1,300 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.80 kW
4.16 kW
El input
1.41 kW
1.97 kW
COP
4.12
2.11
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153 %
111 %
Prated
4.73 kW
3.51 kW
SCOP
3.89
2.85
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.18 kW
3.10 kW
COP Tj = -7°C
2.47
1.70
Pdh Tj = +2°C
2.49 kW
1.95 kW
COP Tj = +2°C
3.79
2.85
Pdh Tj = +7°C
1.66 kW
1.43 kW
COP Tj = +7°C
5.21
3.85
Pdh Tj = 12°C
1.16 kW
1.29 kW
COP Tj = 12°C
6.39
5.24
Pdh Tj = Tbiv
4.18 kW
3.10 kW
COP Tj = Tbiv
2.47
1.70
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.62 kW
2.19 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.03
1.12
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
5 W
5 W
PTO
8 W
8 W
PSB
5 W
5 W
PCK
35 W
35 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.11 kW
1.32 kW
Annual energy consumption Qhe
2509 kWh
2546 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
91 %
COP
2.18
Heating up time
4:04 h:min
Standby power input
54.3 W
Reference hot water temperature
46.7 °C
Mixed water at 40°C
364 l