2,300 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.48 kW
13.57 kW
El input
1.32 kW
5.75 kW
COP
4.92
2.36
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
176 %
128 %
Prated
11.02 kW
9.35 kW
SCOP
4.48
3.28
Tbiv
-10 °C
-9 °C
TOL
-10 °C
-9 °C
Pdh Tj = -7°C
9.94 kW
8.39 kW
COP Tj = -7°C
2.81
2.01
Cdh Tj = -7 °C
0.998
0.998
Pdh Tj = +2°C
5.94 kW
5.03 kW
COP Tj = +2°C
4.61
3.21
Cdh Tj = +2 °C
0.995
0.996
Pdh Tj = +7°C
6.73 kW
6.55 kW
COP Tj = +7°C
5.55
4.43
Cdh Tj = +7 °C
0.994
0.995
Pdh Tj = 12°C
7.11 kW
7.26 kW
COP Tj = 12°C
5.70
5.11
Cdh Tj = +12 °C
0.994
0.995
Pdh Tj = Tbiv
11.02 kW
9.35 kW
COP Tj = Tbiv
2.49
1.65
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.02 kW
9.35 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.49
1.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.998
0.999
WTOL
57 °C
57 °C
Poff
7 W
7 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
9.35 kW
Annual energy consumption Qhe
5084 kWh
5889 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.48 kW
13.57 kW
El input
1.32 kW
5.75 kW
COP
4.92
2.36
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
176 %
128 %
Prated
11.02 kW
9.35 kW
SCOP
4.48
3.28
Tbiv
-10 °C
-9 °C
TOL
-10 °C
-9 °C
Pdh Tj = -7°C
9.94 kW
8.39 kW
COP Tj = -7°C
2.81
2.01
Cdh Tj = -7 °C
0.998
0.998
Pdh Tj = +2°C
5.94 kW
5.03 kW
COP Tj = +2°C
4.61
3.21
Cdh Tj = +2 °C
0.995
0.996
Pdh Tj = +7°C
6.73 kW
6.55 kW
COP Tj = +7°C
5.55
4.43
Cdh Tj = +7 °C
0.994
0.995
Pdh Tj = 12°C
7.11 kW
7.26 kW
COP Tj = 12°C
5.70
5.11
Cdh Tj = +12 °C
0.994
0.995
Pdh Tj = Tbiv
11.02 kW
9.35 kW
COP Tj = Tbiv
2.49
1.65
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.02 kW
9.35 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.49
1.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.998
0.999
WTOL
57 °C
57 °C
Poff
7 W
7 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5084 kWh
5889 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.48 kW
13.57 kW
El input
1.32 kW
5.75 kW
COP
4.92
2.36
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
176 %
128 %
Prated
11.02 kW
9.35 kW
SCOP
4.48
3.28
Tbiv
-10 °C
-9 °C
TOL
-10 °C
-9 °C
Pdh Tj = -7°C
9.94 kW
8.39 kW
COP Tj = -7°C
2.81
2.01
Cdh Tj = -7 °C
0.998
0.998
Pdh Tj = +2°C
5.94 kW
5.03 kW
COP Tj = +2°C
4.61
3.21
Cdh Tj = +2 °C
0.995
0.996
Pdh Tj = +7°C
6.73 kW
6.55 kW
COP Tj = +7°C
5.55
4.43
Cdh Tj = +7 °C
0.994
0.995
Pdh Tj = 12°C
7.11 kW
7.26 kW
COP Tj = 12°C
5.70
5.11
Cdh Tj = +12 °C
0.994
0.995
Pdh Tj = Tbiv
11.02 kW
9.35 kW
COP Tj = Tbiv
2.49
1.65
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.02 kW
9.35 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.49
1.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.998
0.999
WTOL
57 °C
57 °C
Poff
7 W
7 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
9.35 kW
Annual energy consumption Qhe
5084 kWh
5889 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
82 %
COP
1.92
Heating up time
01:38 h:min
Standby power input
70.0 W
Reference hot water temperature
52.3 °C
Mixed water at 40°C
267 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.48 kW
13.57 kW
El input
1.32 kW
5.75 kW
COP
4.92
2.36
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
176 %
128 %
Prated
11.02 kW
9.35 kW
SCOP
4.48
3.28
Tbiv
-10 °C
-9 °C
TOL
-10 °C
-9 °C
Pdh Tj = -7°C
9.94 kW
8.39 kW
COP Tj = -7°C
2.81
2.01
Cdh Tj = -7 °C
0.998
0.998
Pdh Tj = +2°C
5.94 kW
5.03 kW
COP Tj = +2°C
4.61
3.21
Cdh Tj = +2 °C
0.995
0.996
Pdh Tj = +7°C
6.73 kW
6.55 kW
COP Tj = +7°C
5.55
4.43
Cdh Tj = +7 °C
0.994
0.995
Pdh Tj = 12°C
7.11 kW
7.26 kW
COP Tj = 12°C
5.70
5.11
Cdh Tj = +12 °C
0.994
0.995
Pdh Tj = Tbiv
11.02 kW
9.35 kW
COP Tj = Tbiv
2.49
1.65
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.02 kW
9.35 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.49
1.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.998
0.999
WTOL
57 °C
57 °C
Poff
7 W
7 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
9.35 kW
Annual energy consumption Qhe
5084 kWh
5889 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
76 %
COP
1.76
Heating up time
01:36 h:min
Standby power input
75.0 W
Reference hot water temperature
51.2 °C
Mixed water at 40°C
251 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.41 kW
13.45 kW
El input
1.32 kW
5.69 kW
COP
4.85
2.37
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
126 %
Prated
11.70 kW
9.01 kW
SCOP
4.62
3.22
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.04 kW
7.98 kW
COP Tj = -7°C
2.85
2.04
Cdh Tj = -7 °C
0.993
0.993
Pdh Tj = +2°C
6.24 kW
5.04 kW
COP Tj = +2°C
4.69
3.19
Cdh Tj = +2 °C
0.980
0.984
Pdh Tj = +7°C
6.79 kW
6.15 kW
COP Tj = +7°C
5.82
4.07
Cdh Tj = +7 °C
0.978
0.983
Pdh Tj = 12°C
7.62 kW
7.56 kW
COP Tj = 12°C
6.94
5.73
Cdh Tj = +12 °C
0.976
0.980
Pdh Tj = Tbiv
11.70 kW
9.01 kW
COP Tj = Tbiv
2.72
1.62
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.70 kW
9.01 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.72
1.62
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.995
WTOL
57 °C
57 °C
Poff
26 W
26 W
PTO
26 W
26 W
PSB
26 W
26 W
PCK
53 W
53 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5234 kWh
5777 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.41 kW
13.45 kW
El input
1.32 kW
5.69 kW
COP
4.85
2.37
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
126 %
Prated
11.70 kW
9.01 kW
SCOP
4.62
3.22
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.04 kW
7.98 kW
COP Tj = -7°C
2.85
2.04
Cdh Tj = -7 °C
0.993
0.993
Pdh Tj = +2°C
6.24 kW
5.04 kW
COP Tj = +2°C
4.69
3.19
Cdh Tj = +2 °C
0.980
0.984
Pdh Tj = +7°C
6.79 kW
6.15 kW
COP Tj = +7°C
5.82
4.07
Cdh Tj = +7 °C
0.978
0.983
Pdh Tj = 12°C
7.62 kW
7.56 kW
COP Tj = 12°C
6.94
5.73
Cdh Tj = +12 °C
0.976
0.980
Pdh Tj = Tbiv
11.70 kW
9.01 kW
COP Tj = Tbiv
2.72
1.62
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.70 kW
9.01 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.72
1.62
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.995
WTOL
57 °C
57 °C
Poff
26 W
26 W
PTO
26 W
26 W
PSB
26 W
26 W
PCK
53 W
53 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5234 kWh
5777 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.41 kW
13.45 kW
El input
1.32 kW
5.69 kW
COP
4.85
2.37
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
126 %
Prated
11.70 kW
9.01 kW
SCOP
4.62
3.22
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.04 kW
7.98 kW
COP Tj = -7°C
2.85
2.04
Cdh Tj = -7 °C
0.993
0.993
Pdh Tj = +2°C
6.24 kW
5.04 kW
COP Tj = +2°C
4.69
3.19
Cdh Tj = +2 °C
0.980
0.984
Pdh Tj = +7°C
6.79 kW
6.15 kW
COP Tj = +7°C
5.82
4.07
Cdh Tj = +7 °C
0.978
0.983
Pdh Tj = 12°C
7.62 kW
7.56 kW
COP Tj = 12°C
6.94
5.73
Cdh Tj = +12 °C
0.976
0.980
Pdh Tj = Tbiv
11.70 kW
9.01 kW
COP Tj = Tbiv
2.72
1.62
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.70 kW
9.01 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.72
1.62
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.995
WTOL
57 °C
57 °C
Poff
26 W
26 W
PTO
26 W
26 W
PSB
26 W
26 W
PCK
53 W
53 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5234 kWh
5777 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
82 %
COP
1.89
Heating up time
01:20 h:min
Standby power input
80.0 W
Reference hot water temperature
52.1 °C
Mixed water at 40°C
251 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.41 kW
13.45 kW
El input
1.32 kW
5.69 kW
COP
4.85
2.37
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
182 %
126 %
Prated
11.70 kW
9.01 kW
SCOP
4.62
3.22
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.04 kW
7.98 kW
COP Tj = -7°C
2.85
2.04
Cdh Tj = -7 °C
0.993
0.993
Pdh Tj = +2°C
6.24 kW
5.04 kW
COP Tj = +2°C
4.69
3.19
Cdh Tj = +2 °C
0.980
0.984
Pdh Tj = +7°C
6.79 kW
6.15 kW
COP Tj = +7°C
5.82
4.07
Cdh Tj = +7 °C
0.978
0.983
Pdh Tj = 12°C
7.62 kW
7.56 kW
COP Tj = 12°C
6.94
5.73
Cdh Tj = +12 °C
0.976
0.980
Pdh Tj = Tbiv
11.70 kW
9.01 kW
COP Tj = Tbiv
2.72
1.62
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.70 kW
9.01 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.72
1.62
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.994
0.995
WTOL
57 °C
57 °C
Poff
26 W
26 W
PTO
26 W
26 W
PSB
26 W
26 W
PCK
53 W
53 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5234 kWh
5777 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
75 %
COP
1.74
Heating up time
01:18 h:min
Standby power input
85.7 W
Reference hot water temperature
51.1 °C
Mixed water at 40°C
236 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.48 kW
14.44 kW
El input
1.32 kW
6.23 kW
COP
4.92
2.32
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
171 %
134 %
Prated
13.04 kW
11.50 kW
SCOP
4.35
3.43
Tbiv
-10 °C
-9 °C
TOL
-10 °C
-9 °C
Pdh Tj = -7°C
10.79 kW
10.00 kW
COP Tj = -7°C
2.74
1.96
Cdh Tj = -7 °C
0.998
0.999
Pdh Tj = +2°C
6.91 kW
6.01 kW
COP Tj = +2°C
4.30
3.47
Cdh Tj = +2 °C
0.996
0.996
Pdh Tj = +7°C
6.61 kW
6.56 kW
COP Tj = +7°C
5.49
4.55
Cdh Tj = +7 °C
0.994
0.995
Pdh Tj = 12°C
7.60 kW
7.24 kW
COP Tj = 12°C
6.62
5.20
Cdh Tj = +12 °C
0.994
0.995
Pdh Tj = Tbiv
13.05 kW
11.07 kW
COP Tj = Tbiv
2.60
1.72
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.05 kW
11.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.999
0.999
WTOL
57 °C
57 °C
Poff
7 W
7 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
11.50 kW
Annual energy consumption Qhe
6194 kWh
6924 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.48 kW
14.44 kW
El input
1.32 kW
6.23 kW
COP
4.92
2.32
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
171 %
134 %
Prated
13.04 kW
11.50 kW
SCOP
4.35
3.43
Tbiv
-10 °C
-9 °C
TOL
-10 °C
-9 °C
Pdh Tj = -7°C
10.79 kW
10.00 kW
COP Tj = -7°C
2.74
1.96
Cdh Tj = -7 °C
0.998
0.999
Pdh Tj = +2°C
6.91 kW
6.01 kW
COP Tj = +2°C
4.30
3.47
Cdh Tj = +2 °C
0.996
0.996
Pdh Tj = +7°C
6.61 kW
6.56 kW
COP Tj = +7°C
5.49
4.55
Cdh Tj = +7 °C
0.994
0.995
Pdh Tj = 12°C
7.60 kW
7.24 kW
COP Tj = 12°C
6.62
5.20
Cdh Tj = +12 °C
0.994
0.995
Pdh Tj = Tbiv
13.05 kW
11.07 kW
COP Tj = Tbiv
2.60
1.72
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.05 kW
11.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.999
0.999
WTOL
57 °C
57 °C
Poff
7 W
7 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6194 kWh
6924 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.48 kW
14.44 kW
El input
1.32 kW
6.23 kW
COP
4.92
2.32
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
171 %
134 %
Prated
13.04 kW
11.50 kW
SCOP
4.35
3.43
Tbiv
-10 °C
-9 °C
TOL
-10 °C
-9 °C
Pdh Tj = -7°C
10.79 kW
10.00 kW
COP Tj = -7°C
2.74
1.96
Cdh Tj = -7 °C
0.998
0.999
Pdh Tj = +2°C
6.91 kW
6.01 kW
COP Tj = +2°C
4.30
3.47
Cdh Tj = +2 °C
0.996
0.996
Pdh Tj = +7°C
6.61 kW
6.56 kW
COP Tj = +7°C
5.49
4.55
Cdh Tj = +7 °C
0.994
0.995
Pdh Tj = 12°C
7.60 kW
7.24 kW
COP Tj = 12°C
6.62
5.20
Cdh Tj = +12 °C
0.994
0.995
Pdh Tj = Tbiv
13.05 kW
11.07 kW
COP Tj = Tbiv
2.60
1.72
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.05 kW
11.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.999
0.999
WTOL
57 °C
57 °C
Poff
7 W
7 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
11.50 kW
Annual energy consumption Qhe
6194 kWh
6924 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
82 %
COP
1.92
Heating up time
01:38 h:min
Standby power input
70.0 W
Reference hot water temperature
52.3 °C
Mixed water at 40°C
267 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.48 kW
14.44 kW
El input
1.32 kW
6.23 kW
COP
4.92
2.32
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
171 %
134 %
Prated
13.04 kW
11.50 kW
SCOP
4.35
3.43
Tbiv
-10 °C
-9 °C
TOL
-10 °C
-9 °C
Pdh Tj = -7°C
10.79 kW
10.00 kW
COP Tj = -7°C
2.74
1.96
Cdh Tj = -7 °C
0.998
0.999
Pdh Tj = +2°C
6.91 kW
6.01 kW
COP Tj = +2°C
4.30
3.47
Cdh Tj = +2 °C
0.996
0.996
Pdh Tj = +7°C
6.61 kW
6.56 kW
COP Tj = +7°C
5.49
4.55
Cdh Tj = +7 °C
0.994
0.995
Pdh Tj = 12°C
7.60 kW
7.24 kW
COP Tj = 12°C
6.62
5.20
Cdh Tj = +12 °C
0.994
0.995
Pdh Tj = Tbiv
13.05 kW
11.07 kW
COP Tj = Tbiv
2.60
1.72
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.05 kW
11.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.999
0.999
WTOL
57 °C
57 °C
Poff
7 W
7 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
11.50 kW
Annual energy consumption Qhe
6194 kWh
6924 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
76 %
COP
1.76
Heating up time
01:36 h:min
Standby power input
75.0 W
Reference hot water temperature
51.2 °C
Mixed water at 40°C
251 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.41 kW
14.29 kW
El input
1.32 kW
6.16 kW
COP
4.85
2.32
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
167 %
129 %
Prated
12.32 kW
11.30 kW
SCOP
4.25
3.29
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.78 kW
10.02 kW
COP Tj = -7°C
2.79
2.03
Cdh Tj = -7 °C
0.993
0.995
Pdh Tj = +2°C
6.45 kW
6.06 kW
COP Tj = +2°C
4.45
3.28
Cdh Tj = +2 °C
0.982
0.986
Pdh Tj = +7°C
6.29 kW
6.40 kW
COP Tj = +7°C
4.93
4.27
Cdh Tj = +7 °C
0.980
0.983
Pdh Tj = 12°C
6.99 kW
7.28 kW
COP Tj = 12°C
5.64
5.09
Cdh Tj = +12 °C
0.979
0.982
Pdh Tj = Tbiv
12.33 kW
11.30 kW
COP Tj = Tbiv
2.48
1.81
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.33 kW
11.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.48
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
57 °C
57 °C
Poff
26 W
26 W
PTO
26 W
26 W
PSB
26 W
26 W
PCK
53 W
53 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5994 kWh
7088 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.41 kW
14.29 kW
El input
1.32 kW
6.16 kW
COP
4.85
2.32
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
167 %
129 %
Prated
12.32 kW
11.30 kW
SCOP
4.25
3.29
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.78 kW
10.02 kW
COP Tj = -7°C
2.79
2.03
Cdh Tj = -7 °C
0.993
0.995
Pdh Tj = +2°C
6.45 kW
6.06 kW
COP Tj = +2°C
4.45
3.28
Cdh Tj = +2 °C
0.982
0.986
Pdh Tj = +7°C
6.29 kW
6.40 kW
COP Tj = +7°C
4.93
4.27
Cdh Tj = +7 °C
0.980
0.983
Pdh Tj = 12°C
6.99 kW
7.28 kW
COP Tj = 12°C
5.64
5.09
Cdh Tj = +12 °C
0.979
0.982
Pdh Tj = Tbiv
12.33 kW
11.30 kW
COP Tj = Tbiv
2.48
1.81
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.33 kW
11.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.48
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
57 °C
57 °C
Poff
26 W
26 W
PTO
26 W
26 W
PSB
26 W
26 W
PCK
53 W
53 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5994 kWh
7088 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.41 kW
14.29 kW
El input
1.32 kW
6.16 kW
COP
4.85
2.32
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
167 %
129 %
Prated
12.32 kW
11.30 kW
SCOP
4.25
3.29
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.78 kW
10.02 kW
COP Tj = -7°C
2.79
2.03
Cdh Tj = -7 °C
0.993
0.995
Pdh Tj = +2°C
6.45 kW
6.06 kW
COP Tj = +2°C
4.45
3.28
Cdh Tj = +2 °C
0.982
0.986
Pdh Tj = +7°C
6.29 kW
6.40 kW
COP Tj = +7°C
4.93
4.27
Cdh Tj = +7 °C
0.980
0.983
Pdh Tj = 12°C
6.99 kW
7.28 kW
COP Tj = 12°C
5.64
5.09
Cdh Tj = +12 °C
0.979
0.982
Pdh Tj = Tbiv
12.33 kW
11.30 kW
COP Tj = Tbiv
2.48
1.81
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.33 kW
11.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.48
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
57 °C
57 °C
Poff
26 W
26 W
PTO
26 W
26 W
PSB
26 W
26 W
PCK
53 W
53 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5994 kWh
7088 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
75 %
COP
1.74
Heating up time
01:18 h:min
Standby power input
85.7 W
Reference hot water temperature
51.1 °C
Mixed water at 40°C
236 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.41 kW
14.29 kW
El input
1.32 kW
6.16 kW
COP
4.85
2.32
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
167 %
129 %
Prated
12.32 kW
11.30 kW
SCOP
4.25
3.29
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.78 kW
10.02 kW
COP Tj = -7°C
2.79
2.03
Cdh Tj = -7 °C
0.993
0.995
Pdh Tj = +2°C
6.45 kW
6.06 kW
COP Tj = +2°C
4.45
3.28
Cdh Tj = +2 °C
0.982
0.986
Pdh Tj = +7°C
6.29 kW
6.40 kW
COP Tj = +7°C
4.93
4.27
Cdh Tj = +7 °C
0.980
0.983
Pdh Tj = 12°C
6.99 kW
7.28 kW
COP Tj = 12°C
5.64
5.09
Cdh Tj = +12 °C
0.979
0.982
Pdh Tj = Tbiv
12.33 kW
11.30 kW
COP Tj = Tbiv
2.48
1.81
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.33 kW
11.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.48
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
57 °C
57 °C
Poff
26 W
26 W
PTO
26 W
26 W
PSB
26 W
26 W
PCK
53 W
53 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5994 kWh
7088 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
82 %
COP
1.89
Heating up time
01:20 h:min
Standby power input
80.0 W
Reference hot water temperature
52.1 °C
Mixed water at 40°C
251 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.48 kW
15.30 kW
El input
1.32 kW
6.74 kW
COP
4.92
2.27
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
171 %
134 %
Prated
13.04 kW
11.50 kW
SCOP
4.35
3.43
Tbiv
-10 °C
-9 °C
TOL
-10 °C
-9 °C
Pdh Tj = -7°C
10.79 kW
10.00 kW
COP Tj = -7°C
2.74
1.96
Cdh Tj = -7 °C
0.998
0.999
Pdh Tj = +2°C
6.91 kW
6.01 kW
COP Tj = +2°C
4.30
3.47
Cdh Tj = +2 °C
0.996
0.996
Pdh Tj = +7°C
6.61 kW
6.56 kW
COP Tj = +7°C
5.49
4.55
Cdh Tj = +7 °C
0.994
0.995
Pdh Tj = 12°C
7.60 kW
7.24 kW
COP Tj = 12°C
6.62
5.20
Cdh Tj = +12 °C
0.994
0.995
Pdh Tj = Tbiv
13.05 kW
11.07 kW
COP Tj = Tbiv
2.60
1.72
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.05 kW
11.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.999
0.999
WTOL
57 °C
57 °C
Poff
7 W
7 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6194 kWh
6924 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.48 kW
15.30 kW
El input
1.32 kW
6.74 kW
COP
4.92
2.27
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
171 %
134 %
Prated
13.04 kW
11.50 kW
SCOP
4.35
3.43
Tbiv
-10 °C
-9 °C
TOL
-10 °C
-9 °C
Pdh Tj = -7°C
10.79 kW
10.00 kW
COP Tj = -7°C
2.74
1.96
Cdh Tj = -7 °C
0.998
0.999
Pdh Tj = +2°C
6.91 kW
6.01 kW
COP Tj = +2°C
4.30
3.47
Cdh Tj = +2 °C
0.996
0.996
Pdh Tj = +7°C
6.61 kW
6.56 kW
COP Tj = +7°C
5.49
4.55
Cdh Tj = +7 °C
0.994
0.995
Pdh Tj = 12°C
7.60 kW
7.24 kW
COP Tj = 12°C
6.62
5.20
Cdh Tj = +12 °C
0.994
0.995
Pdh Tj = Tbiv
13.05 kW
11.07 kW
COP Tj = Tbiv
2.60
1.72
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.05 kW
11.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.999
0.999
WTOL
57 °C
57 °C
Poff
7 W
7 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
11.50 kW
Annual energy consumption Qhe
6194 kWh
6924 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.48 kW
15.30 kW
El input
1.32 kW
6.74 kW
COP
4.92
2.27
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
171 %
134 %
Prated
13.04 kW
11.50 kW
SCOP
4.35
3.43
Tbiv
-10 °C
-9 °C
TOL
-10 °C
-9 °C
Pdh Tj = -7°C
10.79 kW
10.00 kW
COP Tj = -7°C
2.74
1.96
Cdh Tj = -7 °C
0.998
0.999
Pdh Tj = +2°C
6.91 kW
6.01 kW
COP Tj = +2°C
4.30
3.47
Cdh Tj = +2 °C
0.996
0.996
Pdh Tj = +7°C
6.61 kW
6.56 kW
COP Tj = +7°C
5.49
4.55
Cdh Tj = +7 °C
0.994
0.995
Pdh Tj = 12°C
7.60 kW
7.24 kW
COP Tj = 12°C
6.62
5.20
Cdh Tj = +12 °C
0.994
0.995
Pdh Tj = Tbiv
13.05 kW
11.07 kW
COP Tj = Tbiv
2.60
1.72
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.05 kW
11.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.999
0.999
WTOL
57 °C
57 °C
Poff
7 W
7 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
11.50 kW
Annual energy consumption Qhe
6194 kWh
6924 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
82 %
COP
1.92
Heating up time
01:38 h:min
Standby power input
70.0 W
Reference hot water temperature
52.3 °C
Mixed water at 40°C
267 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.48 kW
15.30 kW
El input
1.32 kW
6.74 kW
COP
4.92
2.27
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
171 %
134 %
Prated
13.04 kW
11.50 kW
SCOP
4.35
3.43
Tbiv
-10 °C
-9 °C
TOL
-10 °C
-9 °C
Pdh Tj = -7°C
10.79 kW
10.00 kW
COP Tj = -7°C
2.74
1.96
Cdh Tj = -7 °C
0.998
0.999
Pdh Tj = +2°C
6.91 kW
6.01 kW
COP Tj = +2°C
4.30
3.47
Cdh Tj = +2 °C
0.996
0.996
Pdh Tj = +7°C
6.61 kW
6.56 kW
COP Tj = +7°C
5.49
4.55
Cdh Tj = +7 °C
0.994
0.995
Pdh Tj = 12°C
7.60 kW
7.24 kW
COP Tj = 12°C
6.62
5.20
Cdh Tj = +12 °C
0.994
0.995
Pdh Tj = Tbiv
13.05 kW
11.07 kW
COP Tj = Tbiv
2.60
1.72
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.05 kW
11.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.72
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.999
0.999
WTOL
57 °C
57 °C
Poff
7 W
7 W
PTO
7 W
7 W
PSB
7 W
7 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
11.50 kW
Annual energy consumption Qhe
6194 kWh
6924 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
76 %
COP
1.76
Heating up time
01:36 h:min
Standby power input
75.0 W
Reference hot water temperature
51.2 °C
Mixed water at 40°C
251 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.41 kW
15.10 kW
El input
1.32 kW
6.64 kW
COP
4.85
2.27
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
167 %
129 %
Prated
12.32 kW
11.30 kW
SCOP
4.25
3.29
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.78 kW
10.02 kW
COP Tj = -7°C
2.79
2.03
Cdh Tj = -7 °C
0.993
0.995
Pdh Tj = +2°C
6.45 kW
6.06 kW
COP Tj = +2°C
4.45
3.28
Cdh Tj = +2 °C
0.982
0.986
Pdh Tj = +7°C
6.29 kW
6.40 kW
COP Tj = +7°C
4.93
4.27
Cdh Tj = +7 °C
0.980
0.983
Pdh Tj = 12°C
6.99 kW
7.28 kW
COP Tj = 12°C
5.64
5.09
Cdh Tj = +12 °C
0.979
0.982
Pdh Tj = Tbiv
12.33 kW
11.30 kW
COP Tj = Tbiv
2.48
1.81
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.33 kW
11.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.48
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
57 °C
57 °C
Poff
26 W
26 W
PTO
26 W
26 W
PSB
26 W
26 W
PCK
53 W
53 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5994 kWh
7088 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.41 kW
15.10 kW
El input
1.32 kW
6.64 kW
COP
4.85
2.27
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
167 %
129 %
Prated
12.32 kW
11.30 kW
SCOP
4.25
3.29
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.78 kW
10.02 kW
COP Tj = -7°C
2.79
2.03
Cdh Tj = -7 °C
0.993
0.995
Pdh Tj = +2°C
6.45 kW
6.06 kW
COP Tj = +2°C
4.45
3.28
Cdh Tj = +2 °C
0.982
0.986
Pdh Tj = +7°C
6.29 kW
6.40 kW
COP Tj = +7°C
4.93
4.27
Cdh Tj = +7 °C
0.980
0.983
Pdh Tj = 12°C
6.99 kW
7.28 kW
COP Tj = 12°C
5.64
5.09
Cdh Tj = +12 °C
0.979
0.982
Pdh Tj = Tbiv
12.33 kW
11.30 kW
COP Tj = Tbiv
2.48
1.81
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.33 kW
11.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.48
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
57 °C
57 °C
Poff
26 W
26 W
PTO
26 W
26 W
PSB
26 W
26 W
PCK
53 W
53 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5994 kWh
7088 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.41 kW
15.10 kW
El input
1.32 kW
6.64 kW
COP
4.85
2.27
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
167 %
129 %
Prated
12.32 kW
11.30 kW
SCOP
4.25
3.29
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.78 kW
10.02 kW
COP Tj = -7°C
2.79
2.03
Cdh Tj = -7 °C
0.993
0.995
Pdh Tj = +2°C
6.45 kW
6.06 kW
COP Tj = +2°C
4.45
3.28
Cdh Tj = +2 °C
0.982
0.986
Pdh Tj = +7°C
6.29 kW
6.40 kW
COP Tj = +7°C
4.93
4.27
Cdh Tj = +7 °C
0.980
0.983
Pdh Tj = 12°C
6.99 kW
7.28 kW
COP Tj = 12°C
5.64
5.09
Cdh Tj = +12 °C
0.979
0.982
Pdh Tj = Tbiv
12.33 kW
11.30 kW
COP Tj = Tbiv
2.48
1.81
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.33 kW
11.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.48
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
57 °C
57 °C
Poff
26 W
26 W
PTO
26 W
26 W
PSB
26 W
26 W
PCK
53 W
53 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5994 kWh
7088 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
82 %
COP
1.89
Heating up time
01:20 h:min
Standby power input
80.0 W
Reference hot water temperature
52.1 °C
Mixed water at 40°C
251 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.41 kW
15.10 kW
El input
1.32 kW
6.64 kW
COP
4.85
2.27
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
167 %
129 %
Prated
12.32 kW
11.30 kW
SCOP
4.25
3.29
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.78 kW
10.02 kW
COP Tj = -7°C
2.79
2.03
Cdh Tj = -7 °C
0.993
0.995
Pdh Tj = +2°C
6.45 kW
6.06 kW
COP Tj = +2°C
4.45
3.28
Cdh Tj = +2 °C
0.982
0.986
Pdh Tj = +7°C
6.29 kW
6.40 kW
COP Tj = +7°C
4.93
4.27
Cdh Tj = +7 °C
0.980
0.983
Pdh Tj = 12°C
6.99 kW
7.28 kW
COP Tj = 12°C
5.64
5.09
Cdh Tj = +12 °C
0.979
0.982
Pdh Tj = Tbiv
12.33 kW
11.30 kW
COP Tj = Tbiv
2.48
1.81
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.33 kW
11.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.48
1.81
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
57 °C
57 °C
Poff
26 W
26 W
PTO
26 W
26 W
PSB
26 W
26 W
PCK
53 W
53 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5994 kWh
7088 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
75 %
COP
1.74
Heating up time
01:18 h:min
Standby power input
85.7 W
Reference hot water temperature
51.1 °C
Mixed water at 40°C
236 l