7,900 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
25.38 kW
23.06 kW
El input
5.81 kW
9.04 kW
COP
4.37
2.55
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
212 %
153 %
Prated
20.75 kW
15.97 kW
SCOP
5.39
3.91
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
20.75 kW
15.97 kW
COP Tj = +2°C
3.37
2.08
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
13.85 kW
11.18 kW
COP Tj = +7°C
4.99
3.49
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
14.21 kW
13.51 kW
COP Tj = 12°C
6.72
5.3
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
20.75 kW
15.97 kW
COP Tj = Tbiv
3.37
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
20.75 kW
15.97 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.37
2.08
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
5147 kWh
5462 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
144 %
106 %
Prated
16.55 kW
17.13 kW
SCOP
3.67
2.73
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
10.54 kW
10.18 kW
COP Tj = -7°C
2.8
2.16
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
10.53 kW
10.09 kW
COP Tj = +2°C
5.01
3.91
Cdh Tj = +2 °C
0.96
0.96
Pdh Tj = +7°C
12.39 kW
11.93 kW
COP Tj = +7°C
5.98
4.95
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
14.3 kW
13.93 kW
COP Tj = 12°C
6.93
6.17
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
13.5 kW
12.62 kW
COP Tj = Tbiv
2.32
1.6
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.14 kW
11.35 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.78
1.45
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
16.55 kW
17.13 kW
Annual energy consumption Qhe
11102 kWh
15484 kWh
Pdh Tj = -15°C (if TOL<-20°C)
11.14
11.35
COP Tj = -15°C (if TOL<-20°C)
1.78
1.45
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
173 %
127 %
Prated
19.42 kW
16.78 kW
SCOP
4.41
3.24
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
17.18 kW
13.04 kW
COP Tj = -7°C
2.63
1.93
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
11.61 kW
9.50 kW
COP Tj = +2°C
4.63
3.25
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
12.42 kW
11.10 kW
COP Tj = +7°C
5.49
4.40
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
14.75 kW
13.45 kW
COP Tj = 12°C
6.87
6.15
Cdh Tj = +12 °C
0.98
0.98
Pdh Tj = Tbiv
17.18 kW
14.20 kW
COP Tj = Tbiv
2.63
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
16.67 kW
9.15 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.55
1.35
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.76 kW
7.63 kW
Annual energy consumption Qhe
9104 kWh
10709 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
25.38 kW
23.06 kW
El input
5.81 kW
9.04 kW
COP
4.37
2.55
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
212 %
153 %
Prated
20.75 kW
15.97 kW
SCOP
5.39
3.91
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
20.75 kW
15.97 kW
COP Tj = +2°C
3.37
2.08
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
13.85 kW
11.18 kW
COP Tj = +7°C
4.99
3.49
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
14.21 kW
13.51 kW
COP Tj = 12°C
6.72
5.3
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
20.75 kW
15.97 kW
COP Tj = Tbiv
3.37
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
20.75 kW
15.97 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.37
2.08
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
5147 kWh
5462 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
144 %
106 %
Prated
16.55 kW
17.13 kW
SCOP
3.67
2.73
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
10.54 kW
10.18 kW
COP Tj = -7°C
2.8
2.16
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
10.53 kW
10.09 kW
COP Tj = +2°C
5.01
3.91
Cdh Tj = +2 °C
0.96
0.96
Pdh Tj = +7°C
12.39 kW
11.93 kW
COP Tj = +7°C
5.98
4.95
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
14.3 kW
13.93 kW
COP Tj = 12°C
6.93
6.17
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
13.5 kW
12.62 kW
COP Tj = Tbiv
2.32
1.6
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.14 kW
11.35 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.78
1.45
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
16.55 kW
17.13 kW
Annual energy consumption Qhe
11102 kWh
15484 kWh
Pdh Tj = -15°C (if TOL<-20°C)
11.14
11.35
COP Tj = -15°C (if TOL<-20°C)
1.78
1.45
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
173 %
127 %
Prated
19.42 kW
16.78 kW
SCOP
4.41
3.24
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
17.18 kW
13.04 kW
COP Tj = -7°C
2.63
1.93
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
11.61 kW
9.50 kW
COP Tj = +2°C
4.63
3.25
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
12.42 kW
11.10 kW
COP Tj = +7°C
5.49
4.40
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
14.75 kW
13.45 kW
COP Tj = 12°C
6.87
6.15
Cdh Tj = +12 °C
0.98
0.98
Pdh Tj = Tbiv
17.18 kW
14.20 kW
COP Tj = Tbiv
2.63
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
16.67 kW
9.15 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.55
1.35
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.76 kW
7.63 kW
Annual energy consumption Qhe
9104 kWh
10709 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
25.38 kW
23.06 kW
El input
5.81 kW
9.04 kW
COP
4.37
2.55
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
212 %
153 %
Prated
20.75 kW
15.97 kW
SCOP
5.39
3.91
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
20.75 kW
15.97 kW
COP Tj = +2°C
3.37
2.08
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
13.85 kW
11.18 kW
COP Tj = +7°C
4.99
3.49
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
14.21 kW
13.51 kW
COP Tj = 12°C
6.72
5.3
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
20.75 kW
15.97 kW
COP Tj = Tbiv
3.37
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
20.75 kW
15.97 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.37
2.08
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
5147 kWh
5462 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
144 %
106 %
Prated
16.55 kW
17.13 kW
SCOP
3.67
2.73
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
10.54 kW
10.18 kW
COP Tj = -7°C
2.8
2.16
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
10.53 kW
10.09 kW
COP Tj = +2°C
5.01
3.91
Cdh Tj = +2 °C
0.96
0.96
Pdh Tj = +7°C
12.39 kW
11.93 kW
COP Tj = +7°C
5.98
4.95
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
14.3 kW
13.93 kW
COP Tj = 12°C
6.93
6.17
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
13.5 kW
12.62 kW
COP Tj = Tbiv
2.32
1.6
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.14 kW
11.35 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.78
1.45
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
16.55 kW
17.13 kW
Annual energy consumption Qhe
11102 kWh
15484 kWh
Pdh Tj = -15°C (if TOL<-20°C)
11.14
11.35
COP Tj = -15°C (if TOL<-20°C)
1.78
1.45
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
173 %
127 %
Prated
19.42 kW
16.78 kW
SCOP
4.41
3.24
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
17.18 kW
13.04 kW
COP Tj = -7°C
2.63
1.93
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
11.61 kW
9.50 kW
COP Tj = +2°C
4.63
3.25
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
12.42 kW
11.10 kW
COP Tj = +7°C
5.49
4.40
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
14.75 kW
13.45 kW
COP Tj = 12°C
6.87
6.15
Cdh Tj = +12 °C
0.98
0.98
Pdh Tj = Tbiv
17.18 kW
14.20 kW
COP Tj = Tbiv
2.63
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
16.67 kW
9.15 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.55
1.35
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.76 kW
7.63 kW
Annual energy consumption Qhe
9104 kWh
10709 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
25.38 kW
23.06 kW
El input
5.81 kW
9.04 kW
COP
4.37
2.55
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
212 %
153 %
Prated
20.75 kW
15.97 kW
SCOP
5.39
3.91
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
20.75 kW
15.97 kW
COP Tj = +2°C
3.37
2.08
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
13.85 kW
11.18 kW
COP Tj = +7°C
4.99
3.49
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
14.21 kW
13.51 kW
COP Tj = 12°C
6.72
5.3
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
20.75 kW
15.97 kW
COP Tj = Tbiv
3.37
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
20.75 kW
15.97 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.37
2.08
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
5147 kWh
5462 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
144 %
106 %
Prated
16.55 kW
17.13 kW
SCOP
3.67
2.73
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
10.54 kW
10.18 kW
COP Tj = -7°C
2.8
2.16
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
10.53 kW
10.09 kW
COP Tj = +2°C
5.01
3.91
Cdh Tj = +2 °C
0.96
0.96
Pdh Tj = +7°C
12.39 kW
11.93 kW
COP Tj = +7°C
5.98
4.95
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
14.3 kW
13.93 kW
COP Tj = 12°C
6.93
6.17
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
13.5 kW
12.62 kW
COP Tj = Tbiv
2.32
1.6
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.14 kW
11.35 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.78
1.45
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
16.55 kW
17.13 kW
Annual energy consumption Qhe
11102 kWh
15484 kWh
Pdh Tj = -15°C (if TOL<-20°C)
11.14
11.35
COP Tj = -15°C (if TOL<-20°C)
1.78
1.45
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
173 %
127 %
Prated
19.42 kW
16.78 kW
SCOP
4.41
3.24
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
17.18 kW
13.04 kW
COP Tj = -7°C
2.63
1.93
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
11.61 kW
9.50 kW
COP Tj = +2°C
4.63
3.25
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
12.42 kW
11.10 kW
COP Tj = +7°C
5.49
4.40
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
14.75 kW
13.45 kW
COP Tj = 12°C
6.87
6.15
Cdh Tj = +12 °C
0.98
0.98
Pdh Tj = Tbiv
17.18 kW
14.20 kW
COP Tj = Tbiv
2.63
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
16.67 kW
9.15 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.55
1.35
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.76 kW
7.63 kW
Annual energy consumption Qhe
9104 kWh
10709 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
30 kW
27.7 kW
El input
6.88 kW
11.49 kW
COP
4.36
2.41
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
210 %
154 %
Prated
24.4 kW
17.75 kW
SCOP
5.33
3.92
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
24.4 kW
17.75 kW
COP Tj = +2°C
3.28
2.04
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
16.03 kW
11.18 kW
COP Tj = +7°C
4.83
3.49
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
14.26 kW
13.5 kW
COP Tj = 12°C
6.67
5.28
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
24.4 kW
17.75 kW
COP Tj = Tbiv
3.28
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
24.4 kW
17.75 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.28
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
6120 kWh
6042 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
143 %
106 %
Prated
18.75 kW
19.01 kW
SCOP
3.65
2.73
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
10.57 kW
11.35 kW
COP Tj = -7°C
2.78
2.14
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
10.56 kW
10.09 kW
COP Tj = +2°C
4.94
3.91
Cdh Tj = +2 °C
0.96
0.96
Pdh Tj = +7°C
12.43 kW
11.93 kW
COP Tj = +7°C
5.9
4.95
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
14.34 kW
13.93 kW
COP Tj = 12°C
6.87
6.17
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
15.3 kW
14.01 kW
COP Tj = Tbiv
2.28
1.58
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.17 kW
13.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.76
1.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
18.75 kW
19.01 kW
Annual energy consumption Qhe
12674 kWh
17151 kWh
Pdh Tj = -15°C (if TOL<-20°C)
12.17
13.07
COP Tj = -15°C (if TOL<-20°C)
1.76
1.49
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
172 %
126 %
Prated
22.5 kW
19.53 kW
SCOP
4.36
3.22
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
19.90 kW
15.95 kW
COP Tj = -7°C
2.60
1.94
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
12.43 kW
10.80 kW
COP Tj = +2°C
4.52
3.20
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
12.42 kW
11.47 kW
COP Tj = +7°C
5.46
4.41
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
14.76 kW
13.80 kW
COP Tj = 12°C
6.85
6.14
Cdh Tj = +12 °C
0.98
0.98
Pdh Tj = Tbiv
19.90 kW
16.52 kW
COP Tj = Tbiv
2.60
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
17.28 kW
10.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.30
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.21 kW
9.53 kW
Annual energy consumption Qhe
10646 kWh
12512 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
30 kW
27.7 kW
El input
6.88 kW
11.49 kW
COP
4.36
2.41
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
210 %
154 %
Prated
24.4 kW
17.75 kW
SCOP
5.33
3.92
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
24.4 kW
17.75 kW
COP Tj = +2°C
3.28
2.04
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
16.03 kW
11.18 kW
COP Tj = +7°C
4.83
3.49
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
14.26 kW
13.5 kW
COP Tj = 12°C
6.67
5.28
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
24.4 kW
17.75 kW
COP Tj = Tbiv
3.28
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
24.4 kW
17.75 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.28
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
6120 kWh
6042 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
143 %
106 %
Prated
18.75 kW
19.01 kW
SCOP
3.65
2.73
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
10.57 kW
11.35 kW
COP Tj = -7°C
2.78
2.14
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
10.56 kW
10.09 kW
COP Tj = +2°C
4.94
3.91
Cdh Tj = +2 °C
0.96
0.96
Pdh Tj = +7°C
12.43 kW
11.93 kW
COP Tj = +7°C
5.9
4.95
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
14.34 kW
13.93 kW
COP Tj = 12°C
6.87
6.17
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
15.3 kW
14.01 kW
COP Tj = Tbiv
2.28
1.58
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.17 kW
13.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.76
1.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
18.75 kW
19.01 kW
Annual energy consumption Qhe
12674 kWh
17151 kWh
Pdh Tj = -15°C (if TOL<-20°C)
12.17
13.07
COP Tj = -15°C (if TOL<-20°C)
1.76
1.49
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
172 %
126 %
Prated
22.5 kW
19.53 kW
SCOP
4.36
3.22
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
19.90 kW
15.95 kW
COP Tj = -7°C
2.60
1.94
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
12.43 kW
10.80 kW
COP Tj = +2°C
4.52
3.20
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
12.42 kW
11.47 kW
COP Tj = +7°C
5.46
4.41
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
14.76 kW
13.80 kW
COP Tj = 12°C
6.85
6.14
Cdh Tj = +12 °C
0.98
0.98
Pdh Tj = Tbiv
19.90 kW
16.52 kW
COP Tj = Tbiv
2.60
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
17.28 kW
10.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.30
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.21 kW
9.53 kW
Annual energy consumption Qhe
10646 kWh
12512 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
30 kW
27.7 kW
El input
6.88 kW
11.49 kW
COP
4.36
2.41
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
210 %
154 %
Prated
24.4 kW
17.75 kW
SCOP
5.33
3.92
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
24.4 kW
17.75 kW
COP Tj = +2°C
3.28
2.04
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
16.03 kW
11.18 kW
COP Tj = +7°C
4.83
3.49
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
14.26 kW
13.5 kW
COP Tj = 12°C
6.67
5.28
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
24.4 kW
17.75 kW
COP Tj = Tbiv
3.28
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
24.4 kW
17.75 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.28
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
6120 kWh
6042 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
143 %
106 %
Prated
18.75 kW
19.01 kW
SCOP
3.65
2.73
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
10.57 kW
11.35 kW
COP Tj = -7°C
2.78
2.14
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
10.56 kW
10.09 kW
COP Tj = +2°C
4.94
3.91
Cdh Tj = +2 °C
0.96
0.96
Pdh Tj = +7°C
12.43 kW
11.93 kW
COP Tj = +7°C
5.9
4.95
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
14.34 kW
13.93 kW
COP Tj = 12°C
6.87
6.17
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
15.3 kW
14.01 kW
COP Tj = Tbiv
2.28
1.58
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.17 kW
13.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.76
1.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
18.75 kW
19.01 kW
Annual energy consumption Qhe
12674 kWh
17151 kWh
Pdh Tj = -15°C (if TOL<-20°C)
12.17
13.07
COP Tj = -15°C (if TOL<-20°C)
1.76
1.49
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
172 %
126 %
Prated
22.5 kW
19.53 kW
SCOP
4.36
3.22
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
19.90 kW
15.95 kW
COP Tj = -7°C
2.60
1.94
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
12.43 kW
10.80 kW
COP Tj = +2°C
4.52
3.20
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
12.42 kW
11.47 kW
COP Tj = +7°C
5.46
4.41
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
14.76 kW
13.80 kW
COP Tj = 12°C
6.85
6.14
Cdh Tj = +12 °C
0.98
0.98
Pdh Tj = Tbiv
19.90 kW
16.52 kW
COP Tj = Tbiv
2.60
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
17.28 kW
10.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.30
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.21 kW
9.53 kW
Annual energy consumption Qhe
10646 kWh
12512 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
30 kW
27.7 kW
El input
6.88 kW
11.49 kW
COP
4.36
2.41
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
210 %
154 %
Prated
24.4 kW
17.75 kW
SCOP
5.33
3.92
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
24.4 kW
17.75 kW
COP Tj = +2°C
3.28
2.04
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
16.03 kW
11.18 kW
COP Tj = +7°C
4.83
3.49
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
14.26 kW
13.5 kW
COP Tj = 12°C
6.67
5.28
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
24.4 kW
17.75 kW
COP Tj = Tbiv
3.28
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
24.4 kW
17.75 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.28
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
6120 kWh
6042 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
143 %
106 %
Prated
18.75 kW
19.01 kW
SCOP
3.65
2.73
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
10.57 kW
11.35 kW
COP Tj = -7°C
2.78
2.14
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
10.56 kW
10.09 kW
COP Tj = +2°C
4.94
3.91
Cdh Tj = +2 °C
0.96
0.96
Pdh Tj = +7°C
12.43 kW
11.93 kW
COP Tj = +7°C
5.9
4.95
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
14.34 kW
13.93 kW
COP Tj = 12°C
6.87
6.17
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
15.3 kW
14.01 kW
COP Tj = Tbiv
2.28
1.58
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.17 kW
13.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.76
1.49
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
18.75 kW
19.01 kW
Annual energy consumption Qhe
12674 kWh
17151 kWh
Pdh Tj = -15°C (if TOL<-20°C)
12.17
13.07
COP Tj = -15°C (if TOL<-20°C)
1.76
1.49
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
172 %
126 %
Prated
22.5 kW
19.53 kW
SCOP
4.36
3.22
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
19.90 kW
15.95 kW
COP Tj = -7°C
2.60
1.94
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
12.43 kW
10.80 kW
COP Tj = +2°C
4.52
3.20
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
12.42 kW
11.47 kW
COP Tj = +7°C
5.46
4.41
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
14.76 kW
13.80 kW
COP Tj = 12°C
6.85
6.14
Cdh Tj = +12 °C
0.98
0.98
Pdh Tj = Tbiv
19.90 kW
16.52 kW
COP Tj = Tbiv
2.60
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
17.28 kW
10.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.30
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
5.21 kW
9.53 kW
Annual energy consumption Qhe
10646 kWh
12512 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
35.78 kW
32.64 kW
El input
8.75 kW
14.01 kW
COP
4.09
2.33
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
199 %
155 %
Prated
27.9 kW
19.9 kW
SCOP
5.05
3.95
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
27.9 kW
19.9 kW
COP Tj = +2°C
3.08
2.04
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
19.1 kW
12.4 kW
COP Tj = +7°C
4.41
3.48
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
14.34 kW
13.52 kW
COP Tj = 12°C
6.48
5.29
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
27.9 kW
19.9 kW
COP Tj = Tbiv
3.08
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
27.9 kW
19.9 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.08
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
7376 kWh
6734 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
140 %
106 %
Prated
21.57 kW
20.72 kW
SCOP
3.57
2.73
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-15 °C
Pdh Tj = -7°C
11.9 kW
12.58 kW
COP Tj = -7°C
2.7
2.12
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
10.64 kW
10.1 kW
COP Tj = +2°C
4.78
3.9
Cdh Tj = +2 °C
0.96
0.96
Pdh Tj = +7°C
12.5 kW
11.95 kW
COP Tj = +7°C
5.72
4.96
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
14.42 kW
13.93 kW
COP Tj = 12°C
6.69
6.17
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
17.6 kW
15.27 kW
COP Tj = Tbiv
2.22
1.59
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.8 kW
13.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.84
1.47
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
21.57 kW
20.72 kW
Annual energy consumption Qhe
14915 kWh
18714 kWh
Pdh Tj = -15°C (if TOL<-20°C)
13.8
13.86
COP Tj = -15°C (if TOL<-20°C)
1.84
1.47
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
169 %
124 %
Prated
25.5 kW
22.97 kW
SCOP
4.31
3.18
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
22.60 kW
18.82 kW
COP Tj = -7°C
2.60
1.89
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
13.25 kW
12.44 kW
COP Tj = +2°C
4.41
3.15
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
12.44 kW
11.48 kW
COP Tj = +7°C
5.44
4.40
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
14.77 kW
13.82 kW
COP Tj = 12°C
6.83
6.12
Cdh Tj = +12 °C
0.98
0.98
Pdh Tj = Tbiv
22.60 kW
19.44 kW
COP Tj = Tbiv
2.60
1.96
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
18.38 kW
11.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.25
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.17 kW
11.97 kW
Annual energy consumption Qhe
12250 kWh
14935 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
35.78 kW
32.64 kW
El input
8.75 kW
14.01 kW
COP
4.09
2.33
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
199 %
155 %
Prated
27.9 kW
19.9 kW
SCOP
5.05
3.95
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
27.9 kW
19.9 kW
COP Tj = +2°C
3.08
2.04
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
19.1 kW
12.4 kW
COP Tj = +7°C
4.41
3.48
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
14.34 kW
13.52 kW
COP Tj = 12°C
6.48
5.29
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
27.9 kW
19.9 kW
COP Tj = Tbiv
3.08
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
27.9 kW
19.9 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.08
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
7376 kWh
6734 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
140 %
106 %
Prated
21.57 kW
20.72 kW
SCOP
3.57
2.73
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-15 °C
Pdh Tj = -7°C
11.9 kW
12.58 kW
COP Tj = -7°C
2.7
2.12
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
10.64 kW
10.1 kW
COP Tj = +2°C
4.78
3.9
Cdh Tj = +2 °C
0.96
0.96
Pdh Tj = +7°C
12.5 kW
11.95 kW
COP Tj = +7°C
5.72
4.96
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
14.42 kW
13.93 kW
COP Tj = 12°C
6.69
6.17
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
17.6 kW
15.27 kW
COP Tj = Tbiv
2.22
1.59
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.8 kW
13.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.84
1.47
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
21.57 kW
20.72 kW
Annual energy consumption Qhe
14915 kWh
18714 kWh
Pdh Tj = -15°C (if TOL<-20°C)
13.8
13.86
COP Tj = -15°C (if TOL<-20°C)
1.84
1.47
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
169 %
124 %
Prated
25.5 kW
22.97 kW
SCOP
4.31
3.18
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
22.60 kW
18.82 kW
COP Tj = -7°C
2.60
1.89
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
13.25 kW
12.44 kW
COP Tj = +2°C
4.41
3.15
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
12.44 kW
11.48 kW
COP Tj = +7°C
5.44
4.40
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
14.77 kW
13.82 kW
COP Tj = 12°C
6.83
6.12
Cdh Tj = +12 °C
0.98
0.98
Pdh Tj = Tbiv
22.60 kW
19.44 kW
COP Tj = Tbiv
2.60
1.96
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
18.38 kW
11.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.25
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.17 kW
11.97 kW
Annual energy consumption Qhe
12250 kWh
14935 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
35.78 kW
32.64 kW
El input
8.75 kW
14.01 kW
COP
4.09
2.33
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
199 %
155 %
Prated
27.9 kW
19.9 kW
SCOP
5.05
3.95
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
27.9 kW
19.9 kW
COP Tj = +2°C
3.08
2.04
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
19.1 kW
12.4 kW
COP Tj = +7°C
4.41
3.48
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
14.34 kW
13.52 kW
COP Tj = 12°C
6.48
5.29
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
27.9 kW
19.9 kW
COP Tj = Tbiv
3.08
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
27.9 kW
19.9 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.08
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
7376 kWh
6734 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
140 %
106 %
Prated
21.57 kW
20.72 kW
SCOP
3.57
2.73
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-15 °C
Pdh Tj = -7°C
11.9 kW
12.58 kW
COP Tj = -7°C
2.7
2.12
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
10.64 kW
10.1 kW
COP Tj = +2°C
4.78
3.9
Cdh Tj = +2 °C
0.96
0.96
Pdh Tj = +7°C
12.5 kW
11.95 kW
COP Tj = +7°C
5.72
4.96
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
14.42 kW
13.93 kW
COP Tj = 12°C
6.69
6.17
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
17.6 kW
15.27 kW
COP Tj = Tbiv
2.22
1.59
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.8 kW
13.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.84
1.47
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
21.57 kW
20.72 kW
Annual energy consumption Qhe
14915 kWh
18714 kWh
Pdh Tj = -15°C (if TOL<-20°C)
13.8
13.86
COP Tj = -15°C (if TOL<-20°C)
1.84
1.47
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
169 %
124 %
Prated
25.5 kW
22.97 kW
SCOP
4.31
3.18
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
22.60 kW
18.82 kW
COP Tj = -7°C
2.60
1.89
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
13.25 kW
12.44 kW
COP Tj = +2°C
4.41
3.15
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
12.44 kW
11.48 kW
COP Tj = +7°C
5.44
4.40
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
14.77 kW
13.82 kW
COP Tj = 12°C
6.83
6.12
Cdh Tj = +12 °C
0.98
0.98
Pdh Tj = Tbiv
22.60 kW
19.44 kW
COP Tj = Tbiv
2.60
1.96
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
18.38 kW
11.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.25
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.17 kW
11.97 kW
Annual energy consumption Qhe
12250 kWh
14935 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
35.78 kW
32.64 kW
El input
8.75 kW
14.01 kW
COP
4.09
2.33
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
199 %
155 %
Prated
27.9 kW
19.9 kW
SCOP
5.05
3.95
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
27.9 kW
19.9 kW
COP Tj = +2°C
3.08
2.04
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
19.1 kW
12.4 kW
COP Tj = +7°C
4.41
3.48
Cdh Tj = +7 °C
0.9
0.9
Pdh Tj = 12°C
14.34 kW
13.52 kW
COP Tj = 12°C
6.48
5.29
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
27.9 kW
19.9 kW
COP Tj = Tbiv
3.08
2.04
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
27.9 kW
19.9 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.08
2.04
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
7376 kWh
6734 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
140 %
106 %
Prated
21.57 kW
20.72 kW
SCOP
3.57
2.73
Tbiv
-15 °C
-12 °C
TOL
-20 °C
-15 °C
Pdh Tj = -7°C
11.9 kW
12.58 kW
COP Tj = -7°C
2.7
2.12
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
10.64 kW
10.1 kW
COP Tj = +2°C
4.78
3.9
Cdh Tj = +2 °C
0.96
0.96
Pdh Tj = +7°C
12.5 kW
11.95 kW
COP Tj = +7°C
5.72
4.96
Cdh Tj = +7 °C
0.96
0.96
Pdh Tj = 12°C
14.42 kW
13.93 kW
COP Tj = 12°C
6.69
6.17
Cdh Tj = +12 °C
0.96
0.96
Pdh Tj = Tbiv
17.6 kW
15.27 kW
COP Tj = Tbiv
2.22
1.59
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.8 kW
13.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.84
1.47
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
21.57 kW
20.72 kW
Annual energy consumption Qhe
14915 kWh
18714 kWh
Pdh Tj = -15°C (if TOL<-20°C)
13.8
13.86
COP Tj = -15°C (if TOL<-20°C)
1.84
1.47
Cdh Tj = -15 °C
0.9
0.9
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
-99 dB(A)
-99 dB(A)
Sound power level outdoor
68 dB(A)
68 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
169 %
124 %
Prated
25.5 kW
22.97 kW
SCOP
4.31
3.18
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
22.60 kW
18.82 kW
COP Tj = -7°C
2.60
1.89
Cdh Tj = -7 °C
0.9
0.9
Pdh Tj = +2°C
13.25 kW
12.44 kW
COP Tj = +2°C
4.41
3.15
Cdh Tj = +2 °C
0.9
0.9
Pdh Tj = +7°C
12.44 kW
11.48 kW
COP Tj = +7°C
5.44
4.40
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
14.77 kW
13.82 kW
COP Tj = 12°C
6.83
6.12
Cdh Tj = +12 °C
0.98
0.98
Pdh Tj = Tbiv
22.60 kW
19.44 kW
COP Tj = Tbiv
2.60
1.96
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
18.38 kW
11.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.25
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.9
0.9
WTOL
60 °C
60 °C
Poff
50 W
50 W
PTO
100 W
100 W
PSB
50 W
50 W
PCK
10 W
10 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.17 kW
11.97 kW
Annual energy consumption Qhe