Certificate holders

Subtype

ecoAIR EVI 4-20 kW

Certificate Holder
Ecoforest Geotermia S.L.
Rúa das Pontes, 25
36350 Nigrán (Pontevedra)
Spain
Registration number
011-1W0196
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
ecoAIR EVI 4-20 kW
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

3,500 kg

Certification Date
06.01.2020
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 2

Models

ECOAIR EVI 4-20kW
Configure model
Model name
ECOAIR EVI 4-20kW
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

9.22 kW

9.37 kW

El input

1.85 kW

2.82 kW

COP

4.97

3.33

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

0 dB(A)

0 dB(A)

Sound power level outdoor

63 dB(A)

63 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

207 %

159 %

Prated

13.70 kW

15.16 kW

SCOP

5.24

4.06

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

13.70 kW

15.16 kW

COP Tj = +2°C

3.11

2.42

Cdh Tj = +2 °C

0.990

1.000

Pdh Tj = +7°C

9.67 kW

10.03 kW

COP Tj = +7°C

5.11

3.78

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

4.57 kW

4.65 kW

COP Tj = 12°C

6.78

5.18

Cdh Tj = +12 °C

0.960

0.970

Pdh Tj = Tbiv

13.70 kW

15.16 kW

COP Tj = Tbiv

3.11

2.42

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.70 kW

15.16 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.11

2.42

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

1.000

WTOL

60 °C

60 °C

Poff

28 W

25 W

PTO

24 W

24 W

PSB

24 W

24 W

PCK

24 W

24 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3493 kWh

4994 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

0 dB(A)

0 dB(A)

Sound power level outdoor

63 dB(A)

63 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

167 %

157 %

Prated

12.00 kW

12.50 kW

SCOP

4.25

4.00

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

7.19 kW

7.67 kW

COP Tj = -7°C

4.15

3.33

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

4.66 kW

4.29 kW

COP Tj = +2°C

5.86

5.94

Cdh Tj = +2 °C

0.970

0.970

Pdh Tj = +7°C

4.15 kW

4.07 kW

COP Tj = +7°C

7.39

8.27

Cdh Tj = +7 °C

0.960

0.950

Pdh Tj = 12°C

4.54 kW

4.58 kW

COP Tj = 12°C

9.85

12.83

Cdh Tj = +12 °C

0.950

0.930

Pdh Tj = Tbiv

10.21 kW

10.05 kW

COP Tj = Tbiv

2.63

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.21 kW

10.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.63

2.15

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

0.990

WTOL

60 °C

60 °C

Poff

28 W

25 W

PTO

24 W

24 W

PSB

24 W

24 W

PCK

24 W

24 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

12.00 kW

12.50 kW

Annual energy consumption Qhe

6963 kWh

7705 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.21

10.05

COP Tj = -15°C (if TOL<-20°C)

2.63

2.15

Cdh Tj = -15 °C

0.990

0.990

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

0 dB(A)

0 dB(A)

Sound power level outdoor

63 dB(A)

63 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

180 %

151 %

Prated

13.23 kW

13.88 kW

SCOP

4.57

3.84

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.26 kW

11.95 kW

COP Tj = -7°C

3.34

2.66

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

7.62 kW

7.85 kW

COP Tj = +2°C

4.79

4.06

Cdh Tj = +2 °C

0.980

0.990

Pdh Tj = +7°C

5.38 kW

5.32 kW

COP Tj = +7°C

5.14

4.16

Cdh Tj = +7 °C

0.980

0.980

Pdh Tj = 12°C

4.50 kW

4.56 kW

COP Tj = 12°C

7.57

7.09

Cdh Tj = +12 °C

0.960

0.960

Pdh Tj = Tbiv

13.23 kW

13.88 kW

COP Tj = Tbiv

2.74

2.14

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.23 kW

13.88 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.74

2.14

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

28 W

25 W

PTO

24 W

24 W

PSB

24 W

24 W

PCK

24 W

24 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5983 kWh

7465 kWh

ECOAIR EVI T 4-20kW
Configure model
Model name
ECOAIR EVI T 4-20kW
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

9.22 kW

9.37 kW

El input

1.85 kW

2.82 kW

COP

4.97

3.33

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

0 dB(A)

0 dB(A)

Sound power level outdoor

63 dB(A)

63 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

207 %

159 %

Prated

13.70 kW

15.16 kW

SCOP

5.24

4.06

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

13.70 kW

15.16 kW

COP Tj = +2°C

3.11

2.42

Cdh Tj = +2 °C

0.990

1.000

Pdh Tj = +7°C

9.67 kW

10.03 kW

COP Tj = +7°C

5.11

3.78

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

4.57 kW

4.65 kW

COP Tj = 12°C

6.78

5.18

Cdh Tj = +12 °C

0.960

0.970

Pdh Tj = Tbiv

13.70 kW

15.16 kW

COP Tj = Tbiv

3.11

2.42

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.70 kW

15.16 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.11

2.42

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

1.000

WTOL

60 °C

60 °C

Poff

28 W

25 W

PTO

24 W

24 W

PSB

24 W

24 W

PCK

24 W

24 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3493 kWh

4994 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

0 dB(A)

0 dB(A)

Sound power level outdoor

63 dB(A)

63 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

167 %

157 %

Prated

12.00 kW

12.50 kW

SCOP

4.25

4.00

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

7.19 kW

7.67 kW

COP Tj = -7°C

4.15

3.33

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

4.66 kW

4.29 kW

COP Tj = +2°C

5.86

5.94

Cdh Tj = +2 °C

0.970

0.970

Pdh Tj = +7°C

4.15 kW

4.07 kW

COP Tj = +7°C

7.39

8.27

Cdh Tj = +7 °C

0.960

0.950

Pdh Tj = 12°C

4.54 kW

4.58 kW

COP Tj = 12°C

9.85

12.83

Cdh Tj = +12 °C

0.950

0.930

Pdh Tj = Tbiv

10.21 kW

10.05 kW

COP Tj = Tbiv

2.63

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.21 kW

10.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.63

2.15

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

0.990

WTOL

60 °C

60 °C

Poff

28 W

25 W

PTO

24 W

24 W

PSB

24 W

24 W

PCK

24 W

24 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

12.00 kW

12.50 kW

Annual energy consumption Qhe

6963 kWh

7705 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.21

10.05

COP Tj = -15°C (if TOL<-20°C)

2.63

2.15

Cdh Tj = -15 °C

0.990

0.990

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

0 dB(A)

0 dB(A)

Sound power level outdoor

63 dB(A)

63 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

180 %

151 %

Prated

13.23 kW

13.88 kW

SCOP

4.57

3.84

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

12.26 kW

11.95 kW

COP Tj = -7°C

3.34

2.66

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

7.62 kW

7.85 kW

COP Tj = +2°C

4.79

4.06

Cdh Tj = +2 °C

0.980

0.990

Pdh Tj = +7°C

5.38 kW

5.32 kW

COP Tj = +7°C

5.14

4.16

Cdh Tj = +7 °C

0.980

0.980

Pdh Tj = 12°C

4.50 kW

4.56 kW

COP Tj = 12°C

7.57

7.09

Cdh Tj = +12 °C

0.960

0.960

Pdh Tj = Tbiv

13.23 kW

13.88 kW

COP Tj = Tbiv

2.74

2.14

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.23 kW

13.88 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.74

2.14

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

60 °C

60 °C

Poff

28 W

25 W

PTO

24 W

24 W

PSB

24 W

24 W

PCK

24 W

24 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5983 kWh

7465 kWh