2,100 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
11.00 kW
El input
2.38 kW
3.79 kW
COP
5.04
2.90
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
181 %
137 %
Prated
11.50 kW
12.00 kW
SCOP
4.60
3.50
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.20 kW
10.20 kW
COP Tj = -7°C
3.01
2.20
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.20 kW
6.30 kW
COP Tj = +2°C
4.42
3.38
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.50 kW
4.60 kW
COP Tj = +7°C
6.04
4.67
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
5.00 kW
4.60 kW
COP Tj = 12°C
8.44
6.66
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
11.50 kW
10.20 kW
COP Tj = Tbiv
2.65
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.50 kW
10.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.65
1.92
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
65 °C
65 °C
Poff
60 W
60 W
PTO
60 W
60 W
PSB
60 W
60 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
Electricity
Supplementary Heater: PSUP
0.00 kW
1.20 kW
Annual energy consumption Qhe
5165 kWh
6788 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
11.00 kW
El input
2.38 kW
3.79 kW
COP
5.04
2.90
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
181 %
137 %
Prated
11.50 kW
12.00 kW
SCOP
4.60
3.50
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.20 kW
10.20 kW
COP Tj = -7°C
3.01
2.20
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.20 kW
6.30 kW
COP Tj = +2°C
4.42
3.38
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.50 kW
4.60 kW
COP Tj = +7°C
6.04
4.67
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
5.00 kW
4.60 kW
COP Tj = 12°C
8.44
6.66
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
11.50 kW
10.20 kW
COP Tj = Tbiv
2.65
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.50 kW
10.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.65
1.92
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
65 °C
65 °C
Poff
60 W
60 W
PTO
60 W
60 W
PSB
60 W
60 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
Electricity
Supplementary Heater: PSUP
0.00 kW
1.20 kW
Annual energy consumption Qhe
5165 kWh
6788 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.00 kW
11.50 kW
El input
2.86 kW
4.04 kW
COP
4.89
2.85
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
136 %
Prated
12.00 kW
12.00 kW
SCOP
4.57
3.47
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.60 kW
10.40 kW
COP Tj = -7°C
2.94
2.16
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
6.50 kW
6.30 kW
COP Tj = +2°C
4.45
3.35
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
4.70 kW
4.70 kW
COP Tj = +7°C
5.95
4.66
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
5.00 kW
4.60 kW
COP Tj = 12°C
8.12
6.62
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
12.00 kW
10.40 kW
COP Tj = Tbiv
2.60
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.00 kW
10.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.86
WTOL
65 °C
65 °C
Poff
60 W
60 W
PTO
60 W
60 W
PSB
60 W
60 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
Electricity
Supplementary Heater: PSUP
0.00 kW
1.10 kW
Annual energy consumption Qhe
5425 kWh
6992 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.00 kW
11.50 kW
El input
2.86 kW
4.04 kW
COP
4.89
2.85
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
136 %
Prated
12.00 kW
12.00 kW
SCOP
4.57
3.47
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.60 kW
10.40 kW
COP Tj = -7°C
2.94
2.16
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
6.50 kW
6.30 kW
COP Tj = +2°C
4.45
3.35
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
4.70 kW
4.70 kW
COP Tj = +7°C
5.95
4.66
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
5.00 kW
4.60 kW
COP Tj = 12°C
8.12
6.62
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
12.00 kW
10.40 kW
COP Tj = Tbiv
2.60
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.00 kW
10.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.86
WTOL
65 °C
65 °C
Poff
60 W
60 W
PTO
60 W
60 W
PSB
60 W
60 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
Electricity
Supplementary Heater: PSUP
0.00 kW
1.10 kW
Annual energy consumption Qhe
5425 kWh
6992 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
12.00 kW
El input
3.33 kW
4.29 kW
COP
4.80
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
135 %
Prated
12.00 kW
12.00 kW
SCOP
4.55
3.45
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.90 kW
10.60 kW
COP Tj = -7°C
2.88
2.15
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
6.70 kW
6.50 kW
COP Tj = +2°C
4.45
3.34
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
5.00 kW
5.20 kW
COP Tj = +7°C
5.97
4.65
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
5.30 kW
4.60 kW
COP Tj = 12°C
8.11
6.58
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
12.30 kW
10.60 kW
COP Tj = Tbiv
2.56
2.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.30 kW
11.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.85
WTOL
65 °C
65 °C
Poff
60 W
60 W
PTO
60 W
60 W
PSB
60 W
60 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
Electricity
Supplementary Heater: PSUP
0.00 kW
0.90 kW
Annual energy consumption Qhe
5586 kWh
7187 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
12.00 kW
El input
3.33 kW
4.29 kW
COP
4.80
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
135 %
Prated
12.00 kW
12.00 kW
SCOP
4.55
3.45
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.90 kW
10.60 kW
COP Tj = -7°C
2.88
2.15
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
6.70 kW
6.50 kW
COP Tj = +2°C
4.45
3.34
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
5.00 kW
5.20 kW
COP Tj = +7°C
5.97
4.65
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
5.30 kW
4.60 kW
COP Tj = 12°C
8.11
6.58
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
12.30 kW
10.60 kW
COP Tj = Tbiv
2.56
2.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.30 kW
11.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.85
WTOL
65 °C
65 °C
Poff
60 W
60 W
PTO
60 W
60 W
PSB
60 W
60 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
Electricity
Supplementary Heater: PSUP
0.00 kW
0.90 kW
Annual energy consumption Qhe
5586 kWh
7187 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
11.00 kW
El input
2.38 kW
3.79 kW
COP
5.04
2.90
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
181 %
137 %
Prated
11.50 kW
12.00 kW
SCOP
4.60
3.50
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.20 kW
10.20 kW
COP Tj = -7°C
3.01
2.20
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.20 kW
6.30 kW
COP Tj = +2°C
4.42
3.38
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.50 kW
4.60 kW
COP Tj = +7°C
6.04
4.67
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
5.00 kW
4.60 kW
COP Tj = 12°C
8.44
6.66
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
11.50 kW
10.20 kW
COP Tj = Tbiv
2.65
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.50 kW
10.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.65
1.92
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
65 °C
65 °C
Poff
60 W
60 W
PTO
60 W
60 W
PSB
60 W
60 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
Electricity
Supplementary Heater: PSUP
0.00 kW
1.20 kW
Annual energy consumption Qhe
5165 kWh
6788 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
11.00 kW
El input
2.38 kW
3.79 kW
COP
5.04
2.90
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
181 %
137 %
Prated
11.50 kW
12.00 kW
SCOP
4.60
3.50
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.20 kW
10.20 kW
COP Tj = -7°C
3.01
2.20
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
6.20 kW
6.30 kW
COP Tj = +2°C
4.42
3.38
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
4.50 kW
4.60 kW
COP Tj = +7°C
6.04
4.67
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
5.00 kW
4.60 kW
COP Tj = 12°C
8.44
6.66
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
11.50 kW
10.20 kW
COP Tj = Tbiv
2.65
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.50 kW
10.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.65
1.92
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
65 °C
65 °C
Poff
60 W
60 W
PTO
60 W
60 W
PSB
60 W
60 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
Electricity
Supplementary Heater: PSUP
0.00 kW
1.20 kW
Annual energy consumption Qhe
5165 kWh
6788 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.00 kW
11.50 kW
El input
2.86 kW
4.04 kW
COP
4.89
2.85
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
136 %
Prated
12.00 kW
12.00 kW
SCOP
4.57
3.47
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.60 kW
10.40 kW
COP Tj = -7°C
2.94
2.16
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
6.50 kW
6.30 kW
COP Tj = +2°C
4.45
3.35
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
4.70 kW
4.70 kW
COP Tj = +7°C
5.95
4.66
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
5.00 kW
4.60 kW
COP Tj = 12°C
8.12
6.62
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
12.00 kW
10.40 kW
COP Tj = Tbiv
2.60
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.00 kW
10.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.86
WTOL
65 °C
65 °C
Poff
60 W
60 W
PTO
60 W
60 W
PSB
60 W
60 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
Electricity
Supplementary Heater: PSUP
0.00 kW
1.10 kW
Annual energy consumption Qhe
5425 kWh
6992 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
14.00 kW
11.50 kW
El input
2.86 kW
4.04 kW
COP
4.89
2.85
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
62 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
136 %
Prated
12.00 kW
12.00 kW
SCOP
4.57
3.47
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.60 kW
10.40 kW
COP Tj = -7°C
2.94
2.16
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
6.50 kW
6.30 kW
COP Tj = +2°C
4.45
3.35
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
4.70 kW
4.70 kW
COP Tj = +7°C
5.95
4.66
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
5.00 kW
4.60 kW
COP Tj = 12°C
8.12
6.62
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
12.00 kW
10.40 kW
COP Tj = Tbiv
2.60
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.00 kW
10.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.86
WTOL
65 °C
65 °C
Poff
60 W
60 W
PTO
60 W
60 W
PSB
60 W
60 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
Electricity
Supplementary Heater: PSUP
0.00 kW
1.10 kW
Annual energy consumption Qhe
5425 kWh
6992 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
12.00 kW
El input
3.33 kW
4.29 kW
COP
4.80
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
135 %
Prated
12.00 kW
12.00 kW
SCOP
4.55
3.45
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.90 kW
10.60 kW
COP Tj = -7°C
2.88
2.15
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
6.70 kW
6.50 kW
COP Tj = +2°C
4.45
3.34
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
5.00 kW
5.20 kW
COP Tj = +7°C
5.97
4.65
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
5.30 kW
4.60 kW
COP Tj = 12°C
8.11
6.58
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
12.30 kW
10.60 kW
COP Tj = Tbiv
2.56
2.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.30 kW
11.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.85
WTOL
65 °C
65 °C
Poff
60 W
60 W
PTO
60 W
60 W
PSB
60 W
60 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
Electricity
Supplementary Heater: PSUP
0.00 kW
0.90 kW
Annual energy consumption Qhe
5586 kWh
7187 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
12.00 kW
El input
3.33 kW
4.29 kW
COP
4.80
2.80
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
44 dB(A)
44 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
179 %
135 %
Prated
12.00 kW
12.00 kW
SCOP
4.55
3.45
Tbiv
-10 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.90 kW
10.60 kW
COP Tj = -7°C
2.88
2.15
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
6.70 kW
6.50 kW
COP Tj = +2°C
4.45
3.34
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
5.00 kW
5.20 kW
COP Tj = +7°C
5.97
4.65
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
5.30 kW
4.60 kW
COP Tj = 12°C
8.11
6.58
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
12.30 kW
10.60 kW
COP Tj = Tbiv
2.56
2.15
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.30 kW
11.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.85
WTOL
65 °C
65 °C
Poff
60 W
60 W
PTO
60 W
60 W
PSB
60 W
60 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
Electricity
Supplementary Heater: PSUP
0.00 kW
0.90 kW
Annual energy consumption Qhe
5586 kWh
7187 kWh