5,000 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
18.32 kW
18.10 kW
El input
3.96 kW
6.63 kW
COP
4.63
2.73
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
226 %
157 %
Prated
17.67 kW
18.07 kW
SCOP
5.74
4.00
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
17.67 kW
18.07 kW
COP Tj = +2°C
3.53
2.12
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
11.36 kW
11.62 kW
COP Tj = +7°C
5.16
3.49
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
5.45 kW
5.35 kW
COP Tj = 12°C
7.01
5.09
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
11.36 kW
11.62 kW
COP Tj = Tbiv
5.16
3.49
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
17.67 kW
18.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.53
2.12
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
18 W
18 W
PTO
96 W
96 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4116 kWh
6041 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
146 %
97 %
Prated
17.76 kW
18.38 kW
SCOP
3.73
2.50
Tbiv
-15 °C
-7 °C
TOL
-22 °C
-15 °C
Pdh Tj = -7°C
11.21 kW
11.13 kW
COP Tj = -7°C
3.09
1.98
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
6.64 kW
6.65 kW
COP Tj = +2°C
4.50
3.44
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
4.77 kW
4.66 kW
COP Tj = +7°C
5.85
4.35
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.95 kW
3.74 kW
COP Tj = 12°C
7.18
5.68
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
14.49 kW
11.13 kW
COP Tj = Tbiv
2.42
1.98
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.14 kW
13.56 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.67
1.21
WTOL
60 °C
60 °C
Poff
20 W
20 W
PTO
96 W
96 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.62 kW
18.38 kW
Annual energy consumption Qhe
11740 kWh
18156 kWh
Pdh Tj = -15°C (if TOL<-20°C)
14.49
13.56
COP Tj = -15°C (if TOL<-20°C)
2.42
1.21
Cdh Tj = -15 °C
0.90
0.90
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
71 dB(A)
71 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
181 %
125 %
Prated
17.99 kW
17.67 kW
SCOP
4.60
3.21
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
15.90 kW
15.61 kW
COP Tj = -7°C
2.85
1.72
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
9.66 kW
9.59 kW
COP Tj = +2°C
4.59
3.32
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
6.56 kW
6.37 kW
COP Tj = +7°C
5.99
4.48
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
3.76 kW
3.57 kW
COP Tj = 12°C
7.08
5.27
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
15.90 kW
15.61 kW
COP Tj = Tbiv
2.85
1.72
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
17.99 kW
15.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.49
1.17
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
18 W
18 W
PTO
96 W
96 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
2.64 kW
Annual energy consumption Qhe
8086 kWh
11375 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
22.30 kW
22.10 kW
El input
5.13 kW
8.33 kW
COP
4.35
2.65
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
73 dB(A)
73 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
234 %
161 %
Prated
21.90 kW
22.01 kW
SCOP
5.85
4.09
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
21.81 kW
22.01 kW
COP Tj = +2°C
3.31
2.12
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
14.08 kW
14.15 kW
COP Tj = +7°C
5.20
3.50
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
6.44 kW
6.38 kW
COP Tj = 12°C
7.50
5.34
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
14.08 kW
14.15 kW
COP Tj = Tbiv
5.20
3.50
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
21.81 kW
22.01 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.31
2.12
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
18 W
18 W
PTO
96 W
96 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.09 kW
0.00 kW
Annual energy consumption Qhe
4945 kWh
7180 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
73 dB(A)
73 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
146 %
102 %
Prated
21.40 kW
22.36 kW
SCOP
3.72
2.62
Tbiv
-15 °C
-7 °C
TOL
-22 °C
-15 °C
Pdh Tj = -7°C
13.30 kW
13.53 kW
COP Tj = -7°C
3.12
2.07
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
8.25 kW
8.61 kW
COP Tj = +2°C
4.42
3.70
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
5.45 kW
5.21 kW
COP Tj = +7°C
5.87
4.49
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.98 kW
3.74 kW
COP Tj = 12°C
7.19
5.76
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
17.46 kW
13.53 kW
COP Tj = Tbiv
2.36
2.07
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.27 kW
13.78 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.69
1.24
WTOL
60 °C
60 °C
Poff
20 W
20 W
PTO
96 W
96 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
8.13 kW
22.36 kW
Annual energy consumption Qhe
14179 kWh
21067 kWh
Pdh Tj = -15°C (if TOL<-20°C)
17.46
13.78
COP Tj = -15°C (if TOL<-20°C)
2.36
1.24
Cdh Tj = -15 °C
0.90
0.90
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
73 dB(A)
73 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
178 %
126 %
Prated
22.31 kW
22.43 kW
SCOP
4.53
3.22
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
19.72 kW
19.82 kW
COP Tj = -7°C
2.74
1.74
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
12.03 kW
11.89 kW
COP Tj = +2°C
4.41
3.32
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
8.00 kW
7.97 kW
COP Tj = +7°C
6.29
4.66
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
3.79 kW
3.60 kW
COP Tj = 12°C
7.14
5.32
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
19.72 kW
19.82 kW
COP Tj = Tbiv
2.74
1.74
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
20.33 kW
13.81 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.35
1.08
WTOL
60 °C
60 °C
Poff
18 W
18 W
PTO
96 W
96 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.97 kW
8.60 kW
Annual energy consumption Qhe
10180 kWh
14390 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
26.30 kW
26.06 kW
El input
6.50 kW
10.72 kW
COP
4.05
2.43
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
75 dB(A)
75 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
231 %
168 %
Prated
26.08 kW
26.22 kW
SCOP
5.85
4.26
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
25.50 kW
26.22 kW
COP Tj = +2°C
3.00
1.99
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
16.77 kW
16.86 kW
COP Tj = +7°C
5.02
3.47
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
7.65 kW
7.58 kW
COP Tj = 12°C
7.78
5.94
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
16.77 kW
16.86 kW
COP Tj = Tbiv
5.02
3.47
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
25.50 kW
26.22 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.00
1.99
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
WTOL
60 °C
60 °C
Poff
18 W
18 W
PTO
96 W
96 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.58 kW
0.00 kW
Annual energy consumption Qhe
5959 kWh
8218 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
75 dB(A)
75 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
143 %
101 %
Prated
25.75 kW
26.27 kW
SCOP
3.64
2.59
Tbiv
-12 °C
-7 °C
TOL
-22 °C
-15 °C
Pdh Tj = -7°C
15.91 kW
15.90 kW
COP Tj = -7°C
3.10
2.10
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
10.10 kW
10.17 kW
COP Tj = +2°C
4.45
3.58
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
6.30 kW
6.52 kW
COP Tj = +7°C
6.06
4.99
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
4.03 kW
3.63 kW
COP Tj = 12°C
7.13
5.68
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
18.97 kW
15.90 kW
COP Tj = Tbiv
2.36
2.10
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.07 kW
13.37 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.67
1.20
WTOL
60 °C
60 °C
Poff
20 W
20 W
PTO
96 W
96 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
12.68 kW
26.27 kW
Annual energy consumption Qhe
17421 kWh
24967 kWh
Pdh Tj = -15°C (if TOL<-20°C)
18.95
13.37
COP Tj = -15°C (if TOL<-20°C)
2.27
1.20
Cdh Tj = -15 °C
0.90
0.90
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
75 dB(A)
75 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
123 %
Prated
25.04 kW
26.15 kW
SCOP
4.50
3.14
Tbiv
-7 °C
-6 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
22.12 kW
20.64 kW
COP Tj = -7°C
2.57
1.69
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
13.76 kW
14.26 kW
COP Tj = +2°C
4.44
3.12
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
9.36 kW
9.29 kW
COP Tj = +7°C
6.52
4.74
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
4.09 kW
3.89 kW
COP Tj = 12°C
7.35
5.48
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
22.12 kW
22.11 kW
COP Tj = Tbiv
2.57
1.88
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
20.33 kW
13.86 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.35
1.08
WTOL
60 °C
60 °C
Poff
18 W
18 W
PTO
96 W
96 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.68 kW
12.28 kW
Annual energy consumption Qhe
11489 kWh
17204 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
29.93 kW
29.68 kW
El input
8.02 kW
12.97 kW
COP
3.73
2.29
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
77 dB(A)
77 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
213 %
163 %
Prated
30.44 kW
29.73 kW
SCOP
5.39
4.15
Tbiv
7 °C
7 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
26.29 kW
26.41 kW
COP Tj = +2°C
2.94
1.99
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
19.57 kW
19.11 kW
COP Tj = +7°C
4.75
3.37
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
8.90 kW
8.92 kW
COP Tj = 12°C
7.53
6.09
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
19.57 kW
19.11 kW
COP Tj = Tbiv
4.75
3.37
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
26.29 kW
26.41 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.94
1.99
WTOL
60 °C
60 °C
Poff
18 W
18 W
PTO
96 W
96 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
4.15 kW
3.32 kW
Annual energy consumption Qhe
7540 kWh
9580 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
77 dB(A)
77 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
138 %
100 %
Prated
29.13 kW
30.41 kW
SCOP
3.52
2.56
Tbiv
-10 °C
-7 °C
TOL
-22 °C
-15 °C
Pdh Tj = -7°C
18.49 kW
18.40 kW
COP Tj = -7°C
3.07
2.10
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
11.88 kW
11.22 kW
COP Tj = +2°C
4.42
3.51
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
7.53 kW
7.42 kW
COP Tj = +7°C
6.15
5.18
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
4.11 kW
3.64 kW
COP Tj = 12°C
6.87
5.73
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
19.93 kW
18.40 kW
COP Tj = Tbiv
2.44
2.10
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.17 kW
13.06 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.67
1.18
WTOL
60 °C
60 °C
Poff
18 W
18 W
PTO
96 W
96 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
15.96 kW
30.41 kW
Annual energy consumption Qhe
20390 kWh
29238 kWh
Pdh Tj = -15°C (if TOL<-20°C)
18.61
13.06
COP Tj = -15°C (if TOL<-20°C)
2.24
1.18
Cdh Tj = -15 °C
0.90
0.90
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
77 dB(A)
77 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
165 %
123 %
Prated
29.18 kW
29.69 kW
SCOP
4.19
3.14
Tbiv
-5 °C
-5 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
21.90 kW
20.11 kW
COP Tj = -7°C
2.54
1.63
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
16.16 kW
16.49 kW
COP Tj = +2°C
4.16
3.09
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
10.64 kW
10.50 kW
COP Tj = +7°C
6.38
4.75
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
4.54 kW
4.64 kW
COP Tj = 12°C
7.72
5.91
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
23.51 kW
23.97 kW
COP Tj = Tbiv
2.71
2.02
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
20.37 kW
13.82 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.35
1.07
WTOL
60 °C
60 °C
Poff
18 W
18 W
PTO
96 W
96 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
8.75 kW
15.86 kW
Annual energy consumption Qhe
14165 kWh
19316.17 kWh