2,050 kg
Domestic Hot Water (DHW)
Warmer Climate
EN 12102-2
Sound power level indoor
16 dB(A)
Sound power level outdoor
63 dB(A)
EN 16147
Declared load profile
L
Efficiency ηDHW
136 %
COP
3.35
Heating up time
2:10 h:min
Standby power input
26.0 W
Reference hot water temperature
52.6 °C
Mixed water at 40°C
256 l
Average Climate
EN 12102-2
Sound power level indoor
16 dB(A)
Sound power level outdoor
63 dB(A)
EN 16147
Declared load profile
L
Efficiency ηDHW
126 %
COP
3.10
Heating up time
2:20 h:min
Standby power input
26.0 W
Reference hot water temperature
52.6 °C
Mixed water at 40°C
256 l
Operating test
EN 16147
Temperature operating range
passed
Safety devices checking test
passed
Condensate draining
passed