4,300 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
21.30 kW
19.80 kW
El input
4.92 kW
7.51 kW
COP
4.33
2.64
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
5.86 kW
Cooling capacity
17.70
EER
3.02
EN 14825
+7°C/+12°C
Pdesignc
17.67 kW
SEER
4.44
Pdc Tj = 35°C
17.70 kW
EER Tj = 35°C
3.02
Pdc Tj = 30°C
12.94 kW
EER Tj = 30°C
4.03
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
8.82 kW
EER Tj = 25°C
4.89
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
9.53 kW
EER Tj = 20°C
5.94
Cdc Tj = 20 °C
0.900
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
2389 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
165 %
122 %
Prated
20.00 kW
19.00 kW
SCOP
4.20
3.14
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-10 °C
Pdh Tj = -7°C
17.30 kW
17.00 kW
COP Tj = -7°C
2.54
1.86
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
10.60 kW
10.50 kW
COP Tj = +2°C
4.24
3.13
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
9.30 kW
9.20 kW
COP Tj = +7°C
5.15
3.94
Cdh Tj = +7 °C
0.992
0.995
Pdh Tj = 12°C
10.90 kW
10.80 kW
COP Tj = 12°C
7.08
5.51
Cdh Tj = +12 °C
0.990
0.994
Pdh Tj = Tbiv
17.30 kW
17.00 kW
COP Tj = Tbiv
2.54
1.86
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.50 kW
15.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.31
1.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
4.50 kW
3.90 kW
Annual energy consumption Qhe
9608 kWh
12663 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
26.00 kW
25.10 kW
El input
6.44 kW
9.51 kW
COP
4.04
2.64
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
6.19 kW
Cooling capacity
18.69
EER
3.02
EN 14825
+7°C/+12°C
Pdesignc
18.69 kW
SEER
4.55
Pdc Tj = 35°C
18.69 kW
EER Tj = 35°C
3.02
Pdc Tj = 30°C
13.69 kW
EER Tj = 30°C
4.15
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
9.00 kW
EER Tj = 25°C
5.00
Cdc Tj = 25 °C
0.900
Pdc Tj = 20°C
9.74 kW
EER Tj = 20°C
6.06
Cdc Tj = 20 °C
0.900
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
2465 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
155 %
123 %
Prated
20.00 kW
19.00 kW
SCOP
3.95
3.14
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-10 °C
Pdh Tj = -7°C
17.40 kW
17.00 kW
COP Tj = -7°C
2.49
1.89
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
10.60 kW
10.50 kW
COP Tj = +2°C
3.93
3.09
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
9.30 kW
9.30 kW
COP Tj = +7°C
4.88
4.03
Cdh Tj = +7 °C
0.992
0.993
Pdh Tj = 12°C
10.70 kW
10.90 kW
COP Tj = 12°C
6.53
5.62
Cdh Tj = +12 °C
0.991
0.992
Pdh Tj = Tbiv
17.40 kW
17.00 kW
COP Tj = Tbiv
2.49
1.89
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
15.40 kW
15.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.27
1.68
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
4.60 kW
3.70 kW
Annual energy consumption Qhe
10286 kWh
12652 kWh