1,600 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.85 kW
7.40 kW
El input
2.11 kW
2.32 kW
COP
4.68
3.19
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
3.00 kW
1.90 kW
Cooling capacity
7.32
7.16
EER
2.44
3.76
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
7.69 kW
8.44 kW
SEER
3.97
5.94
Pdc Tj = 35°C
7.69 kW
8.44 kW
EER Tj = 35°C
2.39
3.61
Cdc Tj = 35 °C
1.000
1.000
Pdc Tj = 30°C
5.34 kW
5.98 kW
EER Tj = 30°C
3.43
5.01
Cdc Tj = 30 °C
1.000
1.000
Pdc Tj = 25°C
3.32 kW
4.48 kW
EER Tj = 25°C
4.44
6.84
Cdc Tj = 25 °C
0.975
0.972
Pdc Tj = 20°C
3.65 kW
4.82 kW
EER Tj = 20°C
5.50
8.57
Cdc Tj = 20 °C
0.972
0.967
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
1161 kWh
853 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
225 %
162 %
Prated
8.03 kW
7.39 kW
SCOP
5.71
4.12
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
8.03 kW
7.39 kW
COP Tj = +2°C
3.35
2.08
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
5.51 kW
5.16 kW
COP Tj = +7°C
5.21
3.50
Cdh Tj = +7 °C
0.98
0.99
Pdh Tj = 12°C
5.41 kW
5.40 kW
COP Tj = 12°C
7.05
5.55
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
8.03 kW
7.39 kW
COP Tj = Tbiv
3.35
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.03 kW
7.39 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.35
2.08
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1878 kWh
2396 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
144 %
106 %
Prated
6.86 kW
8.14 kW
SCOP
3.69
2.72
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-15 °C
Pdh Tj = -7°C
4.31 kW
4.73 kW
COP Tj = -7°C
3.00
2.20
Cdh Tj = -7 °C
0.99
1.00
Pdh Tj = +2°C
3.62 kW
3.34 kW
COP Tj = +2°C
4.54
3.48
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
4.44 kW
4.42 kW
COP Tj = +7°C
6.02
5.02
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
5.08 kW
5.18 kW
COP Tj = 12°C
7.37
5.62
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
5.60 kW
6.64 kW
COP Tj = Tbiv
2.20
1.72
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.80 kW
6.64 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.09
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
6.86 kW
8.14 kW
Annual energy consumption Qhe
4587 kWh
7362 kWh
Pdh Tj = -15°C (if TOL<-20°C)
5.60
6.64
COP Tj = -15°C (if TOL<-20°C)
2.20
1.72
Cdh Tj = -15 °C
1.00
1.00
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
130 %
Prated
7.75 kW
8.35 kW
SCOP
4.51
3.34
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.86 kW
7.38 kW
COP Tj = -7°C
2.80
2.24
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
4.10 kW
4.39 kW
COP Tj = +2°C
4.43
3.10
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
4.47 kW
4.45 kW
COP Tj = +7°C
6.09
4.51
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
5.12 kW
5.34 kW
COP Tj = 12°C
7.95
6.07
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
6.86 kW
7.38 kW
COP Tj = Tbiv
2.80
2.24
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.08 kW
7.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.98
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.67 kW
1.28 kW
Annual energy consumption Qhe
3548 kWh
5170 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.85 kW
7.40 kW
El input
2.11 kW
2.32 kW
COP
4.68
3.19
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
3.00 kW
1.90 kW
Cooling capacity
7.32
7.16
EER
2.44
3.76
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
7.69 kW
8.44 kW
SEER
3.97
5.94
Pdc Tj = 35°C
7.69 kW
8.44 kW
EER Tj = 35°C
2.39
3.61
Cdc Tj = 35 °C
1.000
1.000
Pdc Tj = 30°C
5.34 kW
5.98 kW
EER Tj = 30°C
3.43
5.01
Cdc Tj = 30 °C
1.000
1.000
Pdc Tj = 25°C
3.32 kW
4.48 kW
EER Tj = 25°C
4.44
6.84
Cdc Tj = 25 °C
1.000
0.972
Pdc Tj = 20°C
3.65 kW
4.82 kW
EER Tj = 20°C
5.50
8.57
Cdc Tj = 20 °C
0.972
0.967
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
1161 kWh
853 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
225 %
162 %
Prated
8.03 kW
7.39 kW
SCOP
5.71
4.12
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
8.03 kW
7.39 kW
COP Tj = +2°C
3.35
2.08
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
5.51 kW
5.16 kW
COP Tj = +7°C
5.21
3.50
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
5.41 kW
5.40 kW
COP Tj = 12°C
7.05
5.55
Cdh Tj = +12 °C
0.970
0.980
Pdh Tj = Tbiv
8.03 kW
7.39 kW
COP Tj = Tbiv
3.35
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.03 kW
7.39 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.35
2.08
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1878 kWh
2396 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
130 %
Prated
6.08 kW
7.07 kW
SCOP
4.51
3.33
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.86 kW
7.38 kW
COP Tj = -7°C
2.80
2.24
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.10 kW
4.39 kW
COP Tj = +2°C
4.43
3.10
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
4.47 kW
4.45 kW
COP Tj = +7°C
6.09
4.51
Cdh Tj = +7 °C
0.970
0.980
Pdh Tj = 12°C
5.12 kW
5.34 kW
COP Tj = 12°C
7.95
6.07
Cdh Tj = +12 °C
0.970
0.980
Pdh Tj = Tbiv
6.08 kW
7.07 kW
COP Tj = Tbiv
2.40
1.98
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.08 kW
7.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.98
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2787 kWh
4379 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.85 kW
7.40 kW
El input
2.11 kW
2.32 kW
COP
4.68
3.19
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
3.00 kW
1.90 kW
Cooling capacity
7.32
7.16
EER
2.44
3.76
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
7.69 kW
8.44 kW
SEER
3.97
5.94
Pdc Tj = 35°C
7.69 kW
8.44 kW
EER Tj = 35°C
2.39
3.61
Cdc Tj = 35 °C
1.000
1.000
Pdc Tj = 30°C
5.34 kW
5.98 kW
EER Tj = 30°C
3.43
5.01
Cdc Tj = 30 °C
1.000
1.000
Pdc Tj = 25°C
3.32 kW
4.48 kW
EER Tj = 25°C
4.44
6.84
Cdc Tj = 25 °C
0.975
0.972
Pdc Tj = 20°C
3.65 kW
4.82 kW
EER Tj = 20°C
5.50
8.57
Cdc Tj = 20 °C
0.972
0.967
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
1161 kWh
853 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
225 %
162 %
Prated
8.03 kW
7.39 kW
SCOP
5.71
4.12
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
8.03 kW
7.39 kW
COP Tj = +2°C
3.35
2.08
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
5.51 kW
5.16 kW
COP Tj = +7°C
5.21
3.50
Cdh Tj = +7 °C
0.98
0.99
Pdh Tj = 12°C
5.41 kW
5.40 kW
COP Tj = 12°C
7.05
5.55
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
8.03 kW
7.39 kW
COP Tj = Tbiv
3.35
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.03 kW
7.39 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.35
2.08
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1878 kWh
2396 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
144 %
106 %
Prated
6.86 kW
8.14 kW
SCOP
3.69
2.72
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-15 °C
Pdh Tj = -7°C
4.31 kW
4.73 kW
COP Tj = -7°C
3.00
2.20
Cdh Tj = -7 °C
0.99
1.00
Pdh Tj = +2°C
3.62 kW
3.34 kW
COP Tj = +2°C
4.54
3.48
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
4.44 kW
4.42 kW
COP Tj = +7°C
6.02
5.02
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
5.08 kW
5.18 kW
COP Tj = 12°C
7.37
5.62
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
5.60 kW
6.64 kW
COP Tj = Tbiv
2.20
1.72
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.80 kW
6.64 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.09
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
6.86 kW
8.14 kW
Annual energy consumption Qhe
4587 kWh
7362 kWh
Pdh Tj = -15°C (if TOL<-20°C)
5.60
6.64
COP Tj = -15°C (if TOL<-20°C)
2.20
1.72
Cdh Tj = -15 °C
1.00
1.00
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
130 %
Prated
7.75 kW
8.35 kW
SCOP
4.51
3.34
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.86 kW
7.38 kW
COP Tj = -7°C
2.80
2.24
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
4.10 kW
4.39 kW
COP Tj = +2°C
4.43
3.10
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
4.47 kW
4.45 kW
COP Tj = +7°C
6.09
4.51
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
5.12 kW
5.34 kW
COP Tj = 12°C
7.95
6.07
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
6.86 kW
7.38 kW
COP Tj = Tbiv
2.80
2.24
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.08 kW
7.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.98
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.67 kW
1.28 kW
Annual energy consumption Qhe
3548 kWh
5170 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
113.9 %
COP
2.72
Heating up time
00:51 h:min
Standby power input
34.9 W
Reference hot water temperature
51.68 °C
Mixed water at 40°C
236.73 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
83 %
COP
2.00
Heating up time
00:57 h:min
Standby power input
40.9 W
Reference hot water temperature
51.45 °C
Mixed water at 40°C
235.28 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
98.5 %
COP
2.36
Heating up time
00:54 h:min
Standby power input
39.0 W
Reference hot water temperature
51.53 °C
Mixed water at 40°C
236.2 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.85 kW
7.40 kW
El input
2.16 kW
2.37 kW
COP
4.57
3.12
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
3.05 kW
1.95 kW
Cooling capacity
7.32
7.16
EER
2.40
3.67
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
7.69 kW
8.44 kW
SEER
3.78
5.60
Pdc Tj = 35°C
7.69 kW
8.44 kW
EER Tj = 35°C
2.35
3.54
Cdc Tj = 35 °C
1.000
1.000
Pdc Tj = 30°C
5.34 kW
5.98 kW
EER Tj = 30°C
3.33
4.81
Cdc Tj = 30 °C
1.000
1.000
Pdc Tj = 25°C
3.32 kW
4.48 kW
EER Tj = 25°C
4.16
6.35
Cdc Tj = 25 °C
1.000
0.974
Pdc Tj = 20°C
3.65 kW
4.82 kW
EER Tj = 20°C
5.11
7.87
Cdc Tj = 20 °C
0.974
0.970
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
1220 kWh
904 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
214 %
156 %
Prated
8.03 kW
7.39 kW
SCOP
5.43
3.97
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
8.03 kW
7.39 kW
COP Tj = +2°C
3.28
2.05
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
5.51 kW
5.16 kW
COP Tj = +7°C
4.97
3.39
Cdh Tj = +7 °C
0.98
0.99
Pdh Tj = 12°C
5.41 kW
5.40 kW
COP Tj = 12°C
6.62
5.28
Cdh Tj = +12 °C
0.98
0.98
Pdh Tj = Tbiv
8.03 kW
7.39 kW
COP Tj = Tbiv
3.28
2.05
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.03 kW
7.39 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.28
2.05
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1976 kWh
2490 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
138 %
102 %
Prated
6.86 kW
8.14 kW
SCOP
3.52
2.64
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-15 °C
Pdh Tj = -7°C
4.31 kW
4.73 kW
COP Tj = -7°C
2.90
2.15
Cdh Tj = -7 °C
0.99
1.00
Pdh Tj = +2°C
3.62 kW
3.34 kW
COP Tj = +2°C
4.27
3.31
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
4.44 kW
4.42 kW
COP Tj = +7°C
5.64
4.75
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
5.08 kW
5.18 kW
COP Tj = 12°C
6.87
5.33
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
5.60 kW
6.64 kW
COP Tj = Tbiv
2.16
1.70
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.80 kW
6.64 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.05
1.70
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
6.86 kW
8.14 kW
Annual energy consumption Qhe
4798 kWh
7612 kWh
Pdh Tj = -15°C (if TOL<-20°C)
5.60
6.64
COP Tj = -15°C (if TOL<-20°C)
2.16
1.70
Cdh Tj = -15 °C
1.00
1.00
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
169 %
126 %
Prated
7.75 kW
8.35 kW
SCOP
4.30
3.22
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.86 kW
7.38 kW
COP Tj = -7°C
2.74
2.21
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
4.10 kW
4.39 kW
COP Tj = +2°C
4.20
3.00
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
4.47 kW
4.45 kW
COP Tj = +7°C
5.70
4.29
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
5.12 kW
5.34 kW
COP Tj = 12°C
7.37
5.74
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
6.86 kW
7.38 kW
COP Tj = Tbiv
2.74
2.21
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.08 kW
7.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.35
1.96
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.67 kW
1.28 kW
Annual energy consumption Qhe
3729 kWh
5354 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
113.9 %
COP
2.72
Heating up time
00:51 h:min
Standby power input
34.9 W
Reference hot water temperature
51.68 °C
Mixed water at 40°C
236.73 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
83 %
COP
2.00
Heating up time
00:57 h:min
Standby power input
40.9 W
Reference hot water temperature
51.45 °C
Mixed water at 40°C
235.28 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
98.5 %
COP
2.36
Heating up time
00:54 h:min
Standby power input
39.0 W
Reference hot water temperature
51.53 °C
Mixed water at 40°C
236.2 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.85 kW
7.40 kW
El input
2.11 kW
2.32 kW
COP
4.68
3.19
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
3.00 kW
1.90 kW
Cooling capacity
7.32
7.16
EER
2.44
3.76
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
7.69 kW
8.44 kW
SEER
3.97
5.94
Pdc Tj = 35°C
7.69 kW
8.44 kW
EER Tj = 35°C
2.39
3.61
Cdc Tj = 35 °C
1.000
1.000
Pdc Tj = 30°C
5.34 kW
5.98 kW
EER Tj = 30°C
3.43
5.01
Cdc Tj = 30 °C
1.000
1.000
Pdc Tj = 25°C
3.32 kW
4.48 kW
EER Tj = 25°C
4.44
6.84
Cdc Tj = 25 °C
0.975
0.972
Pdc Tj = 20°C
3.65 kW
4.82 kW
EER Tj = 20°C
5.50
8.57
Cdc Tj = 20 °C
0.972
0.967
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
1161 kWh
853 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
225 %
162 %
Prated
8.03 kW
7.39 kW
SCOP
5.71
4.12
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
8.03 kW
7.39 kW
COP Tj = +2°C
3.35
2.08
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
5.51 kW
5.16 kW
COP Tj = +7°C
5.21
3.50
Cdh Tj = +7 °C
0.98
0.99
Pdh Tj = 12°C
5.41 kW
5.40 kW
COP Tj = 12°C
7.05
5.55
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
8.03 kW
7.39 kW
COP Tj = Tbiv
3.35
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.03 kW
7.39 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.35
2.08
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1878 kWh
2396 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
144 %
106 %
Prated
6.86 kW
8.14 kW
SCOP
3.69
2.72
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-15 °C
Pdh Tj = -7°C
4.31 kW
4.73 kW
COP Tj = -7°C
3.00
2.20
Cdh Tj = -7 °C
0.99
1.00
Pdh Tj = +2°C
3.62 kW
3.34 kW
COP Tj = +2°C
4.54
3.48
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
4.44 kW
4.42 kW
COP Tj = +7°C
6.02
5.02
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
5.08 kW
5.18 kW
COP Tj = 12°C
7.37
5.62
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
5.60 kW
6.64 kW
COP Tj = Tbiv
2.20
1.72
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.80 kW
6.64 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.09
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
6.86 kW
8.14 kW
Annual energy consumption Qhe
4587 kWh
7362 kWh
Pdh Tj = -15°C (if TOL<-20°C)
5.60
6.64
COP Tj = -15°C (if TOL<-20°C)
2.20
1.72
Cdh Tj = -15 °C
1.00
1.00
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
130 %
Prated
7.75 kW
8.35 kW
SCOP
4.51
3.34
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.86 kW
7.38 kW
COP Tj = -7°C
2.80
2.24
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
4.10 kW
4.39 kW
COP Tj = +2°C
4.43
3.10
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
4.47 kW
4.45 kW
COP Tj = +7°C
6.09
4.51
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
5.12 kW
5.34 kW
COP Tj = 12°C
7.95
6.07
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
6.86 kW
7.38 kW
COP Tj = Tbiv
2.80
2.24
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.08 kW
7.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.98
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.67 kW
1.28 kW
Annual energy consumption Qhe
3548 kWh
5170 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
113.9 %
COP
2.72
Heating up time
00:51 h:min
Standby power input
34.9 W
Reference hot water temperature
51.68 °C
Mixed water at 40°C
236.73 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
83 %
COP
2.00
Heating up time
00:57 h:min
Standby power input
40.9 W
Reference hot water temperature
51.45 °C
Mixed water at 40°C
235.28 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
98.5 %
COP
2.36
Heating up time
00:54 h:min
Standby power input
39.0 W
Reference hot water temperature
51.53 °C
Mixed water at 40°C
236.2 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.88 kW
6.71 kW
El input
1.70 kW
2.14 kW
COP
4.65
3.14
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
2.27 kW
1.78 kW
Cooling capacity
6.37
7.04
EER
2.81
3.96
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
7.41 kW
7.04 kW
SEER
4.04
6.00
Pdc Tj = 35°C
7.41 kW
7.04 kW
EER Tj = 35°C
2.54
3.96
Cdc Tj = 35 °C
0.994
1.000
Pdc Tj = 30°C
5.40 kW
5.15 kW
EER Tj = 30°C
3.43
5.24
Cdc Tj = 30 °C
0.988
1.000
Pdc Tj = 25°C
3.45 kW
4.60 kW
EER Tj = 25°C
4.35
6.81
Cdc Tj = 25 °C
0.977
0.973
Pdc Tj = 20°C
4.00 kW
5.00 kW
EER Tj = 20°C
6.05
8.80
Cdc Tj = 20 °C
0.972
0.968
Poff
15 W
15 W
PTO
18 W
18 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
1100 kWh
704 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
225 %
156 %
Prated
8.03 kW
7.02 kW
SCOP
5.71
3.96
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
8.03 kW
7.02 kW
COP Tj = +2°C
3.35
2.16
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
5.51 kW
4.73 kW
COP Tj = +7°C
5.21
3.40
Cdh Tj = +7 °C
0.98
0.99
Pdh Tj = 12°C
5.41 kW
5.27 kW
COP Tj = 12°C
7.05
5.22
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
8.03 kW
7.02 kW
COP Tj = Tbiv
3.35
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.03 kW
7.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.35
2.16
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1878 kWh
2367 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
145 %
109 %
Prated
7.74 kW
8.13 kW
SCOP
3.71
2.81
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-15 °C
Pdh Tj = -7°C
4.97 kW
4.50 kW
COP Tj = -7°C
3.05
2.31
Cdh Tj = -7 °C
0.99
1.00
Pdh Tj = +2°C
3.38 kW
3.71 kW
COP Tj = +2°C
4.40
3.65
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
4.57 kW
4.37 kW
COP Tj = +7°C
6.37
4.73
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
5.06 kW
5.02 kW
COP Tj = 12°C
7.71
6.07
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
6.31 kW
6.63 kW
COP Tj = Tbiv
2.50
1.73
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.25 kW
6.63 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.94
1.73
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.74 kW
8.13 kW
Annual energy consumption Qhe
5141 kWh
7129 kWh
Pdh Tj = -15°C (if TOL<-20°C)
6.31
6.63
COP Tj = -15°C (if TOL<-20°C)
2.50
1.73
Cdh Tj = -15 °C
1.00
1.00
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
131 %
Prated
7.46 kW
7.68 kW
SCOP
4.46
3.34
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.60 kW
6.80 kW
COP Tj = -7°C
2.84
2.16
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
3.89 kW
4.12 kW
COP Tj = +2°C
4.46
3.26
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
4.40 kW
4.31 kW
COP Tj = +7°C
5.72
4.29
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
5.08 kW
5.16 kW
COP Tj = 12°C
7.39
5.81
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
6.60 kW
6.80 kW
COP Tj = Tbiv
2.84
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.75 kW
6.51 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.45
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.71 kW
1.18 kW
Annual energy consumption Qhe
3457 kWh
4755 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.88 kW
6.71 kW
El input
1.70 kW
2.14 kW
COP
4.65
3.14
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
2.27 kW
1.78 kW
Cooling capacity
6.37
7.04
EER
2.81
3.96
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
7.41 kW
7.04 kW
SEER
4.04
6.00
Pdc Tj = 35°C
7.41 kW
7.04 kW
EER Tj = 35°C
2.54
3.96
Cdc Tj = 35 °C
1.000
1.000
Pdc Tj = 30°C
5.40 kW
5.15 kW
EER Tj = 30°C
3.43
5.24
Cdc Tj = 30 °C
1.000
1.000
Pdc Tj = 25°C
3.45 kW
4.60 kW
EER Tj = 25°C
4.35
6.81
Cdc Tj = 25 °C
1.000
0.973
Pdc Tj = 20°C
4.00 kW
5.00 kW
EER Tj = 20°C
6.05
8.80
Cdc Tj = 20 °C
0.972
0.968
Poff
15 W
15 W
PTO
18 W
18 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
1100 kWh
704 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
225 %
156 %
Prated
8.03 kW
7.02 kW
SCOP
5.71
3.96
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
8.03 kW
7.02 kW
COP Tj = +2°C
3.35
2.16
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
5.51 kW
4.73 kW
COP Tj = +7°C
5.21
3.40
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
5.41 kW
5.27 kW
COP Tj = 12°C
7.05
5.22
Cdh Tj = +12 °C
0.970
0.980
Pdh Tj = Tbiv
8.03 kW
7.02 kW
COP Tj = Tbiv
3.35
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.03 kW
7.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.35
2.16
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1878 kWh
2367 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
130 %
Prated
5.75 kW
6.51 kW
SCOP
4.45
3.33
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.60 kW
6.80 kW
COP Tj = -7°C
2.84
2.16
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
3.89 kW
4.12 kW
COP Tj = +2°C
4.46
3.26
Cdh Tj = +2 °C
0.980
0.980
Pdh Tj = +7°C
4.40 kW
4.31 kW
COP Tj = +7°C
5.72
4.29
Cdh Tj = +7 °C
0.970
0.980
Pdh Tj = 12°C
5.08 kW
5.16 kW
COP Tj = 12°C
7.39
5.81
Cdh Tj = +12 °C
0.970
0.980
Pdh Tj = Tbiv
5.75 kW
6.51 kW
COP Tj = Tbiv
2.45
1.72
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.75 kW
6.51 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.45
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
2669 kWh
4032 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.88 kW
6.71 kW
El input
1.70 kW
2.14 kW
COP
4.65
3.14
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
2.27 kW
1.78 kW
Cooling capacity
6.37
7.04
EER
2.81
3.96
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
7.41 kW
7.04 kW
SEER
4.04
6.00
Pdc Tj = 35°C
7.41 kW
7.04 kW
EER Tj = 35°C
2.54
3.96
Cdc Tj = 35 °C
0.994
1.000
Pdc Tj = 30°C
5.40 kW
5.15 kW
EER Tj = 30°C
3.43
5.24
Cdc Tj = 30 °C
0.988
1.000
Pdc Tj = 25°C
3.45 kW
4.60 kW
EER Tj = 25°C
4.35
6.81
Cdc Tj = 25 °C
0.977
0.973
Pdc Tj = 20°C
4.00 kW
5.00 kW
EER Tj = 20°C
6.05
8.80
Cdc Tj = 20 °C
0.972
0.968
Poff
15 W
15 W
PTO
18 W
18 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
1100 kWh
704 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
225 %
156 %
Prated
8.03 kW
7.02 kW
SCOP
5.71
3.96
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
8.03 kW
7.02 kW
COP Tj = +2°C
3.35
2.16
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
5.51 kW
4.73 kW
COP Tj = +7°C
5.21
3.40
Cdh Tj = +7 °C
0.98
0.99
Pdh Tj = 12°C
5.41 kW
5.27 kW
COP Tj = 12°C
7.05
5.22
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
8.03 kW
7.02 kW
COP Tj = Tbiv
3.35
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.03 kW
7.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.35
2.16
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1878 kWh
2367 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
145 %
109 %
Prated
7.74 kW
8.13 kW
SCOP
3.71
2.81
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-15 °C
Pdh Tj = -7°C
4.97 kW
4.50 kW
COP Tj = -7°C
3.05
2.31
Cdh Tj = -7 °C
0.99
1.00
Pdh Tj = +2°C
3.38 kW
3.71 kW
COP Tj = +2°C
4.40
3.65
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
4.57 kW
4.37 kW
COP Tj = +7°C
6.37
4.73
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
5.06 kW
5.02 kW
COP Tj = 12°C
7.71
6.07
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
6.31 kW
6.63 kW
COP Tj = Tbiv
2.50
1.73
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.25 kW
6.63 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.94
1.73
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.74 kW
8.13 kW
Annual energy consumption Qhe
5141 kWh
7129 kWh
Pdh Tj = -15°C (if TOL<-20°C)
6.31
6.63
COP Tj = -15°C (if TOL<-20°C)
2.50
1.73
Cdh Tj = -15 °C
1.00
1.00
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
131 %
Prated
7.46 kW
7.68 kW
SCOP
4.46
3.34
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.60 kW
6.80 kW
COP Tj = -7°C
2.84
2.16
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
3.89 kW
4.12 kW
COP Tj = +2°C
4.46
3.26
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
4.40 kW
4.31 kW
COP Tj = +7°C
5.72
4.29
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
5.08 kW
5.16 kW
COP Tj = 12°C
7.39
5.81
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
6.60 kW
6.80 kW
COP Tj = Tbiv
2.84
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.75 kW
6.51 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.45
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.71 kW
1.18 kW
Annual energy consumption Qhe
3457 kWh
4755 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
113.9 %
COP
2.72
Heating up time
00:51 h:min
Standby power input
34.9 W
Reference hot water temperature
51.68 °C
Mixed water at 40°C
236.73 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
83 %
COP
2.00
Heating up time
00:57 h:min
Standby power input
40.9 W
Reference hot water temperature
51.45 °C
Mixed water at 40°C
235.28 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
98.5 %
COP
2.36
Heating up time
00:54 h:min
Standby power input
39.0 W
Reference hot water temperature
51.53 °C
Mixed water at 40°C
236.2 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.88 kW
6.71 kW
El input
1.75 kW
2.19 kW
COP
4.51
3.07
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
2.32 kW
1.83 kW
Cooling capacity
6.37
7.04
EER
2.75
3.85
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
7.41 kW
7.04 kW
SEER
3.85
5.66
Pdc Tj = 35°C
7.41 kW
7.04 kW
EER Tj = 35°C
2.49
3.85
Cdc Tj = 35 °C
0.994
1.000
Pdc Tj = 30°C
5.40 kW
5.15 kW
EER Tj = 30°C
3.33
4.98
Cdc Tj = 30 °C
0.989
1.000
Pdc Tj = 25°C
3.45 kW
4.60 kW
EER Tj = 25°C
4.09
6.34
Cdc Tj = 25 °C
0.978
0.975
Pdc Tj = 20°C
4.00 kW
5.00 kW
EER Tj = 20°C
5.63
8.09
Cdc Tj = 20 °C
0.974
0.970
Poff
15 W
15 W
PTO
18 W
18 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
1155 kWh
747 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
214 %
149 %
Prated
8.03 kW
7.02 kW
SCOP
5.43
3.81
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
8.03 kW
7.02 kW
COP Tj = +2°C
3.28
2.13
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
5.51 kW
4.73 kW
COP Tj = +7°C
4.97
3.28
Cdh Tj = +7 °C
0.98
0.99
Pdh Tj = 12°C
5.41 kW
5.27 kW
COP Tj = 12°C
6.62
4.97
Cdh Tj = +12 °C
0.98
0.98
Pdh Tj = Tbiv
8.03 kW
7.02 kW
COP Tj = Tbiv
3.28
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.03 kW
7.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.28
2.13
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1976 kWh
2460 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
139 %
106 %
Prated
7.74 kW
8.13 kW
SCOP
3.55
2.72
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-15 °C
Pdh Tj = -7°C
4.97 kW
4.50 kW
COP Tj = -7°C
2.96
2.26
Cdh Tj = -7 °C
0.99
1.00
Pdh Tj = +2°C
3.38 kW
3.71 kW
COP Tj = +2°C
4.13
3.48
Cdh Tj = +2 °C
0.98
0.98
Pdh Tj = +7°C
4.57 kW
4.37 kW
COP Tj = +7°C
5.96
4.49
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
5.06 kW
5.02 kW
COP Tj = 12°C
7.16
5.72
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
6.31 kW
6.63 kW
COP Tj = Tbiv
2.45
1.70
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.25 kW
6.63 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.90
1.70
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.74 kW
8.13 kW
Annual energy consumption Qhe
5375 kWh
7367 kWh
Pdh Tj = -15°C (if TOL<-20°C)
6.31
6.63
COP Tj = -15°C (if TOL<-20°C)
2.45
1.70
Cdh Tj = -15 °C
1.00
1.00
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
166 %
126 %
Prated
7.46 kW
7.68 kW
SCOP
4.24
3.22
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.60 kW
6.80 kW
COP Tj = -7°C
2.78
2.13
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
3.89 kW
4.12 kW
COP Tj = +2°C
4.22
3.13
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
4.40 kW
4.31 kW
COP Tj = +7°C
5.37
4.09
Cdh Tj = +7 °C
0.98
0.98
Pdh Tj = 12°C
5.08 kW
5.16 kW
COP Tj = 12°C
6.89
5.50
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
6.60 kW
6.80 kW
COP Tj = Tbiv
2.78
2.13
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.75 kW
6.51 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.39
1.70
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.71 kW
1.18 kW
Annual energy consumption Qhe
3636 kWh
4934 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
113.9 %
COP
2.72
Heating up time
00:51 h:min
Standby power input
34.9 W
Reference hot water temperature
51.68 °C
Mixed water at 40°C
236.73 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
83 %
COP
2.00
Heating up time
00:57 h:min
Standby power input
40.9 W
Reference hot water temperature
51.45 °C
Mixed water at 40°C
235.28 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
98.5 %
COP
2.36
Heating up time
00:54 h:min
Standby power input
39.0 W
Reference hot water temperature
51.53 °C
Mixed water at 40°C
236.2 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.88 kW
6.71 kW
El input
1.70 kW
2.14 kW
COP
4.65
3.14
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
2.27 kW
1.78 kW
Cooling capacity
6.37
7.04
EER
2.81
3.96
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
7.41 kW
7.04 kW
SEER
4.04
6.00
Pdc Tj = 35°C
7.41 kW
7.04 kW
EER Tj = 35°C
2.54
3.96
Cdc Tj = 35 °C
0.994
1.000
Pdc Tj = 30°C
5.40 kW
5.15 kW
EER Tj = 30°C
3.43
5.24
Cdc Tj = 30 °C
0.988
1.000
Pdc Tj = 25°C
3.45 kW
4.60 kW
EER Tj = 25°C
4.35
6.81
Cdc Tj = 25 °C
0.977
0.973
Pdc Tj = 20°C
4.00 kW
5.00 kW
EER Tj = 20°C
6.05
8.80
Cdc Tj = 20 °C
0.972
0.968
Poff
15 W
15 W
PTO
18 W
18 W
PSB
15 W
15 W
PCK
0 W
0 W
Annual energy consumption Qce
1100 kWh
704 kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
225 %
156 %
Prated
8.03 kW
7.02 kW
SCOP
5.71
3.96
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
8.03 kW
7.02 kW
COP Tj = +2°C
3.35
2.16
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
5.51 kW
4.73 kW
COP Tj = +7°C
5.21
3.40
Cdh Tj = +7 °C
0.98
0.99
Pdh Tj = 12°C
5.41 kW
5.27 kW
COP Tj = 12°C
7.05
5.22
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
8.03 kW
7.02 kW
COP Tj = Tbiv
3.35
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.03 kW
7.02 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.35
2.16
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1878 kWh
2367 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
145 %
109 %
Prated
7.74 kW
8.13 kW
SCOP
3.71
2.81
Tbiv
-15 °C
-15 °C
TOL
-20 °C
-15 °C
Pdh Tj = -7°C
4.97 kW
4.50 kW
COP Tj = -7°C
3.05
2.31
Cdh Tj = -7 °C
0.99
1.00
Pdh Tj = +2°C
3.38 kW
3.71 kW
COP Tj = +2°C
4.40
3.65
Cdh Tj = +2 °C
0.97
0.98
Pdh Tj = +7°C
4.57 kW
4.37 kW
COP Tj = +7°C
6.37
4.73
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
5.06 kW
5.02 kW
COP Tj = 12°C
7.71
6.07
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
6.31 kW
6.63 kW
COP Tj = Tbiv
2.50
1.73
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.25 kW
6.63 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.94
1.73
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.74 kW
8.13 kW
Annual energy consumption Qhe
5141 kWh
7129 kWh
Pdh Tj = -15°C (if TOL<-20°C)
6.31
6.63
COP Tj = -15°C (if TOL<-20°C)
2.50
1.73
Cdh Tj = -15 °C
1.00
1.00
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
131 %
Prated
7.46 kW
7.68 kW
SCOP
4.46
3.34
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.60 kW
6.80 kW
COP Tj = -7°C
2.84
2.16
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
3.89 kW
4.12 kW
COP Tj = +2°C
4.46
3.26
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
4.40 kW
4.31 kW
COP Tj = +7°C
5.72
4.29
Cdh Tj = +7 °C
0.97
0.98
Pdh Tj = 12°C
5.08 kW
5.16 kW
COP Tj = 12°C
7.39
5.81
Cdh Tj = +12 °C
0.97
0.98
Pdh Tj = Tbiv
6.60 kW
6.80 kW
COP Tj = Tbiv
2.84
2.16
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.75 kW
6.51 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.45
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
60 °C
60 °C
Poff
15 W
15 W
PTO
20 W
20 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.71 kW
1.18 kW
Annual energy consumption Qhe
3457 kWh
4755 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
113.9 %
COP
2.72
Heating up time
00:51 h:min
Standby power input
34.9 W
Reference hot water temperature
51.68 °C
Mixed water at 40°C
236.73 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
83 %
COP
2.00
Heating up time
00:57 h:min
Standby power input
40.9 W
Reference hot water temperature
51.45 °C
Mixed water at 40°C
235.28 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
98.5 %
COP
2.36
Heating up time
00:54 h:min
Standby power input
39.0 W
Reference hot water temperature
51.53 °C
Mixed water at 40°C
236.2 l