Certificate holders

Subtype

Yutaki M 4.0HP R32 (tri)

Certificate Holder
Johnson Controls-Hitachi AirConditioning Spain
Ronda Shimizu, 1. Pol. Ind. Can Torrella
08233 Vacarisses, Barcelona
Spain
Registration number
041-K002-60
Certification Body
BRE Global Limited
Subtype title
Yutaki M 4.0HP R32 (tri)
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

2,600 kg

Certification Date
14.10.2022
Testing basis
Heat Pump Keymark Scheme Rules Rev 09
Generate PDF Export model CSV Download certificate
  • Number of models 7

Models

RASM-4R1E - heating only
Configure model
Model name
RASM-4R1E - heating only
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.00 kW

11.00 kW

El input

2.34 kW

4.04 kW

COP

4.70

2.72

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

166 %

125 %

Prated

11.00 kW

11.00 kW

SCOP

4.24

3.21

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

9.70 kW

COP Tj = -7°C

3.06

2.40

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.90 kW

5.90 kW

COP Tj = +2°C

4.30

3.22

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.80 kW

3.80 kW

COP Tj = +7°C

5.06

3.60

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.34 kW

4.20 kW

COP Tj = 12°C

7.13

6.00

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.70 kW

9.70 kW

COP Tj = Tbiv

3.06

2.40

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.70 kW

9.70 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.65

2.13

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

35 °C

55 °C

Poff

29 W

29 W

PTO

0 W

0 W

PSB

29 W

29 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

1.30 kW

1.30 kW

Annual energy consumption Qhe

5347 kWh

7054 kWh

RASM-4R1E - with cooling kit
Configure model
Model name
RASM-4R1E - with cooling kit
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.00 kW

11.00 kW

El input

2.34 kW

4.04 kW

COP

4.70

2.72

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

3.31 kW

2.18 kW

Cooling capacity

11.00

11.00

EER

3.32

5.04

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

11.00 kW

11.00 kW

SEER

4.42

7.88

Pdc Tj = 35°C

11.00 kW

11.00 kW

EER Tj = 35°C

3.32

5.04

Cdc Tj = 35 °C

 

 

Pdc Tj = 30°C

8.11 kW

8.11 kW

EER Tj = 30°C

4.11

6.96

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

5.16 kW

5.27 kW

EER Tj = 25°C

5.17

9.91

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

3.20 kW

5.56 kW

EER Tj = 20°C

5.71

15.01

Cdc Tj = 20 °C

0.900

0.900

Poff

29 W

29 W

PTO

0 W

0 W

PSB

29 W

29 W

PCK

0 W

0 W

Annual energy consumption Qce

871 kWh

489 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

170 %

127 %

Prated

11.00 kW

11.00 kW

SCOP

4.24

3.21

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

9.70 kW

COP Tj = -7°C

3.06

2.40

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.90 kW

5.90 kW

COP Tj = +2°C

4.30

3.22

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.80 kW

3.80 kW

COP Tj = +7°C

5.06

3.60

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.34 kW

4.20 kW

COP Tj = 12°C

7.13

6.00

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.70 kW

9.70 kW

COP Tj = Tbiv

3.06

2.40

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.70 kW

9.70 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.65

2.13

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

35 °C

55 °C

Poff

29 W

29 W

PTO

0 W

0 W

PSB

29 W

29 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

1.30 kW

1.30 kW

Annual energy consumption Qhe

5241 kWh

6948 kWh

RASM-4RW1E & HWM-WE - heating only
Configure model
Model name
RASM-4RW1E & HWM-WE - heating only
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
n/a

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.00 kW

11.00 kW

El input

2.34 kW

4.04 kW

COP

4.70

2.72

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

49 dB(A)

49 dB(A)

Sound power level outdoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

166 %

125 %

Prated

11.00 kW

11.00 kW

SCOP

4.24

3.21

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

9.70 kW

COP Tj = -7°C

3.06

2.40

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.90 kW

5.90 kW

COP Tj = +2°C

4.30

3.22

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.80 kW

3.80 kW

COP Tj = +7°C

5.06

3.60

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.34 kW

4.20 kW

COP Tj = 12°C

7.13

6.00

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.70 kW

9.70 kW

COP Tj = Tbiv

3.06

2.40

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.70 kW

9.70 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.65

2.13

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

35 °C

55 °C

Poff

29 W

29 W

PTO

0 W

0 W

PSB

29 W

29 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

1.30 kW

1.30 kW

Annual energy consumption Qhe

5347 kWh

7054 kWh

RASM-4RW1E & HWM-WE - with cooling kit
Configure model
Model name
RASM-4RW1E & HWM-WE - with cooling kit
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
n/a

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.00 kW

11.00 kW

El input

2.34 kW

4.04 kW

COP

4.70

2.72

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

3.31 kW

2.18 kW

Cooling capacity

11.00

11.00

EER

3.32

5.04

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

11.00 kW

11.00 kW

SEER

4.42

7.88

Pdc Tj = 35°C

11.00 kW

11.00 kW

EER Tj = 35°C

3.32

5.04

Cdc Tj = 35 °C

 

 

Pdc Tj = 30°C

8.11 kW

8.11 kW

EER Tj = 30°C

4.11

6.96

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

5.16 kW

5.27 kW

EER Tj = 25°C

5.17

9.91

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

3.20 kW

5.56 kW

EER Tj = 20°C

5.71

15.01

Cdc Tj = 20 °C

0.900

0.900

Poff

29 W

29 W

PTO

0 W

0 W

PSB

29 W

29 W

PCK

0 W

0 W

Annual energy consumption Qce

871 kWh

489 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

49 dB(A)

49 dB(A)

Sound power level outdoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

170 %

127 %

Prated

11.00 kW

11.00 kW

SCOP

4.24

3.21

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

9.70 kW

COP Tj = -7°C

3.06

2.40

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.90 kW

5.90 kW

COP Tj = +2°C

4.30

3.22

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.80 kW

3.80 kW

COP Tj = +7°C

5.06

3.60

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.34 kW

4.20 kW

COP Tj = 12°C

7.13

6.00

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.70 kW

9.70 kW

COP Tj = Tbiv

3.06

2.40

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.70 kW

9.70 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.65

2.13

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

35 °C

55 °C

Poff

29 W

29 W

PTO

0 W

0 W

PSB

29 W

29 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

1.30 kW

1.30 kW

Annual energy consumption Qhe

5241 kWh

6948 kWh

RASM-4RW1E & HWD-WE-220S - heating only
Configure model
Model name
RASM-4RW1E & HWD-WE-220S - heating only
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
n/a

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.00 kW

11.00 kW

El input

2.34 kW

4.04 kW

COP

4.70

2.72

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

49 dB(A)

49 dB(A)

Sound power level outdoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

166 %

125 %

Prated

11.00 kW

11.00 kW

SCOP

4.24

3.21

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

9.70 kW

COP Tj = -7°C

3.06

2.40

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.90 kW

5.90 kW

COP Tj = +2°C

4.30

3.22

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.80 kW

3.80 kW

COP Tj = +7°C

5.06

3.60

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.34 kW

4.20 kW

COP Tj = 12°C

7.13

6.00

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.70 kW

9.70 kW

COP Tj = Tbiv

3.06

2.40

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.70 kW

9.70 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.65

2.13

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

35 °C

55 °C

Poff

29 W

29 W

PTO

0 W

0 W

PSB

29 W

29 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

1.30 kW

1.30 kW

Annual energy consumption Qhe

5347 kWh

7054 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

95 %

COP

2.30

Heating up time

1:10 h:min

Standby power input

56.0 W

Reference hot water temperature

52.9 °C

Mixed water at 40°C

288 l

RASM-4RW1E & HWD-WE-220S-K - heating only
Configure model
Model name
RASM-4RW1E & HWD-WE-220S-K - heating only
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
n/a

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.00 kW

11.00 kW

El input

2.34 kW

4.04 kW

COP

4.70

2.72

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

49 dB(A)

49 dB(A)

Sound power level outdoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

166 %

125 %

Prated

11.00 kW

11.00 kW

SCOP

4.24

3.21

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

9.70 kW

COP Tj = -7°C

3.06

2.40

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.90 kW

5.90 kW

COP Tj = +2°C

4.30

3.22

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.80 kW

3.80 kW

COP Tj = +7°C

5.06

3.60

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.34 kW

4.20 kW

COP Tj = 12°C

7.13

6.00

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.70 kW

9.70 kW

COP Tj = Tbiv

3.06

2.40

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.70 kW

9.70 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.65

2.13

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

35 °C

55 °C

Poff

29 W

29 W

PTO

0 W

0 W

PSB

29 W

29 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

1.30 kW

1.30 kW

Annual energy consumption Qhe

5347 kWh

7054 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

95 %

COP

2.30

Heating up time

1:10 h:min

Standby power input

56.0 W

Reference hot water temperature

52.9 °C

Mixed water at 40°C

288 l

RASM-4RW1E & HWD-WE-220S - with cooling kit
Configure model
Model name
RASM-4RW1E & HWD-WE-220S - with cooling kit
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
n/a

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.00 kW

11.00 kW

El input

2.34 kW

4.04 kW

COP

4.70

2.72

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

3.31 kW

2.18 kW

Cooling capacity

11.00

11.00

EER

3.32

5.04

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

11.00 kW

11.00 kW

SEER

4.42

7.88

Pdc Tj = 35°C

11.00 kW

11.00 kW

EER Tj = 35°C

3.32

5.04

Cdc Tj = 35 °C

 

 

Pdc Tj = 30°C

8.11 kW

8.11 kW

EER Tj = 30°C

4.11

6.96

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

5.16 kW

5.27 kW

EER Tj = 25°C

5.17

9.91

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

3.20 kW

5.56 kW

EER Tj = 20°C

5.71

15.01

Cdc Tj = 20 °C

0.900

0.900

Poff

29 W

29 W

PTO

0 W

0 W

PSB

29 W

29 W

PCK

0 W

0 W

Annual energy consumption Qce

871 kWh

489 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

49 dB(A)

49 dB(A)

Sound power level outdoor

61 dB(A)

61 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

170 %

127 %

Prated

11.00 kW

11.00 kW

SCOP

4.24

3.21

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.70 kW

9.70 kW

COP Tj = -7°C

3.06

2.40

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.90 kW

5.90 kW

COP Tj = +2°C

4.30

3.22

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.80 kW

3.80 kW

COP Tj = +7°C

5.06

3.60

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

4.34 kW

4.20 kW

COP Tj = 12°C

7.13

6.00

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.70 kW

9.70 kW

COP Tj = Tbiv

3.06

2.40

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.70 kW

9.70 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.65

2.13

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

35 °C

55 °C

Poff

29 W

29 W

PTO

0 W

0 W

PSB

29 W

29 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

1.30 kW

1.30 kW

Annual energy consumption Qhe

5241 kWh

6948 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

95 %

COP

2.30

Heating up time

1:10 h:min

Standby power input

56.0 W

Reference hot water temperature

52.9 °C

Mixed water at 40°C

288 l