Certificate holders

Subtype

37. Yutaki S (N1) 10.0HP R410A (3ph)

Certificate Holder
Johnson Controls-Hitachi AirConditioning Spain
Ronda Shimizu, 1. Pol. Ind. Can Torrella
08233 Vacarisses, Barcelona
Spain
Registration number
041-K002-58
Certification Body
BRE Global Limited
Subtype title
37. Yutaki S (N1) 10.0HP R410A (3ph)
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

5,300 kg

Certification Date
08.02.2022
Testing basis
Heat Pump Keymark Scheme Rules Rev 09
Generate PDF Export model CSV Download certificate
  • Number of models 2

Models

01. RAS-10WHNPE RWM-10.0N1E - Heating Only
Configure model
Model name
01. RAS-10WHNPE RWM-10.0N1E - Heating Only
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

24.00 kW

24.00 kW

El input

5.59 kW

9.06 kW

COP

4.29

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

47 dB(A)

47 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

141 %

116 %

Prated

20.00 kW

18.00 kW

SCOP

3.60

2.98

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

17.40 kW

15.60 kW

COP Tj = -7°C

2.30

1.65

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

10.77 kW

9.50 kW

COP Tj = +2°C

3.60

3.10

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

8.70 kW

8.30 kW

COP Tj = +7°C

5.10

4.35

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

8.70 kW

8.50 kW

COP Tj = 12°C

4.90

4.60

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

17.40 kW

15.60 kW

COP Tj = Tbiv

2.10

1.65

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

18.00 kW

14.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.30

1.45

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

36 W

36 W

PTO

0 W

0 W

PSB

36 W

36 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.00 kW

4.00 kW

Annual energy consumption Qhe

11410 kWh

12210 kWh

02. RAS-10WHNPE RWM-10.0N1E - with cooling kit
Configure model
Model name
02. RAS-10WHNPE RWM-10.0N1E - with cooling kit
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

24.00 kW

24.00 kW

El input

5.59 kW

9.06 kW

COP

4.29

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

6.23 kW

5.54 kW

Cooling capacity

17.50

20.00

EER

2.81

3.61

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

17.50 kW

20.00 kW

SEER

4.06

5.44

Pdc Tj = 35°C

17.50 kW

20.00 kW

EER Tj = 35°C

2.81

3.61

Pdc Tj = 30°C

12.90 kW

14.74 kW

EER Tj = 30°C

3.53

5.50

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

8.20 kW

8.20 kW

EER Tj = 25°C

4.87

6.50

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

8.00 kW

8.50 kW

EER Tj = 20°C

5.50

6.60

Cdc Tj = 20 °C

0.900

0.900

Poff

36 W

36 W

PTO

0 W

0 W

PSB

36 W

36 W

PCK

0 W

0 W

Annual energy consumption Qce

1510 kWh

1286 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

47 dB(A)

47 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

142 %

118 %

Prated

20.00 kW

18.00 kW

SCOP

3.60

2.98

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

17.40 kW

15.60 kW

COP Tj = -7°C

2.30

1.65

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

10.77 kW

9.50 kW

COP Tj = +2°C

3.60

3.10

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

8.70 kW

8.30 kW

COP Tj = +7°C

5.10

4.35

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

8.70 kW

8.50 kW

COP Tj = 12°C

4.90

4.60

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

17.40 kW

15.60 kW

COP Tj = Tbiv

2.30

1.65

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

18.00 kW

14.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.30

1.45

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

36 W

36 W

PTO

0 W

0 W

PSB

36 W

36 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.00 kW

4.00 kW

Annual energy consumption Qhe

11278 kWh

12078 kWh