1,800 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.81 kW
8.97 kW
El input
1.96 kW
2.98 kW
COP
5.00
3.01
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
60 dB(A)
62 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
181 %
130 %
Prated
8.73 kW
9.51 kW
SCOP
4.61
3.32
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
7.72 kW
8.41 kW
COP Tj = -7°C
3.39
2.32
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.76 kW
5.13 kW
COP Tj = +2°C
4.38
3.20
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
4.20 kW
4.16 kW
COP Tj = +7°C
5.71
4.04
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
5.06 kW
4.26 kW
COP Tj = 12°C
7.11
5.53
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
7.72 kW
8.41 kW
COP Tj = Tbiv
3.39
2.32
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.90 kW
7.72 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.86
1.99
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
55 °C
55 °C
Poff
12 W
12 W
PTO
12 W
12 W
PSB
12 W
12 W
PCK
59 W
59 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.83 kW
1.79 kW
Annual energy consumption Qhe
3912 kWh
5918 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
9.76 kW
9.49 kW
El input
2.12 kW
3.90 kW
COP
4.61
2.43
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
58 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
183 %
131 %
Prated
8.73 kW
9.51 kW
SCOP
4.65
3.34
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
7.73 kW
8.41 kW
COP Tj = -7°C
3.39
2.30
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
4.73 kW
5.12 kW
COP Tj = +2°C
4.38
3.23
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
4.18 kW
4.11 kW
COP Tj = +7°C
5.72
3.99
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
4.62 kW
4.40 kW
COP Tj = 12°C
7.54
5.69
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
7.73 kW
8.41 kW
COP Tj = Tbiv
3.39
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.79 kW
9.20 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.99
2.09
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
0.990
WTOL
55 °C
55 °C
Poff
14 W
14 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
44 W
44 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.31 kW
Annual energy consumption Qhe
3877 kWh
5879 kWh