1,950 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.45 kW
6.79 kW
El input
1.66 kW
2.35 kW
COP
4.49
2.89
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
48 dB(A)
48 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
184 %
137 %
Prated
7 kW
8 kW
SCOP
4.81
3.64
Tbiv
-10 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
7.46 kW
6.91 kW
COP Tj = -7°C
4.54
3.09
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
7.53 kW
7.14 kW
COP Tj = +2°C
4.81
3.62
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
7.59 kW
7.27 kW
COP Tj = +7°C
5.07
4.02
Cdh Tj = +7 °C
1.00
1.00
Pdh Tj = 12°C
7.65 kW
7.38 kW
COP Tj = 12°C
5.36
4.47
Cdh Tj = +12 °C
1.00
1.00
Pdh Tj = Tbiv
7.45 kW
6.94 kW
COP Tj = Tbiv
4.49
3.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.45 kW
6.79 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.49
2.89
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
62 °C
62 °C
Poff
6 W
6 W
PTO
6 W
6 W
PSB
6 W
6 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
1.21 kW
Annual energy consumption Qhe
3007 kWh
4547 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
88 %
COP
2.13
Heating up time
1:16 h:min
Standby power input
33.9 W
Reference hot water temperature
44.6 °C
Mixed water at 40°C
181 l