2,400 kg
Domestic Hot Water (DHW)
Warmer Climate
EN 12102-2
Sound power level indoor
16 dB(A)
Sound power level outdoor
65 dB(A)
EN 16147
Declared load profile
XL
Efficiency ηDHW
130 %
COP
3.20
Heating up time
2:35 h:min
Standby power input
29.0 W
Reference hot water temperature
52.8 °C
Mixed water at 40°C
360 l
Average Climate
EN 12102-2
Sound power level indoor
16 dB(A)
Sound power level outdoor
65 dB(A)
EN 16147
Declared load profile
XL
Efficiency ηDHW
117 %
COP
2.90
Heating up time
2:45 h:min
Standby power input
29.0 W
Reference hot water temperature
52.8 °C
Mixed water at 40°C
360 l
Operating test
EN 16147
Temperature operating range
passed
Safety devices checking test
passed
Condensate draining
passed