14,000 kg
Heating
EN 14511-2
Heat output
48.60 kW
El input
12.12 kW
COP
4.01
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Average Climate
EN 12102-1
Sound power level outdoor
84 dB(A)
EN 14825
ηs
154 %
Prated
31.00 kW
SCOP
3.91
Tbiv
-10 °C
TOL
-10 °C
Pdh Tj = -7°C
27.80 kW
COP Tj = -7°C
2.72
Cdh Tj = -7 °C
0.90
Pdh Tj = +2°C
16.90 kW
COP Tj = +2°C
3.85
Cdh Tj = +2 °C
0.90
Pdh Tj = +7°C
10.90 kW
COP Tj = +7°C
4.90
Cdh Tj = +7 °C
0.90
Pdh Tj = 12°C
14.20 kW
COP Tj = 12°C
6.02
Cdh Tj = +12 °C
0.90
Pdh Tj = Tbiv
31.40 kW
COP Tj = Tbiv
2.42
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
31.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.42
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
WTOL
54 °C
Poff
30 W
PTO
404 W
PSB
30 W
PCK
0 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.00 kW
Annual energy consumption Qhe
16591 kWh