7,500 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
47.35 kW
47.69 kW
El input
10.89 kW
15.43 kW
COP
4.35
3.09
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
54 dB(A)
54 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
192 %
159 %
Prated
47.35 kW
47.69 kW
SCOP
5
4.16
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
41.89 kW
42.19 kW
COP Tj = -7°C
4.5
3.34
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
25.31 kW
25.49 kW
COP Tj = +2°C
5.12
4.26
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
25.32 kW
25.49 kW
COP Tj = +7°C
5.24
4.53
Cdh Tj = +7 °C
1.00
1.00
Pdh Tj = 12°C
25.32 kW
25.5 kW
COP Tj = 12°C
5.35
4.98
Cdh Tj = +12 °C
1.00
1.00
Pdh Tj = Tbiv
47.35 kW
47.69 kW
COP Tj = Tbiv
4.35
3.09
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
47.35 kW
47.69 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.35
3.09
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.00
1.00
WTOL
68 °C
68 °C
Poff
11 W
11 W
PTO
11 W
11 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0 kW
0 kW
Annual energy consumption Qhe
19560 kWh
23657 kWh