1,000 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.30 kW
6.65 kW
El input
1.60 kW
2.28 kW
COP
4.55
2.91
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
140 %
Prated
15.00 kW
14.55 kW
SCOP
4.78
3.70
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
15.16 kW
13.36 kW
COP Tj = +2°C
3.63
2.58
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
10.48 kW
9.98 kW
COP Tj = +7°C
4.38
3.24
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
4.67 kW
4.61 kW
COP Tj = 12°C
5.50
4.48
Cdh Tj = +12 °C
0.980
0.980
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4192 kWh
5256 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
163 %
Prated
15.00 kW
14.55 kW
SCOP
4.89
4.27
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
9.89 kW
9.46 kW
COP Tj = -7°C
4.56
3.73
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
6.04 kW
5.90 kW
COP Tj = +2°C
5.34
4.78
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
3.86 kW
3.50 kW
COP Tj = +7°C
5.54
5.64
Cdh Tj = +7 °C
0.980
0.980
Pdh Tj = 12°C
1.97 kW
1.99 kW
COP Tj = 12°C
4.64
5.99
Cdh Tj = +12 °C
0.970
0.960
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
7564 kWh
8397 kWh
Pdh Tj = -15°C (if TOL<-20°C)
13.30
12.58
COP Tj = -15°C (if TOL<-20°C)
4.16
3.14
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190 %
138 %
Prated
15.00 kW
14.55 kW
SCOP
4.95
3.65
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.42 kW
11.87 kW
COP Tj = -7°C
4.05
2.81
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
8.47 kW
8.48 kW
COP Tj = +2°C
5.01
3.62
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.34 kW
5.56 kW
COP Tj = +7°C
5.61
4.29
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
2.45 kW
2.47 kW
COP Tj = 12°C
5.18
4.38
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6266 kWh
8231 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
81 %
COP
2.00
Heating up time
1:18:30 h:min
Standby power input
102.2 W
Reference hot water temperature
58.1 °C
Mixed water at 40°C
233 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
81 %
COP
2.00
Heating up time
1:18:30 h:min
Standby power input
102.2 W
Reference hot water temperature
58.1 °C
Mixed water at 40°C
233 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
81 %
COP
2.00
Heating up time
1:18:30 h:min
Standby power input
102.2 W
Reference hot water temperature
58.1 °C
Mixed water at 40°C
233 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.30 kW
6.65 kW
El input
1.60 kW
2.28 kW
COP
4.55
2.91
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
140 %
Prated
15.00 kW
14.55 kW
SCOP
4.78
3.70
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
15.16 kW
13.36 kW
COP Tj = +2°C
3.63
2.58
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
10.48 kW
9.98 kW
COP Tj = +7°C
4.38
3.24
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
4.67 kW
4.61 kW
COP Tj = 12°C
5.50
4.48
Cdh Tj = +12 °C
0.980
0.980
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4192 kWh
5256 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
163 %
Prated
15.00 kW
14.55 kW
SCOP
4.89
4.27
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
9.89 kW
9.46 kW
COP Tj = -7°C
4.56
3.73
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
6.04 kW
5.90 kW
COP Tj = +2°C
5.34
4.78
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
3.86 kW
3.50 kW
COP Tj = +7°C
5.54
5.64
Cdh Tj = +7 °C
0.980
0.980
Pdh Tj = 12°C
1.97 kW
1.99 kW
COP Tj = 12°C
4.64
5.99
Cdh Tj = +12 °C
0.970
0.960
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
7564 kWh
8397 kWh
Pdh Tj = -15°C (if TOL<-20°C)
13.30
12.58
COP Tj = -15°C (if TOL<-20°C)
4.16
3.14
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190 %
138 %
Prated
15.00 kW
14.55 kW
SCOP
4.95
3.65
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.42 kW
11.87 kW
COP Tj = -7°C
4.05
2.81
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
8.47 kW
8.48 kW
COP Tj = +2°C
5.01
3.62
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.34 kW
5.56 kW
COP Tj = +7°C
5.61
4.29
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
2.45 kW
2.47 kW
COP Tj = 12°C
5.18
4.38
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6266 kWh
8231 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
81 %
COP
2.00
Heating up time
1:18:30 h:min
Standby power input
102.2 W
Reference hot water temperature
58.1 °C
Mixed water at 40°C
233 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
81 %
COP
2.00
Heating up time
1:18:30 h:min
Standby power input
102.2 W
Reference hot water temperature
58.1 °C
Mixed water at 40°C
233 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
81 %
COP
2.00
Heating up time
1:18:30 h:min
Standby power input
102.2 W
Reference hot water temperature
58.1 °C
Mixed water at 40°C
233 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.30 kW
6.65 kW
El input
1.60 kW
2.28 kW
COP
4.55
2.91
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
140 %
Prated
15.00 kW
14.55 kW
SCOP
4.78
3.70
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
15.16 kW
13.36 kW
COP Tj = +2°C
3.63
2.58
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
10.48 kW
9.98 kW
COP Tj = +7°C
4.38
3.24
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
4.67 kW
4.61 kW
COP Tj = 12°C
5.50
4.48
Cdh Tj = +12 °C
0.980
0.980
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4192 kWh
5256 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
163 %
Prated
15.00 kW
14.55 kW
SCOP
4.89
4.27
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
9.89 kW
9.46 kW
COP Tj = -7°C
4.56
3.73
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
6.04 kW
5.90 kW
COP Tj = +2°C
5.34
4.78
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
3.86 kW
3.50 kW
COP Tj = +7°C
5.54
5.64
Cdh Tj = +7 °C
0.980
0.980
Pdh Tj = 12°C
1.97 kW
1.99 kW
COP Tj = 12°C
4.64
5.99
Cdh Tj = +12 °C
0.970
0.960
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
7564 kWh
8397 kWh
Pdh Tj = -15°C (if TOL<-20°C)
13.30
12.58
COP Tj = -15°C (if TOL<-20°C)
4.16
3.14
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190 %
138 %
Prated
15.00 kW
14.55 kW
SCOP
4.95
3.65
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.42 kW
11.87 kW
COP Tj = -7°C
4.05
2.81
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
8.47 kW
8.48 kW
COP Tj = +2°C
5.01
3.62
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.34 kW
5.56 kW
COP Tj = +7°C
5.61
4.29
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
2.45 kW
2.47 kW
COP Tj = 12°C
5.18
4.38
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6266 kWh
8231 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
81 %
COP
2.00
Heating up time
1:18:30 h:min
Standby power input
102.2 W
Reference hot water temperature
58.1 °C
Mixed water at 40°C
233 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
81 %
COP
2.00
Heating up time
1:18:30 h:min
Standby power input
102.2 W
Reference hot water temperature
58.1 °C
Mixed water at 40°C
233 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
81 %
COP
2.00
Heating up time
1:18:30 h:min
Standby power input
102.2 W
Reference hot water temperature
58.1 °C
Mixed water at 40°C
233 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.30 kW
6.65 kW
El input
1.60 kW
2.28 kW
COP
4.55
2.91
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
140 %
Prated
15.00 kW
14.55 kW
SCOP
4.78
3.70
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
15.16 kW
13.36 kW
COP Tj = +2°C
3.63
2.58
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
10.48 kW
9.98 kW
COP Tj = +7°C
4.38
3.24
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
4.67 kW
4.61 kW
COP Tj = 12°C
5.50
4.48
Cdh Tj = +12 °C
0.980
0.980
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4192 kWh
5256 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
163 %
Prated
15.00 kW
14.55 kW
SCOP
4.89
4.27
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
9.89 kW
9.46 kW
COP Tj = -7°C
4.56
3.73
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
6.04 kW
5.90 kW
COP Tj = +2°C
5.34
4.78
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
3.86 kW
3.50 kW
COP Tj = +7°C
5.54
5.64
Cdh Tj = +7 °C
0.980
0.980
Pdh Tj = 12°C
1.97 kW
1.99 kW
COP Tj = 12°C
4.64
5.99
Cdh Tj = +12 °C
0.970
0.960
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
7564 kWh
8397 kWh
Pdh Tj = -15°C (if TOL<-20°C)
13.30
12.58
COP Tj = -15°C (if TOL<-20°C)
4.16
3.14
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190 %
138 %
Prated
15.00 kW
14.55 kW
SCOP
4.95
3.65
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.42 kW
11.87 kW
COP Tj = -7°C
4.05
2.81
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
8.47 kW
8.48 kW
COP Tj = +2°C
5.01
3.62
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.34 kW
5.56 kW
COP Tj = +7°C
5.61
4.29
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
2.45 kW
2.47 kW
COP Tj = 12°C
5.18
4.38
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6266 kWh
8231 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
81 %
COP
2.00
Heating up time
1:18:30 h:min
Standby power input
102.2 W
Reference hot water temperature
58.1 °C
Mixed water at 40°C
233 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
81 %
COP
2.00
Heating up time
1:18:30 h:min
Standby power input
102.2 W
Reference hot water temperature
58.1 °C
Mixed water at 40°C
233 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
81 %
COP
2.00
Heating up time
1:18:30 h:min
Standby power input
102.2 W
Reference hot water temperature
58.1 °C
Mixed water at 40°C
233 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.30 kW
6.65 kW
El input
1.60 kW
2.28 kW
COP
4.55
2.91
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
140 %
Prated
15.00 kW
14.55 kW
SCOP
4.78
3.70
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
15.16 kW
13.36 kW
COP Tj = +2°C
3.63
2.58
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
10.48 kW
9.98 kW
COP Tj = +7°C
4.38
3.24
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
4.67 kW
4.61 kW
COP Tj = 12°C
5.50
4.48
Cdh Tj = +12 °C
0.980
0.980
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4192 kWh
5256 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
163 %
Prated
15.00 kW
14.55 kW
SCOP
4.89
4.27
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
9.89 kW
9.46 kW
COP Tj = -7°C
4.56
3.73
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
6.04 kW
5.90 kW
COP Tj = +2°C
5.34
4.78
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
3.86 kW
3.50 kW
COP Tj = +7°C
5.54
5.64
Cdh Tj = +7 °C
0.980
0.980
Pdh Tj = 12°C
1.97 kW
1.99 kW
COP Tj = 12°C
4.64
5.99
Cdh Tj = +12 °C
0.970
0.960
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
7564 kWh
8397 kWh
Pdh Tj = -15°C (if TOL<-20°C)
13.30
12.58
COP Tj = -15°C (if TOL<-20°C)
4.16
3.14
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190 %
138 %
Prated
15.00 kW
14.55 kW
SCOP
4.95
3.65
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.42 kW
11.87 kW
COP Tj = -7°C
4.05
2.81
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
8.47 kW
8.48 kW
COP Tj = +2°C
5.01
3.62
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.34 kW
5.56 kW
COP Tj = +7°C
5.61
4.29
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
2.45 kW
2.47 kW
COP Tj = 12°C
5.18
4.38
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6266 kWh
8231 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.30 kW
6.65 kW
El input
1.60 kW
2.28 kW
COP
4.55
2.91
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
140 %
Prated
15.00 kW
14.55 kW
SCOP
4.78
3.70
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
15.16 kW
13.36 kW
COP Tj = +2°C
3.63
2.58
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
10.48 kW
9.98 kW
COP Tj = +7°C
4.38
3.24
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
4.67 kW
4.61 kW
COP Tj = 12°C
5.50
4.48
Cdh Tj = +12 °C
0.980
0.980
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4192 kWh
5256 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
163 %
Prated
15.00 kW
14.55 kW
SCOP
4.89
4.27
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
9.89 kW
9.46 kW
COP Tj = -7°C
4.56
3.73
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
6.04 kW
5.90 kW
COP Tj = +2°C
5.34
4.78
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
3.86 kW
3.50 kW
COP Tj = +7°C
5.54
5.64
Cdh Tj = +7 °C
0.980
0.980
Pdh Tj = 12°C
1.97 kW
1.99 kW
COP Tj = 12°C
4.64
5.99
Cdh Tj = +12 °C
0.970
0.960
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
7564 kWh
8397 kWh
Pdh Tj = -15°C (if TOL<-20°C)
13.30
12.58
COP Tj = -15°C (if TOL<-20°C)
4.16
3.14
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190 %
138 %
Prated
15.00 kW
14.55 kW
SCOP
4.95
3.65
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.42 kW
11.87 kW
COP Tj = -7°C
4.05
2.81
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
8.47 kW
8.48 kW
COP Tj = +2°C
5.01
3.62
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.34 kW
5.56 kW
COP Tj = +7°C
5.61
4.29
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
2.45 kW
2.47 kW
COP Tj = 12°C
5.18
4.38
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6266 kWh
8231 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.30 kW
6.65 kW
El input
1.60 kW
2.28 kW
COP
4.55
2.91
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
140 %
Prated
15.00 kW
14.55 kW
SCOP
4.78
3.70
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
15.16 kW
13.36 kW
COP Tj = +2°C
3.63
2.58
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
10.48 kW
9.98 kW
COP Tj = +7°C
4.38
3.24
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
4.67 kW
4.61 kW
COP Tj = 12°C
5.50
4.48
Cdh Tj = +12 °C
0.980
0.980
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4192 kWh
5256 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
163 %
Prated
15.00 kW
14.55 kW
SCOP
4.89
4.27
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
9.89 kW
9.46 kW
COP Tj = -7°C
4.56
3.73
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
6.04 kW
5.90 kW
COP Tj = +2°C
5.34
4.78
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
3.86 kW
3.50 kW
COP Tj = +7°C
5.54
5.64
Cdh Tj = +7 °C
0.980
0.980
Pdh Tj = 12°C
1.97 kW
1.99 kW
COP Tj = 12°C
4.64
5.99
Cdh Tj = +12 °C
0.970
0.960
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
7564 kWh
8397 kWh
Pdh Tj = -15°C (if TOL<-20°C)
13.30
12.58
COP Tj = -15°C (if TOL<-20°C)
4.16
3.14
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190 %
138 %
Prated
15.00 kW
14.55 kW
SCOP
4.95
3.65
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.42 kW
11.87 kW
COP Tj = -7°C
4.05
2.81
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
8.47 kW
8.48 kW
COP Tj = +2°C
5.01
3.62
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.34 kW
5.56 kW
COP Tj = +7°C
5.61
4.29
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
2.45 kW
2.47 kW
COP Tj = 12°C
5.18
4.38
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6266 kWh
8231 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.30 kW
6.65 kW
El input
1.60 kW
2.28 kW
COP
4.55
2.91
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
140 %
Prated
15.00 kW
14.55 kW
SCOP
4.78
3.70
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
15.16 kW
13.36 kW
COP Tj = +2°C
3.63
2.58
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
10.48 kW
9.98 kW
COP Tj = +7°C
4.38
3.24
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
4.67 kW
4.61 kW
COP Tj = 12°C
5.50
4.48
Cdh Tj = +12 °C
0.980
0.980
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4192 kWh
5256 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
163 %
Prated
15.00 kW
14.55 kW
SCOP
4.89
4.27
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
9.89 kW
9.46 kW
COP Tj = -7°C
4.56
3.73
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
6.04 kW
5.90 kW
COP Tj = +2°C
5.34
4.78
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
3.86 kW
3.50 kW
COP Tj = +7°C
5.54
5.64
Cdh Tj = +7 °C
0.980
0.980
Pdh Tj = 12°C
1.97 kW
1.99 kW
COP Tj = 12°C
4.64
5.99
Cdh Tj = +12 °C
0.970
0.960
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
7564 kWh
8397 kWh
Pdh Tj = -15°C (if TOL<-20°C)
13.30
12.58
COP Tj = -15°C (if TOL<-20°C)
4.16
3.14
Cdh Tj = -15 °C
0.99
0.99
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190 %
138 %
Prated
15.00 kW
14.55 kW
SCOP
4.95
3.65
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.42 kW
11.87 kW
COP Tj = -7°C
4.05
2.81
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
8.47 kW
8.48 kW
COP Tj = +2°C
5.01
3.62
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
5.34 kW
5.56 kW
COP Tj = +7°C
5.61
4.29
Cdh Tj = +7 °C
0.980
0.990
Pdh Tj = 12°C
2.45 kW
2.47 kW
COP Tj = 12°C
5.18
4.38
Cdh Tj = +12 °C
0.970
0.970
Pdh Tj = Tbiv
15.16 kW
13.95 kW
COP Tj = Tbiv
3.63
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.16 kW
13.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.63
2.56
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6266 kWh
8231 kWh