Certificate holders

Subtype

AQUATOP S17

Certificate Holder
ELCO GmbH
Hohenzollernstrasse 31
72379 Hechingen
Germany
Registration number
011-1W0308
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
AQUATOP S17
Driving energy
n/a
Heat Pump Type
Brine/Water and Water/Water
Refrigerant
R410A
Mass of Refrigerant

3,800 kg

Certification Date
04.05.2019
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 1

Models

AQUATOP S17
Configure model
Model name
AQUATOP S17
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x230V 50Hz

Brine/Water Heat Pump

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.83 kW

14.78 kW

El input

3.44 kW

5.34 kW

COP

4.89

2.77

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

200 %

159 %

Prated

16.92 kW

15.27 kW

SCOP

5.19

4.19

Tbiv

2 °C

2 °C

TOL

-22 °C

-22 °C

Pdh Tj = +2°C

16.92 kW

15.27 kW

COP Tj = +2°C

4.67

2.80

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

17.59 kW

16.64 kW

COP Tj = +7°C

5.23

3.64

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

17.76 kW

18.47 kW

COP Tj = 12°C

5.37

5.15

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

16.92 kW

15.27 kW

COP Tj = Tbiv

4.67

2.80

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

16.92 kW

15.27 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.67

2.80

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

20 W

20 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

4354 kWh

4872 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

203 %

160 %

Prated

16.92 kW

15.27 kW

SCOP

5.28

4.19

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

17.76 kW

16.79 kW

COP Tj = -7°C

5.37

3.86

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

17.76 kW

18.01 kW

COP Tj = +2°C

5.37

4.73

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

17.76 kW

18.78 kW

COP Tj = +7°C

5.37

5.43

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

17.76 kW

19.08 kW

COP Tj = 12°C

5.37

5.74

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

16.92 kW

15.27 kW

COP Tj = Tbiv

4.67

2.80

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

16.92 kW

15.27 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.67

2.80

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

20 W

20 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

7901 kWh

8986 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

45 dB(A)

45 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

201 %

158 %

Prated

16.92 kW

15.27 kW

SCOP

5.22

4.15

Tbiv

-10 °C

-10 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

17.08 kW

15.72 kW

COP Tj = -7°C

5.37

3.05

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

17.76 kW

17.10 kW

COP Tj = +2°C

5.37

4.11

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

17.76 kW

18.17 kW

COP Tj = +7°C

5.37

4.87

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

17.76 kW

19.10 kW

COP Tj = 12°C

5.37

5.74

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

16.92 kW

15.27 kW

COP Tj = Tbiv

4.67

2.80

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

16.92 kW

15.27 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.67

2.80

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

20 W

20 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

6700 kWh

7605 kWh

Water/Water Heat Pump

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

21.27 kW

19.35 kW

El input

3.53 kW

5.31 kW

COP

6.03

3.64

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

34 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

260 %

210 %

Prated

21.27 kW

19.35 kW

SCOP

6.70

5.44

Tbiv

2 °C

2 °C

TOL

-22 °C

-22 °C

Pdh Tj = +2°C

21.27 kW

19.35 kW

COP Tj = +2°C

6.03

3.64

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

22.11 kW

21.09 kW

COP Tj = +7°C

6.75

4.73

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

22.33 kW

23.41 kW

COP Tj = 12°C

6.93

6.70

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

21.27 kW

19.35 kW

COP Tj = Tbiv

6.03

3.64

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

21.27 kW

19.35 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

6.03

3.64

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

20 W

20 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

4242 kWh

4754 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

34 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

264 %

215 %

Prated

21.27 kW

19.35 kW

SCOP

6.81

5.58

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

22.33 kW

21.28 kW

COP Tj = -7°C

6.93

5.02

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

22.33 kW

22.82 kW

COP Tj = +2°C

6.93

6.15

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

22.33 kW

23.80 kW

COP Tj = +7°C

6.93

7.06

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

22.33 kW

24.18 kW

COP Tj = 12°C

6.93

7.46

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

21.27 kW

19.35 kW

COP Tj = Tbiv

6.03

3.64

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

21.27 kW

19.35 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

6.03

3.64

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

20 W

20 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

7701 kWh

8552 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

34 dB(A)

34 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

261 %

207 %

Prated

21.47 kW

19.35 kW

SCOP

6.73

5.39

Tbiv

-10 °C

-10 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

21.47 kW

19.92 kW

COP Tj = -7°C

6.21

3.97

Cdh Tj = -7 °C

 

 

Pdh Tj = +2°C

22.33 kW

21.67 kW

COP Tj = +2°C

6.93

5.34

Cdh Tj = +2 °C

 

 

Pdh Tj = +7°C

22.33 kW

23.02 kW

COP Tj = +7°C

6.93

6.93

Cdh Tj = +7 °C

 

 

Pdh Tj = 12°C

22.33 kW

24.18 kW

COP Tj = 12°C

6.93

7.46

Cdh Tj = +12 °C

 

 

Pdh Tj = Tbiv

21.47 kW

19.35 kW

COP Tj = Tbiv

6.21

3.64

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

21.47 kW

19.35 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

6.21

3.64

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

20 W

20 W

PSB

20 W

20 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

6526 kWh

7422 kWh