3,400 kg
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
16.00 kW
El input
3.50 kW
6.40 kW
COP
4.57
2.50
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
152 %
125 %
Prated
16.00 kW
14.00 kW
SCOP
3.88
3.20
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.80 kW
11.20 kW
COP Tj = -7°C
2.40
1.60
Pdh Tj = +2°C
8.40 kW
6.82 kW
COP Tj = +2°C
3.90
3.35
Pdh Tj = +7°C
5.40 kW
4.38 kW
COP Tj = +7°C
5.00
4.35
Pdh Tj = 12°C
3.50 kW
3.60 kW
COP Tj = 12°C
6.00
5.50
Pdh Tj = Tbiv
13.80 kW
11.20 kW
COP Tj = Tbiv
2.40
1.60
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
14.10 kW
10.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
1.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
19 W
19 W
PTO
0 W
0 W
PSB
19 W
19 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
3.10 kW
Annual energy consumption Qhe
8309 kWh
8802 kWh
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
16.00 kW
El input
3.50 kW
6.40 kW
COP
4.57
2.50
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
152 %
125 %
Prated
16.00 kW
14.00 kW
SCOP
3.88
3.20
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.80 kW
11.20 kW
COP Tj = -7°C
2.40
1.60
Pdh Tj = +2°C
8.40 kW
6.82 kW
COP Tj = +2°C
3.90
3.35
Pdh Tj = +7°C
5.40 kW
4.38 kW
COP Tj = +7°C
5.00
4.35
Pdh Tj = 12°C
3.50 kW
3.60 kW
COP Tj = 12°C
6.00
5.50
Pdh Tj = Tbiv
13.80 kW
11.20 kW
COP Tj = Tbiv
2.40
1.60
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
14.10 kW
10.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
1.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
19 W
19 W
PTO
0 W
0 W
PSB
19 W
19 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
3.10 kW
Annual energy consumption Qhe
8309 kWh
8802 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
130 %
COP
3.25
Heating up time
1:10 h:min
Standby power input
49.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
263 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
16.00 kW
El input
3.50 kW
6.40 kW
COP
4.57
2.50
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
152 %
125 %
Prated
16.00 kW
14.00 kW
SCOP
3.88
3.20
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.80 kW
11.20 kW
COP Tj = -7°C
2.40
1.60
Pdh Tj = +2°C
8.40 kW
6.82 kW
COP Tj = +2°C
3.90
3.35
Pdh Tj = +7°C
5.40 kW
4.38 kW
COP Tj = +7°C
5.00
4.35
Pdh Tj = 12°C
3.50 kW
3.60 kW
COP Tj = 12°C
6.00
5.50
Pdh Tj = Tbiv
13.80 kW
11.20 kW
COP Tj = Tbiv
2.40
1.60
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
14.10 kW
10.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
1.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
19 W
19 W
PTO
0 W
0 W
PSB
19 W
19 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
3.10 kW
Annual energy consumption Qhe
8309 kWh
8802 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
134 %
COP
3.35
Heating up time
1:25 h:min
Standby power input
51.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
350 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
16.00 kW
El input
3.50 kW
6.40 kW
COP
4.57
2.50
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
152 %
125 %
Prated
16.00 kW
14.00 kW
SCOP
3.88
3.20
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.80 kW
11.20 kW
COP Tj = -7°C
2.40
1.60
Pdh Tj = +2°C
8.40 kW
6.82 kW
COP Tj = +2°C
3.90
3.35
Pdh Tj = +7°C
5.40 kW
4.38 kW
COP Tj = +7°C
5.00
4.35
Pdh Tj = 12°C
3.50 kW
3.60 kW
COP Tj = 12°C
6.00
5.50
Pdh Tj = Tbiv
13.80 kW
11.20 kW
COP Tj = Tbiv
2.40
1.60
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
14.10 kW
10.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
1.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
19 W
19 W
PTO
0 W
0 W
PSB
19 W
19 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
3.10 kW
Annual energy consumption Qhe
8309 kWh
8802 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
130 %
COP
3.25
Heating up time
1:10 h:min
Standby power input
49.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
263 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
16.00 kW
El input
3.50 kW
6.40 kW
COP
4.57
2.50
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
152 %
125 %
Prated
16.00 kW
14.00 kW
SCOP
3.88
3.20
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.80 kW
11.20 kW
COP Tj = -7°C
2.40
1.60
Pdh Tj = +2°C
8.40 kW
6.82 kW
COP Tj = +2°C
3.90
3.35
Pdh Tj = +7°C
5.40 kW
4.38 kW
COP Tj = +7°C
5.00
4.35
Pdh Tj = 12°C
3.50 kW
3.60 kW
COP Tj = 12°C
6.00
5.50
Pdh Tj = Tbiv
13.80 kW
11.20 kW
COP Tj = Tbiv
2.40
1.60
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
14.10 kW
10.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
1.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
19 W
19 W
PTO
0 W
0 W
PSB
19 W
19 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
3.10 kW
Annual energy consumption Qhe
8309 kWh
8802 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
134 %
COP
3.35
Heating up time
1:25 h:min
Standby power input
51.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
350 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
16.00 kW
El input
3.50 kW
6.40 kW
COP
4.57
2.50
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
152 %
125 %
Prated
16.00 kW
14.00 kW
SCOP
3.88
3.20
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.80 kW
11.20 kW
COP Tj = -7°C
2.40
1.60
Pdh Tj = +2°C
8.40 kW
6.82 kW
COP Tj = +2°C
3.90
3.35
Pdh Tj = +7°C
5.40 kW
4.38 kW
COP Tj = +7°C
5.00
4.35
Pdh Tj = 12°C
3.50 kW
3.60 kW
COP Tj = 12°C
6.00
5.50
Pdh Tj = Tbiv
13.80 kW
11.20 kW
COP Tj = Tbiv
2.40
1.60
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
14.10 kW
10.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
1.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
19 W
19 W
PTO
0 W
0 W
PSB
19 W
19 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
3.10 kW
Annual energy consumption Qhe
8309 kWh
8802 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
134 %
COP
3.35
Heating up time
1:25 h:min
Standby power input
51.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
350 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
16.00 kW
El input
3.50 kW
6.40 kW
COP
4.57
2.50
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153 %
126 %
Prated
16.00 kW
14.00 kW
SCOP
3.90
3.23
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.80 kW
11.20 kW
COP Tj = -7°C
2.40
1.60
Pdh Tj = +2°C
8.40 kW
6.82 kW
COP Tj = +2°C
3.90
3.35
Pdh Tj = +7°C
5.40 kW
4.38 kW
COP Tj = +7°C
5.00
4.35
Pdh Tj = 12°C
3.50 kW
3.60 kW
COP Tj = 12°C
6.00
5.50
Pdh Tj = Tbiv
13.80 kW
11.20 kW
COP Tj = Tbiv
2.40
1.60
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
14.10 kW
10.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
1.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
19 W
19 W
PTO
0 W
0 W
PSB
19 W
19 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
3.10 kW
Annual energy consumption Qhe
8239 kWh
8732 kWh
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
16.00 kW
El input
3.50 kW
6.40 kW
COP
4.57
2.50
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153 %
126 %
Prated
16.00 kW
14.00 kW
SCOP
3.90
3.23
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.80 kW
11.20 kW
COP Tj = -7°C
2.40
1.60
Pdh Tj = +2°C
8.40 kW
6.82 kW
COP Tj = +2°C
3.90
3.35
Pdh Tj = +7°C
5.40 kW
4.38 kW
COP Tj = +7°C
5.00
4.35
Pdh Tj = 12°C
3.50 kW
3.60 kW
COP Tj = 12°C
6.00
5.50
Pdh Tj = Tbiv
13.80 kW
11.20 kW
COP Tj = Tbiv
2.40
1.60
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
14.10 kW
10.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
1.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
19 W
19 W
PTO
0 W
0 W
PSB
19 W
19 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
3.10 kW
Annual energy consumption Qhe
8239 kWh
8732 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
130 %
COP
3.25
Heating up time
1:10 h:min
Standby power input
49.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
263 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
16.00 kW
El input
3.50 kW
6.40 kW
COP
4.57
2.50
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153 %
126 %
Prated
16.00 kW
14.00 kW
SCOP
3.90
3.23
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.80 kW
11.20 kW
COP Tj = -7°C
2.40
1.60
Pdh Tj = +2°C
8.40 kW
6.82 kW
COP Tj = +2°C
3.90
3.35
Pdh Tj = +7°C
5.40 kW
4.38 kW
COP Tj = +7°C
5.00
4.35
Pdh Tj = 12°C
3.50 kW
3.60 kW
COP Tj = 12°C
6.00
5.50
Pdh Tj = Tbiv
13.80 kW
11.20 kW
COP Tj = Tbiv
2.40
1.60
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
14.10 kW
10.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
1.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
19 W
19 W
PTO
0 W
0 W
PSB
19 W
19 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
3.10 kW
Annual energy consumption Qhe
8239 kWh
8732 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
134 %
COP
3.35
Heating up time
1:25 h:min
Standby power input
51.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
350 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
16.00 kW
El input
3.50 kW
6.40 kW
COP
4.57
2.50
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
67 dB(A)
67 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
153 %
126 %
Prated
16.00 kW
14.00 kW
SCOP
3.90
3.23
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.80 kW
11.20 kW
COP Tj = -7°C
2.40
1.60
Pdh Tj = +2°C
8.40 kW
6.82 kW
COP Tj = +2°C
3.90
3.35
Pdh Tj = +7°C
5.40 kW
4.38 kW
COP Tj = +7°C
5.00
4.35
Pdh Tj = 12°C
3.50 kW
3.60 kW
COP Tj = 12°C
6.00
5.50
Pdh Tj = Tbiv
13.80 kW
11.20 kW
COP Tj = Tbiv
2.40
1.60
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
14.10 kW
10.50 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
1.40
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
19 W
19 W
PTO
0 W
0 W
PSB
19 W
19 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
3.10 kW
Annual energy consumption Qhe
8239 kWh
8732 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
134 %
COP
3.35
Heating up time
1:25 h:min
Standby power input
51.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
350 l