +2°C
22.33 kW
21.67 kW
COP Tj = +2°C
6.93
5.34
Cdh Tj = +2 °C
Pdh Tj = +7°C
22.33 kW
23.02 kW
COP Tj = +7°C
6.93
6.93
Cdh Tj = +7 °C
Pdh Tj = 12°C
22.33 kW
24.18 kW
COP Tj = 12°C
6.93
7.46
Cdh Tj = +12 °C
Pdh Tj = Tbiv
21.47 kW
19.35 kW
COP Tj = Tbiv
6.21
3.64
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
21.47 kW
19.35 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
6.21
3.64
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
65 °C
65 °C
Poff
0 W
0 W
PTO
20 W
20 W
PSB
20 W
20 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6526 kWh
7422 kWh