6,500 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
40.00 kW
38.40 kW
El input
9.84 kW
14.20 kW
COP
4.07
2.70
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
9.54 kW
Cooling capacity
29.60
EER
3.10
EN 14825
+7°C/+12°C
Pdesignc
29.60 kW
SEER
4.80
Pdc Tj = 35°C
29.60 kW
EER Tj = 35°C
3.10
Pdc Tj = 30°C
21.70 kW
EER Tj = 30°C
4.14
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
15.00 kW
EER Tj = 25°C
5.00
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
16.19 kW
EER Tj = 20°C
6.57
Cdc Tj = 20 °C
1.000
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
3700 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
74 dB(A)
74 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
167 %
126 %
Prated
31.00 kW
29.00 kW
SCOP
4.25
3.23
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-9 °C
Pdh Tj = -7°C
27.10 kW
25.80 kW
COP Tj = -7°C
2.49
1.72
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
17.60 kW
17.10 kW
COP Tj = +2°C
4.23
3.10
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
18.00 kW
20.20 kW
COP Tj = +7°C
5.54
4.59
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
20.20 kW
22.90 kW
COP Tj = 12°C
7.11
7.25
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
27.10 kW
25.80 kW
COP Tj = Tbiv
2.49
1.72
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
26.90 kW
25.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.17
1.51
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
58 °C
58 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
38 W
38 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
4.10 kW
29.00 kW
Annual energy consumption Qhe
14894 kWh
18669 kWh