2,800 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
17.08 kW
15.81 kW
El input
3.95 kW
5.51 kW
COP
4.32
2.87
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
49 dB(A)
49 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
135 %
Prated
19 kW
18 kW
SCOP
4.66
3.58
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
17.14 kW
16 kW
COP Tj = -7°C
4.42
3.05
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
17.26 kW
16.4 kW
COP Tj = +2°C
4.65
3.54
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
17.35 kW
16.63 kW
COP Tj = +7°C
4.86
3.91
Cdh Tj = +7 °C
1.00
1.00
Pdh Tj = 12°C
17.43 kW
16.83 kW
COP Tj = 12°C
5.08
4.33
Cdh Tj = +12 °C
1.00
1.00
Pdh Tj = Tbiv
17.14 kW
16 kW
COP Tj = Tbiv
4.42
3.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
17.08 kW
15.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.32
2.87
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
62 °C
62 °C
Poff
6 W
6 W
PTO
6 W
6 W
PSB
6 W
6 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.92 kW
2.19 kW
Annual energy consumption Qhe
8417 kWh
10400 kWh