Certificate holders

Subtype

AEROTOP SG12 INOX / INOX OPTIC

Certificate Holder
ELCO GmbH
Hohenzollernstrasse 31
72379 Hechingen
Germany
Registration number
011-1W0475
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
AEROTOP SG12 INOX / INOX OPTIC
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

4,270 kg

Certification Date
05.07.2021
Testing basis
HP KEYMARK certification scheme rules rev. 8
Generate PDF Export model CSV
  • Number of models 1

Models

AEROTOP SG12 INOX / INOX OPTIC
Configure model
Model name
AEROTOP SG12 INOX / INOX OPTIC
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

7.15 kW

6.70 kW

El input

1.32 kW

2.12 kW

COP

5.40

3.16

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

54 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

220 %

154 %

Prated

8.24 kW

7.70 kW

SCOP

5.57

3.93

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

8.24 kW

7.70 kW

COP Tj = +2°C

4.56

2.95

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

5.30 kW

5.18 kW

COP Tj = +7°C

5.70

3.58

Cdh Tj = +7 °C

0.980

0.980

Pdh Tj = 12°C

4.48 kW

4.30 kW

COP Tj = 12°C

7.47

5.54

Cdh Tj = +12 °C

0.960

0.960

Pdh Tj = Tbiv

8.24 kW

7.70 kW

COP Tj = Tbiv

4.56

2.95

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.24 kW

7.70 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.56

2.95

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

0.990

WTOL

60 °C

60 °C

Poff

24 W

24 W

PTO

24 W

24 W

PSB

24 W

24 W

PCK

24 W

24 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

1977 kWh

2616 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

54 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

152 %

128 %

Prated

18.64 kW

18.44 kW

SCOP

3.86

3.26

Tbiv

-7 °C

-7 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

11.28 kW

11.16 kW

COP Tj = -7°C

3.63

3.04

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

6.82 kW

6.86 kW

COP Tj = +2°C

5.68

4.40

Cdh Tj = +2 °C

0.980

0.980

Pdh Tj = +7°C

4.38 kW

4.38 kW

COP Tj = +7°C

6.35

5.54

Cdh Tj = +7 °C

0.960

0.960

Pdh Tj = 12°C

4.37 kW

4.47 kW

COP Tj = 12°C

8.25

7.10

Cdh Tj = +12 °C

0.960

0.960

Pdh Tj = Tbiv

11.28 kW

11.16 kW

COP Tj = Tbiv

3.63

3.04

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.93 kW

6.08 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.03

1.47

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.960

0.960

WTOL

60 °C

60 °C

Poff

24 W

24 W

PTO

24 W

24 W

PSB

24 W

24 W

PCK

24 W

24 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

18.64 kW

18.44 kW

Annual energy consumption Qhe

11889 kWh

13937 kWh

Pdh Tj = -15°C (if TOL<-20°C)

 

 

COP Tj = -15°C (if TOL<-20°C)

 

 

Cdh Tj = -15 °C

 

 

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

54 dB(A)

54 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

206 %

150 %

Prated

12.63 kW

12.58 kW

SCOP

5.23

3.83

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

11.17 kW

11.15 kW

COP Tj = -7°C

3.87

2.64

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

6.85 kW

6.76 kW

COP Tj = +2°C

5.27

3.95

Cdh Tj = +2 °C

0.980

0.980

Pdh Tj = +7°C

4.37 kW

4.36 kW

COP Tj = +7°C

6.75

4.62

Cdh Tj = +7 °C

0.960

0.960

Pdh Tj = 12°C

4.34 kW

4.20 kW

COP Tj = 12°C

8.26

6.35

Cdh Tj = +12 °C

0.960

0.960

Pdh Tj = Tbiv

11.17 kW

11.15 kW

COP Tj = Tbiv

3.87

2.64

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.00 kW

10.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.99

2.27

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.960

0.960

WTOL

60 °C

60 °C

Poff

24 W

24 W

PTO

24 W

24 W

PSB

24 W

24 W

PCK

24 W

24 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.63 kW

1.78 kW

Annual energy consumption Qhe

4984 kWh

6793 kWh