Certificate holders

Subtype

WPF 05, WPF 05 cool, WPC 05, WPC 05 cool

Certificate Holder
STIEBEL ELTRON GmbH & Co KG
Dr. Stiebel Straße 33
37603 Holzminden
Germany
Registration number
011-1W0009
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
WPF 05, WPF 05 cool, WPC 05, WPC 05 cool
Driving energy
Electricity
Heat Pump Type
Brine/Water
Refrigerant
R410A
Mass of Refrigerant

1,400 kg

Certification Date
23.08.2016
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 8

Models

WPF 05, average climates
Configure model
Model name
WPF 05, average climates
Application
Heating (medium temp)
Units
Indoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5.82 kW

5.19 kW

El input

1.21 kW

1.85 kW

COP

4.80

2.81

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

46 dB(A)

46 dB(A)

Sound power level outdoor

0 dB(A)

0 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

205 %

134 %

Prated

6.00 kW

5.00 kW

SCOP

5.32

3.55

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.80 kW

5.30 kW

COP Tj = -7°C

4.87

2.94

Pdh Tj = +2°C

5.90 kW

5.50 kW

COP Tj = +2°C

5.24

3.49

Pdh Tj = +7°C

6.00 kW

5.60 kW

COP Tj = +7°C

5.61

3.92

Pdh Tj = 12°C

6.00 kW

5.70 kW

COP Tj = 12°C

6.03

4.44

Pdh Tj = Tbiv

5.80 kW

5.20 kW

COP Tj = Tbiv

4.81

2.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.80 kW

5.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

2.81

Rated airflow rate

0 m³/h

0 m³/h

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

54 W

54 W

PSB

9 W

9 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2262 kWh

3017 kWh

WPC 05, all climates
Configure model
Model name
WPC 05, all climates
Application
Heating (low temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

5.82 kW

El input

1.21 kW

COP

4.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Warmer Climate

EN 12102-1

Sound power level indoor

47 dB(A)

Sound power level outdoor

0 dB(A)

EN 14825

ηs

203 %

Prated

6.00 kW

SCOP

5.28

Tbiv

2 °C

TOL

0 °C

Pdh Tj = -7°C

0.00 kW

COP Tj = -7°C

0.00

Pdh Tj = +2°C

5.80 kW

COP Tj = +2°C

4.81

Cdh Tj = +2 °C

 

Pdh Tj = +7°C

5.90 kW

COP Tj = +7°C

5.16

Cdh Tj = +7 °C

 

Pdh Tj = 12°C

6.00 kW

COP Tj = 12°C

5.75

Cdh Tj = +12 °C

 

Pdh Tj = Tbiv

5.80 kW

COP Tj = Tbiv

4.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

Rated airflow rate

0 m³/h

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

WTOL

65 °C

Poff

0 W

PTO

54 W

PSB

9 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.20 kW

Annual energy consumption Qhe

1473 kWh

Colder Climate

EN 12102-1

Sound power level indoor

47 dB(A)

Sound power level outdoor

0 dB(A)

EN 14825

ηs

212 %

Prated

7.00 kW

SCOP

5.49

Tbiv

-15 °C

TOL

-22 °C

Pdh Tj = -7°C

5.90 kW

COP Tj = -7°C

5.43

Cdh Tj = -7 °C

 

Pdh Tj = +2°C

6.00 kW

COP Tj = +2°C

5.72

Cdh Tj = +2 °C

 

Pdh Tj = +7°C

6.00 kW

COP Tj = +7°C

5.97

Cdh Tj = +7 °C

 

Pdh Tj = 12°C

6.00 kW

COP Tj = 12°C

6.01

Cdh Tj = +12 °C

 

Pdh Tj = Tbiv

5.90 kW

COP Tj = Tbiv

5.31

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.90 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.31

Rated airflow rate

0 m³/h

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

WTOL

65 °C

Poff

0 W

PTO

54 W

PSB

9 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

1.10 kW

Annual energy consumption Qhe

3254 kWh

Average Climate

EN 12102-1

Sound power level indoor

47 dB(A)

Sound power level outdoor

0 dB(A)

EN 14825

ηs

205 %

Prated

6.00 kW

SCOP

5.32

Tbiv

-10 °C

TOL

-10 °C

Pdh Tj = -7°C

5.80 kW

COP Tj = -7°C

4.87

Pdh Tj = +2°C

5.90 kW

COP Tj = +2°C

5.24

Pdh Tj = +7°C

6.00 kW

COP Tj = +7°C

5.61

Pdh Tj = 12°C

6.00 kW

COP Tj = 12°C

6.03

Pdh Tj = Tbiv

5.80 kW

COP Tj = Tbiv

4.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

Rated airflow rate

0 m³/h

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

WTOL

65 °C

Poff

0 W

PTO

54 W

PSB

9 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

2262 kWh

WPC 05, average climates
Configure model
Model name
WPC 05, average climates
Application
Heating (medium temp)
Units
Indoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5.82 kW

5.19 kW

El input

1.21 kW

1.85 kW

COP

4.80

2.81

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

47 dB(A)

47 dB(A)

Sound power level outdoor

0 dB(A)

0 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

205 %

134 %

Prated

6.00 kW

5.00 kW

SCOP

5.32

3.55

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.80 kW

5.30 kW

COP Tj = -7°C

4.87

2.94

Pdh Tj = +2°C

5.90 kW

5.50 kW

COP Tj = +2°C

5.24

3.49

Pdh Tj = +7°C

6.00 kW

5.60 kW

COP Tj = +7°C

5.61

3.92

Pdh Tj = 12°C

6.00 kW

5.70 kW

COP Tj = 12°C

6.03

4.44

Pdh Tj = Tbiv

5.80 kW

5.20 kW

COP Tj = Tbiv

4.81

2.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.80 kW

5.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

2.81

Rated airflow rate

0 m³/h

0 m³/h

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

54 W

54 W

PSB

9 W

9 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2262 kWh

3017 kWh

WPF 05, all climates
Configure model
Model name
WPF 05, all climates
Application
Heating (low temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

5.82 kW

El input

1.21 kW

COP

4.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Warmer Climate

EN 12102-1

Sound power level indoor

46 dB(A)

Sound power level outdoor

0 dB(A)

EN 14825

ηs

203 %

Prated

6.00 kW

SCOP

5.28

Tbiv

2 °C

TOL

0 °C

Pdh Tj = -7°C

0.00 kW

COP Tj = -7°C

0.00

Pdh Tj = +2°C

5.80 kW

COP Tj = +2°C

4.81

Cdh Tj = +2 °C

 

Pdh Tj = +7°C

5.90 kW

COP Tj = +7°C

5.16

Cdh Tj = +7 °C

 

Pdh Tj = 12°C

6.00 kW

COP Tj = 12°C

5.75

Cdh Tj = +12 °C

 

Pdh Tj = Tbiv

5.80 kW

COP Tj = Tbiv

4.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

Rated airflow rate

0 m³/h

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

WTOL

65 °C

Poff

0 W

PTO

54 W

PSB

9 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.20 kW

Annual energy consumption Qhe

1473 kWh

Colder Climate

EN 12102-1

Sound power level indoor

46 dB(A)

Sound power level outdoor

0 dB(A)

EN 14825

ηs

212 %

Prated

7.00 kW

SCOP

5.49

Tbiv

-15 °C

TOL

-22 °C

Pdh Tj = -7°C

5.90 kW

COP Tj = -7°C

5.43

Cdh Tj = -7 °C

 

Pdh Tj = +2°C

6.00 kW

COP Tj = +2°C

5.72

Cdh Tj = +2 °C

 

Pdh Tj = +7°C

6.00 kW

COP Tj = +7°C

5.97

Cdh Tj = +7 °C

 

Pdh Tj = 12°C

6.00 kW

COP Tj = 12°C

6.01

Cdh Tj = +12 °C

 

Pdh Tj = Tbiv

5.90 kW

COP Tj = Tbiv

5.31

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.90 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.31

Rated airflow rate

0 m³/h

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

WTOL

65 °C

Poff

0 W

PTO

54 W

PSB

9 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

1.10 kW

Annual energy consumption Qhe

3254 kWh

Average Climate

EN 12102-1

Sound power level indoor

46 dB(A)

Sound power level outdoor

0 dB(A)

EN 14825

ηs

205 %

Prated

6.00 kW

SCOP

5.32

Tbiv

-10 °C

TOL

-10 °C

Pdh Tj = -7°C

5.80 kW

COP Tj = -7°C

4.87

Pdh Tj = +2°C

5.90 kW

COP Tj = +2°C

5.24

Pdh Tj = +7°C

6.00 kW

COP Tj = +7°C

5.61

Pdh Tj = 12°C

6.00 kW

COP Tj = 12°C

6.03

Pdh Tj = Tbiv

5.80 kW

COP Tj = Tbiv

4.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

Rated airflow rate

0 m³/h

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

WTOL

65 °C

Poff

0 W

PTO

54 W

PSB

9 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

2262 kWh

WPF 05 cool, average climates
Configure model
Model name
WPF 05 cool, average climates
Application
Heating (medium temp)
Units
Indoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5.82 kW

5.19 kW

El input

1.21 kW

1.85 kW

COP

4.80

2.81

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

46 dB(A)

46 dB(A)

Sound power level outdoor

0 dB(A)

0 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

205 %

134 %

Prated

6.00 kW

5.00 kW

SCOP

5.32

3.55

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.80 kW

5.30 kW

COP Tj = -7°C

4.87

2.94

Pdh Tj = +2°C

5.90 kW

5.50 kW

COP Tj = +2°C

5.24

3.49

Pdh Tj = +7°C

6.00 kW

5.60 kW

COP Tj = +7°C

5.61

3.92

Pdh Tj = 12°C

6.00 kW

5.70 kW

COP Tj = 12°C

6.03

4.44

Pdh Tj = Tbiv

5.80 kW

5.20 kW

COP Tj = Tbiv

4.81

2.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.80 kW

5.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

2.81

Rated airflow rate

0 m³/h

0 m³/h

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

54 W

54 W

PSB

9 W

9 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2262 kWh

3017 kWh

WPF 05 cool, all climates
Configure model
Model name
WPF 05 cool, all climates
Application
Heating (low temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

5.82 kW

El input

1.21 kW

COP

4.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Warmer Climate

EN 12102-1

Sound power level indoor

46 dB(A)

Sound power level outdoor

0 dB(A)

EN 14825

ηs

203 %

Prated

6.00 kW

SCOP

5.28

Tbiv

2 °C

TOL

0 °C

Pdh Tj = -7°C

0.00 kW

COP Tj = -7°C

0.00

Pdh Tj = +2°C

5.80 kW

COP Tj = +2°C

4.81

Cdh Tj = +2 °C

 

Pdh Tj = +7°C

5.90 kW

COP Tj = +7°C

5.16

Cdh Tj = +7 °C

 

Pdh Tj = 12°C

6.00 kW

COP Tj = 12°C

5.75

Cdh Tj = +12 °C

 

Pdh Tj = Tbiv

5.80 kW

COP Tj = Tbiv

4.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

Rated airflow rate

0 m³/h

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

WTOL

65 °C

Poff

0 W

PTO

54 W

PSB

9 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.20 kW

Annual energy consumption Qhe

1473 kWh

Colder Climate

EN 12102-1

Sound power level indoor

46 dB(A)

Sound power level outdoor

0 dB(A)

EN 14825

ηs

212 %

Prated

7.00 kW

SCOP

5.49

Tbiv

-15 °C

TOL

-22 °C

Pdh Tj = -7°C

5.90 kW

COP Tj = -7°C

5.43

Cdh Tj = -7 °C

 

Pdh Tj = +2°C

6.00 kW

COP Tj = +2°C

5.72

Cdh Tj = +2 °C

 

Pdh Tj = +7°C

6.00 kW

COP Tj = +7°C

5.97

Cdh Tj = +7 °C

 

Pdh Tj = 12°C

6.00 kW

COP Tj = 12°C

6.01

Cdh Tj = +12 °C

 

Pdh Tj = Tbiv

5.90 kW

COP Tj = Tbiv

5.31

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.90 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.31

Rated airflow rate

0 m³/h

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

WTOL

65 °C

Poff

0 W

PTO

54 W

PSB

9 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

1.10 kW

Annual energy consumption Qhe

3254 kWh

Average Climate

EN 12102-1

Sound power level indoor

46 dB(A)

Sound power level outdoor

0 dB(A)

EN 14825

ηs

205 %

Prated

6.00 kW

SCOP

5.32

Tbiv

-10 °C

TOL

-10 °C

Pdh Tj = -7°C

5.80 kW

COP Tj = -7°C

4.87

Pdh Tj = +2°C

5.90 kW

COP Tj = +2°C

5.24

Pdh Tj = +7°C

6.00 kW

COP Tj = +7°C

5.61

Pdh Tj = 12°C

6.00 kW

COP Tj = 12°C

6.03

Pdh Tj = Tbiv

5.80 kW

COP Tj = Tbiv

4.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

Rated airflow rate

0 m³/h

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

WTOL

65 °C

Poff

0 W

PTO

54 W

PSB

9 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

2262 kWh

WPC 05 cool, average climates
Configure model
Model name
WPC 05 cool, average climates
Application
Heating (medium temp)
Units
Indoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5.82 kW

5.19 kW

El input

1.21 kW

1.85 kW

COP

4.80

2.81

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

47 dB(A)

47 dB(A)

Sound power level outdoor

0 dB(A)

0 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

205 %

134 %

Prated

6.00 kW

5.00 kW

SCOP

5.32

3.55

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.80 kW

5.30 kW

COP Tj = -7°C

4.87

2.94

Pdh Tj = +2°C

5.90 kW

5.50 kW

COP Tj = +2°C

5.24

3.49

Pdh Tj = +7°C

6.00 kW

5.60 kW

COP Tj = +7°C

5.61

3.92

Pdh Tj = 12°C

6.00 kW

5.70 kW

COP Tj = 12°C

6.03

4.44

Pdh Tj = Tbiv

5.80 kW

5.20 kW

COP Tj = Tbiv

4.81

2.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.80 kW

5.20 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

2.81

Rated airflow rate

0 m³/h

0 m³/h

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

65 °C

65 °C

Poff

0 W

0 W

PTO

54 W

54 W

PSB

9 W

9 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2262 kWh

3017 kWh

WPC 05 cool, all climates
Configure model
Model name
WPC 05 cool, all climates
Application
Heating (low temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

5.82 kW

El input

1.21 kW

COP

4.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Warmer Climate

EN 12102-1

Sound power level indoor

47 dB(A)

Sound power level outdoor

0 dB(A)

EN 14825

ηs

203 %

Prated

6.00 kW

SCOP

5.28

Tbiv

2 °C

TOL

0 °C

Pdh Tj = -7°C

0.00 kW

COP Tj = -7°C

0.00

Pdh Tj = +2°C

5.80 kW

COP Tj = +2°C

4.81

Cdh Tj = +2 °C

 

Pdh Tj = +7°C

5.90 kW

COP Tj = +7°C

5.16

Cdh Tj = +7 °C

 

Pdh Tj = 12°C

6.00 kW

COP Tj = 12°C

5.75

Cdh Tj = +12 °C

 

Pdh Tj = Tbiv

5.80 kW

COP Tj = Tbiv

4.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

Rated airflow rate

0 m³/h

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

WTOL

65 °C

Poff

0 W

PTO

54 W

PSB

9 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.20 kW

Annual energy consumption Qhe

1473 kWh

Colder Climate

EN 12102-1

Sound power level indoor

47 dB(A)

Sound power level outdoor

0 dB(A)

EN 14825

ηs

212 %

Prated

7.00 kW

SCOP

5.49

Tbiv

-15 °C

TOL

-22 °C

Pdh Tj = -7°C

5.90 kW

COP Tj = -7°C

5.43

Cdh Tj = -7 °C

 

Pdh Tj = +2°C

6.00 kW

COP Tj = +2°C

5.72

Cdh Tj = +2 °C

 

Pdh Tj = +7°C

6.00 kW

COP Tj = +7°C

5.97

Cdh Tj = +7 °C

 

Pdh Tj = 12°C

6.00 kW

COP Tj = 12°C

6.01

Cdh Tj = +12 °C

 

Pdh Tj = Tbiv

5.90 kW

COP Tj = Tbiv

5.31

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.90 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.31

Rated airflow rate

0 m³/h

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

WTOL

65 °C

Poff

0 W

PTO

54 W

PSB

9 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

1.10 kW

Annual energy consumption Qhe

3254 kWh

Average Climate

EN 12102-1

Sound power level indoor

47 dB(A)

Sound power level outdoor

0 dB(A)

EN 14825

ηs

205 %

Prated

6.00 kW

SCOP

5.32

Tbiv

-10 °C

TOL

-10 °C

Pdh Tj = -7°C

5.80 kW

COP Tj = -7°C

4.87

Pdh Tj = +2°C

5.90 kW

COP Tj = +2°C

5.24

Pdh Tj = +7°C

6.00 kW

COP Tj = +7°C

5.61

Pdh Tj = 12°C

6.00 kW

COP Tj = 12°C

6.03

Pdh Tj = Tbiv

5.80 kW

COP Tj = Tbiv

4.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.81

Rated airflow rate

0 m³/h

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

WTOL

65 °C

Poff

0 W

PTO

54 W

PSB

9 W

PCK

0 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

2262 kWh